Deck 17: Industrial Locations

ملء الشاشة (f)
exit full mode
سؤال
____ branch circuits shall be protected at the motor nameplate current rating.

A) Transformer
B) HVAC
C) Torque motor
D) Circuit breaker
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
Barriers are required in all service-entrance motor-control centers to ____ and terminals from the remainder of the motor-control center.

A) isolate service busbars
B) connect the branch circuit
C) provide protection to the motor
D) isolate vertical sections
سؤال
The tap conductor's ampacity shall not be less than the ____ on the circuits it supplies.

A) inverse of the total load
B) combined calculated loads
C) total capacity for the circuit breaker
D) rating for the combined wires
سؤال
Motor circuits rated 1000 volts, nominal, or less, shall have a disconnecting means with an ampere rating of at least ____% of the motor's full-load current rating.

A) 75
B) 90
C) 115
D) 150
سؤال
Cable tray systems should be ____.

A) watertight
B) insulated from frost damage
C) mounted at least 8 ft above grade
D) corrosion resistant
سؤال
For the 10-ft feeder tap rule, a 60-ampere rated conductor is the minimum size allowed if the overcurrent protection on the tap conductor's line side is ____.

A) 300 amperes
B) 500 amperes
C) 600 amperes
D) 800 amperes
سؤال
Means shall be provided to disconnect all conductors in a building (or other structure) from the ____.

A) main feeder line
B) auxiliary panelboard
C) primary panelboard
D) service-entrance conductors
سؤال
Knife switches rated more than ____, and at over 1000 amperes at 251 to 1000 volts, shall be used only as isolating switches and shall not be opened under load.

A) 1000 amperes at 250 volts or less
B) 1100 amperes at 200 volts or less
C) 1200 amperes at 250 volts or less
D) 1200 amperes at 200 volts or less
سؤال
Cartridge fuse and fuseholder overcurrent protection provisions are located in ____.

A) 240.12
B) 240.21
C) 240.60 through 240.67
D) 404.8 and 404.13
سؤال
Wherever such an arrangement is practicable, transformer vaults shall be located so that ____.

A) they are directly under the main service line entrance
B) all junction boxes are adjacent to them on a vertical line
C) ventilation to outside air does not rely on flues or ducts
D) all junction boxes are adjacent to them on a horizontal line
سؤال
The combined length of one primary plus one secondary conductor (excluding any portion of the primary conductor protected at its ampacity) shall not exceed ____.

A) 5 ft (1.5 m)
B) 10 ft (3.0 m)
C) 15 ft (4.6 m)
D) 25 ft (7.5 m)
سؤال
A transformer vault door must be ____.

A) made of dual layer steel
B) equipped with fully engaged locks
C) installed with a door sill
D) accessible to all
سؤال
For the 25-ft feeder tap rule, a ____ is the minimum size allowed if the overcurrent protection on the tap conductor's line side is 600 amperes.

A) 100-ampere rated conductor
B) 200-ampere rated conductor
C) 300-ampere rated conductor
D) 400-ampere rated conductor
سؤال
Where an orderly shutdown is required to minimize the personnel/equipment hazard(s), a system of coordination based on the following two conditions is permitted: (1) coordinated short-circuit protection and (2) ____.

A) overload indication based on monitoring systems or devices
B) coordinated service (a single main feeder line)
C) a single switching source
D) integrated circuitry
سؤال
A tap conductor is a ____ that exceeds the value permitted for similar conductors protected as otherwise described in 240.4.

A) conductor other than a service conductor having overcurrent protection ahead of its point of supply
B) switch that redirects service to a branch having a total capacity
C) spliced line having an average peak load
D) dual-phase system having branches to an overload system
سؤال
To calculate the ampacity of conductors supplying several motors (feeder conductors), multiply the largest motor full-load current (FLC) rating by ____% and add the FLC ratings of all other motors (or loads) in the group.

A) 90
B) 100
C) 115
D) 125
سؤال
Overload is defined as operation of equipment in excess of normal, full-load rating, or of a conductor ____ that, when it persists for a sufficient length of time, would cause damage or dangerous overheating.

A) at 75% of rated ampacity
B) in excess of rated ampacity
C) at 90% of rated ampacity
D) in excess calculated peak voltage
سؤال
If the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the supply-side bonding jumper shall have an area not less than ____ percent of the area of the largest ungrounded supply conductor or equivalent area for parallel supply conductors.

A) 10.5
B) 12.5
C) 12.75
D) 14.0
سؤال
A transformer's primary conductors shall have an ampacity at least ____ of the feeder conductors' overcurrent device rating.

A) one-third
B) one-half
C) three-quarters
D) two-thirds
سؤال
If a single raceway or cable tray is used to supply the equipment, only one ____ is required.

A) 3/0 AWG copper
B) 4/0 AWG copper
C) 5/0 AWG copper
D) 6/0 AWG copper
سؤال
Conductors used in the secondary circuit of electric welders shall have ____.

A) polymer insulation
B) flame-retardant insulation
C) hybrid insulation
D) terminal busbars
سؤال
Where multiple power supplies serve the same dc system, the dc side of each power supply shall have a ____.

A) disconnecting means
B) suitable ground
C) removable conductor
D) removable fuses
سؤال
Minimum ampacity of arc welder conductors supplying a group of welders shall be based on ____ as determined in 630.11(A).

A) total branch capacity
B) aggregate load
C) individual resistances
D) individual currents
سؤال
The capacitor circuit conductor's ampacity shall be at least ____% of the capacitor's rated current.

A) 100
B) 125
C) 135
D) 150
سؤال
If a crane, hoist, or monorail hoist operates above readily combustible material, specific requirements shall apply to ____.

A) capacitors
B) resistors
C) overload protection
D) receptacle placement
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/25
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 17: Industrial Locations
1
____ branch circuits shall be protected at the motor nameplate current rating.

A) Transformer
B) HVAC
C) Torque motor
D) Circuit breaker
C
2
Barriers are required in all service-entrance motor-control centers to ____ and terminals from the remainder of the motor-control center.

A) isolate service busbars
B) connect the branch circuit
C) provide protection to the motor
D) isolate vertical sections
A
3
The tap conductor's ampacity shall not be less than the ____ on the circuits it supplies.

A) inverse of the total load
B) combined calculated loads
C) total capacity for the circuit breaker
D) rating for the combined wires
B
4
Motor circuits rated 1000 volts, nominal, or less, shall have a disconnecting means with an ampere rating of at least ____% of the motor's full-load current rating.

A) 75
B) 90
C) 115
D) 150
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
5
Cable tray systems should be ____.

A) watertight
B) insulated from frost damage
C) mounted at least 8 ft above grade
D) corrosion resistant
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
6
For the 10-ft feeder tap rule, a 60-ampere rated conductor is the minimum size allowed if the overcurrent protection on the tap conductor's line side is ____.

A) 300 amperes
B) 500 amperes
C) 600 amperes
D) 800 amperes
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
7
Means shall be provided to disconnect all conductors in a building (or other structure) from the ____.

A) main feeder line
B) auxiliary panelboard
C) primary panelboard
D) service-entrance conductors
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
8
Knife switches rated more than ____, and at over 1000 amperes at 251 to 1000 volts, shall be used only as isolating switches and shall not be opened under load.

A) 1000 amperes at 250 volts or less
B) 1100 amperes at 200 volts or less
C) 1200 amperes at 250 volts or less
D) 1200 amperes at 200 volts or less
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
9
Cartridge fuse and fuseholder overcurrent protection provisions are located in ____.

A) 240.12
B) 240.21
C) 240.60 through 240.67
D) 404.8 and 404.13
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
10
Wherever such an arrangement is practicable, transformer vaults shall be located so that ____.

A) they are directly under the main service line entrance
B) all junction boxes are adjacent to them on a vertical line
C) ventilation to outside air does not rely on flues or ducts
D) all junction boxes are adjacent to them on a horizontal line
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
11
The combined length of one primary plus one secondary conductor (excluding any portion of the primary conductor protected at its ampacity) shall not exceed ____.

A) 5 ft (1.5 m)
B) 10 ft (3.0 m)
C) 15 ft (4.6 m)
D) 25 ft (7.5 m)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
12
A transformer vault door must be ____.

A) made of dual layer steel
B) equipped with fully engaged locks
C) installed with a door sill
D) accessible to all
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
13
For the 25-ft feeder tap rule, a ____ is the minimum size allowed if the overcurrent protection on the tap conductor's line side is 600 amperes.

A) 100-ampere rated conductor
B) 200-ampere rated conductor
C) 300-ampere rated conductor
D) 400-ampere rated conductor
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
14
Where an orderly shutdown is required to minimize the personnel/equipment hazard(s), a system of coordination based on the following two conditions is permitted: (1) coordinated short-circuit protection and (2) ____.

A) overload indication based on monitoring systems or devices
B) coordinated service (a single main feeder line)
C) a single switching source
D) integrated circuitry
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
15
A tap conductor is a ____ that exceeds the value permitted for similar conductors protected as otherwise described in 240.4.

A) conductor other than a service conductor having overcurrent protection ahead of its point of supply
B) switch that redirects service to a branch having a total capacity
C) spliced line having an average peak load
D) dual-phase system having branches to an overload system
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
16
To calculate the ampacity of conductors supplying several motors (feeder conductors), multiply the largest motor full-load current (FLC) rating by ____% and add the FLC ratings of all other motors (or loads) in the group.

A) 90
B) 100
C) 115
D) 125
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
17
Overload is defined as operation of equipment in excess of normal, full-load rating, or of a conductor ____ that, when it persists for a sufficient length of time, would cause damage or dangerous overheating.

A) at 75% of rated ampacity
B) in excess of rated ampacity
C) at 90% of rated ampacity
D) in excess calculated peak voltage
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
18
If the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the supply-side bonding jumper shall have an area not less than ____ percent of the area of the largest ungrounded supply conductor or equivalent area for parallel supply conductors.

A) 10.5
B) 12.5
C) 12.75
D) 14.0
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
19
A transformer's primary conductors shall have an ampacity at least ____ of the feeder conductors' overcurrent device rating.

A) one-third
B) one-half
C) three-quarters
D) two-thirds
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
20
If a single raceway or cable tray is used to supply the equipment, only one ____ is required.

A) 3/0 AWG copper
B) 4/0 AWG copper
C) 5/0 AWG copper
D) 6/0 AWG copper
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
21
Conductors used in the secondary circuit of electric welders shall have ____.

A) polymer insulation
B) flame-retardant insulation
C) hybrid insulation
D) terminal busbars
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
22
Where multiple power supplies serve the same dc system, the dc side of each power supply shall have a ____.

A) disconnecting means
B) suitable ground
C) removable conductor
D) removable fuses
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
23
Minimum ampacity of arc welder conductors supplying a group of welders shall be based on ____ as determined in 630.11(A).

A) total branch capacity
B) aggregate load
C) individual resistances
D) individual currents
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
24
The capacitor circuit conductor's ampacity shall be at least ____% of the capacitor's rated current.

A) 100
B) 125
C) 135
D) 150
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
25
If a crane, hoist, or monorail hoist operates above readily combustible material, specific requirements shall apply to ____.

A) capacitors
B) resistors
C) overload protection
D) receptacle placement
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
locked card icon
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.