Deck 3: Determining the Required Number of Branch Circuits, Lighting Outlets, Receptacle Outlets

ملء الشاشة (f)
exit full mode
سؤال
How is track lighting load in residences calculated?

A) It is calculated at 150 volt-amperes per each two feet of track.
B) It is calculated at 60 watts per lighting head.
C) It is considered to be part of the general lighting load of 3 volt-amperes per square foot.
D) The method of calculation varies depending on the type of residence.
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
The NEC defines a ____ as "the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)."

A) receptacle outlet
B) branch circuit
C) service-entrance conductor
D) feeder
سؤال
List two cases where receptacles may be installed below countertops.
سؤال
Wall receptacles in a habitable room must be placed so they are no further than ____ feet from any point along the wall.

A) 3
B) 5
C) 6
D) 12
سؤال
Most public service commissions require that the voltage for residential services be held to ± ____ percent of the nominal voltage as measured at the service point.

A) three
B) five
C) eight
D) ten
سؤال
Explain what is meant by a nominal voltage rating.
سؤال
List the two cases where outdoor receptacles are exempt from GFCI protection.
سؤال
With the exception of ____, the 20-ampere appliance circuits required by NEC are permitted to serve no other loads.

A) clock outlets
B) receptacles that are installed to plug in the cords of gas-fired ranges, ovens, or counter-mounted cooking units
C) receptacles in bathrooms
D) receptacles in a master bedroom
سؤال
What are the outdoor receptacle requirements of a one-family dwelling as specified in NEC 210.52(E)(1)?
سؤال
Explain the difference between a receptacle and a receptacle outlet.
سؤال
Which of the following is NOT included when calculating the usable area of a dwelling to compute the required lighting load?

A) living room
B) crawl space
C) unfinished basement
D) powder rooms
سؤال
Where there are _________________________ or more on an interior stairway, a wall-switch control of the stairway lighting must be provided on each floor level and any level that has an entryway.
سؤال
The general lighting load for a dwelling is based on the ____.

A) total number of rooms
B) city ordinance requirements
C) family lifestyle needs
D) square footage of the dwelling
سؤال
The National Electrical Code requires outdoor receptacles to be ____.

A) AFCI protected
B) GFCI protected
C) on a dedicated circuit
D) b and c
سؤال
What determines the rating of a branch circuit?

A) Branch-circuit wire size
B) Rating of the overcurrent device
C) Length of the circuit
D) Total number of receptacles
سؤال
A continuous load shall not exceed ____ percent of the rating of the branch circuit.

A) 50
B) 80
C) 100
D) 125
سؤال
The minimum lighting load requirement for dwelling units is ____ volt-amperes per square ft (0.093 m3).

A) 2
B) 3
C) 5
D) 10
سؤال
For continuous loads, the branch-circuit rating, the conductors, and the overcurrent device shall not be less than ____ percent of the rating of the equipment.

A) 75
B) 100
C) 125
D) 150
سؤال
In construction of one- and two-family dwellings, the electrical circuits are usually designed by the ____.

A) electrician
B) architect
C) consulting engineer
D) project manager
سؤال
Calculate the minimum number of 15-ampere lighting branch circuits required in a residence of 1,850 square feet.
سؤال
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Bathroom
سؤال
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Crawl space (contains equipment that requires servicing)
سؤال
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Hallway
سؤال
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Attic (not intended for storage)
سؤال
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Stairway
سؤال
Receptacles in unfinished basements must be ____________________ protected.
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/26
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 3: Determining the Required Number of Branch Circuits, Lighting Outlets, Receptacle Outlets
1
How is track lighting load in residences calculated?

A) It is calculated at 150 volt-amperes per each two feet of track.
B) It is calculated at 60 watts per lighting head.
C) It is considered to be part of the general lighting load of 3 volt-amperes per square foot.
D) The method of calculation varies depending on the type of residence.
C
2
The NEC defines a ____ as "the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)."

A) receptacle outlet
B) branch circuit
C) service-entrance conductor
D) feeder
B
3
List two cases where receptacles may be installed below countertops.
Receptacles may be installed below countertops only:
- where the construction is for the physically impaired, or
- for island and peninsula countertop spaces where the countertop is flat across its entire surface and there is no way to mount a receptacle within 20 in. (500 mm) above the countertop.
4
Wall receptacles in a habitable room must be placed so they are no further than ____ feet from any point along the wall.

A) 3
B) 5
C) 6
D) 12
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
5
Most public service commissions require that the voltage for residential services be held to ± ____ percent of the nominal voltage as measured at the service point.

A) three
B) five
C) eight
D) ten
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
6
Explain what is meant by a nominal voltage rating.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
7
List the two cases where outdoor receptacles are exempt from GFCI protection.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
8
With the exception of ____, the 20-ampere appliance circuits required by NEC are permitted to serve no other loads.

A) clock outlets
B) receptacles that are installed to plug in the cords of gas-fired ranges, ovens, or counter-mounted cooking units
C) receptacles in bathrooms
D) receptacles in a master bedroom
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
9
What are the outdoor receptacle requirements of a one-family dwelling as specified in NEC 210.52(E)(1)?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
10
Explain the difference between a receptacle and a receptacle outlet.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
11
Which of the following is NOT included when calculating the usable area of a dwelling to compute the required lighting load?

A) living room
B) crawl space
C) unfinished basement
D) powder rooms
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
12
Where there are _________________________ or more on an interior stairway, a wall-switch control of the stairway lighting must be provided on each floor level and any level that has an entryway.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
13
The general lighting load for a dwelling is based on the ____.

A) total number of rooms
B) city ordinance requirements
C) family lifestyle needs
D) square footage of the dwelling
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
14
The National Electrical Code requires outdoor receptacles to be ____.

A) AFCI protected
B) GFCI protected
C) on a dedicated circuit
D) b and c
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
15
What determines the rating of a branch circuit?

A) Branch-circuit wire size
B) Rating of the overcurrent device
C) Length of the circuit
D) Total number of receptacles
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
16
A continuous load shall not exceed ____ percent of the rating of the branch circuit.

A) 50
B) 80
C) 100
D) 125
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
17
The minimum lighting load requirement for dwelling units is ____ volt-amperes per square ft (0.093 m3).

A) 2
B) 3
C) 5
D) 10
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
18
For continuous loads, the branch-circuit rating, the conductors, and the overcurrent device shall not be less than ____ percent of the rating of the equipment.

A) 75
B) 100
C) 125
D) 150
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
19
In construction of one- and two-family dwellings, the electrical circuits are usually designed by the ____.

A) electrician
B) architect
C) consulting engineer
D) project manager
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
20
Calculate the minimum number of 15-ampere lighting branch circuits required in a residence of 1,850 square feet.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
21
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Bathroom
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
22
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Crawl space (contains equipment that requires servicing)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
23
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Hallway
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
24
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Attic (not intended for storage)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
25
The Code specifies which rooms in a dwelling are required to have switched lighting outlets or switched receptacles. Choose yes (switch required) or no (switch not required) for the following areas:
a.Yes
b.No
Stairway
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
26
Receptacles in unfinished basements must be ____________________ protected.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.
فتح الحزمة
k this deck
locked card icon
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 26 في هذه المجموعة.