سؤال
A drip loop's lowest point has a minimum vertical clearance of ____.

A) 4 ft (1.2 m)
B) 6 ft (1.8 m)
C) 8 ft (2.4 m)
D) 10 ft (3.0 m)
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
Service conductors supplying a building (or other structure) shall not ____.

A) terminate in a panel
B) be enclosed in a six-gang enclosure
C) pass through the interior of another building
D) have less than two disconnects
سؤال
The vertical clearance above roof level must be maintained for a distance of at least ____ from all edges of the roof.

A) 3 ft (900 mm)
B) 4 ft (1.2 m)
C) 6 ft (1.8 m)
D) 8 ft (2.4 m)
سؤال
If each feeder is 100 amperes, the minimum conductor size is ____.

A) 4 AWG copper (or 2 AWG aluminum)
B) 2 AWG copper (or 4 AWG aluminum)
C) 6 AWG copper (or 3 AWG aluminum)
D) 8 AWG copper (or4 AWG aluminum)
سؤال
All electric equipment must be ____ to allow ready and safe equipment operation and maintenance.

A) externally grounded
B) surrounded by sufficient unobstructed space
C) enclosed within a metal cabinet
D) surrounded by at least 2 ft of ventilation space
سؤال
The maximum distance to any receptacle, measured horizontally along the wall line, is ____.

A) 6 in.(150 mm)
B) 12 in.(300 mm)
C) 18 in.(450 mm)
D) 24 in.(600 mm)
سؤال
Each occupant must have ready access to ____ protecting the conductors supplying that occupancy unless otherwise permitted in 240.24(B)(1) and (B)(2).

A) primary feeders
B) all overcurrent devices
C) panel boxes
D) service laterals
سؤال
If the load requirements of a single-phase installation are greater than the serving agency normally supplies through one service, ____ are permitted.

A) additional agencies
B) multiple branches
C) service disconnects
D) multiple services
سؤال
____ is defined as the underground conductors between the utility electric supply system and the service point.

A) Service lateral
B) Primary branch
C) Ancillary service
D) Connection branch
سؤال
The conductors and equipment connecting the serving utility to the wiring system of the premises are called the ____.

A) main feeders
B) service
C) central lines
D) primary carriers
سؤال
A minimum of ____ wall switch-controlled lighting outlet(s) is (are) required for dwelling hallways.

A) one
B) two
C) three
D) four
سؤال
All 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground serving kitchen countertops must have ____.

A) separate circuit breakers
B) interior grounding
C) GFCI protection
D) exterior grounding
سؤال
____ is the maximum number of disconnects per service.

A) Two
B) Three
C) Six
D) Nine
سؤال
Skin effect and induction change the resistance in alternating-current (ac) circuits; therefore, resistance of a conductor is ____.

A) slightly lower in an ac circuit
B) reciprocally lower in a dc circuit
C) slightly higher in an ac circuit
D) reciprocally higher in a dc circuit
سؤال
On long runs, it may be necessary to ____ to compensate for voltage drop.

A) decrease the branch circuit length
B) apply an approved voltage amplifier
C) boost supply influx
D) increase the branch-circuit conductor's size
سؤال
Dwelling-unit branch circuits shall supply only loads within, or associated with, ____.

A) dwellings in that vertical line
B) a parallel unit
C) other branch circuits
D) that dwelling unit
سؤال
A multifamily dwelling is a building containing ____ dwelling units.

A) one or more
B) two or more
C) three or more
D) four or more
سؤال
General receptacle installation provisions for multifamily dwellings are almost identical to those for ____.

A) commercial properties
B) garage facilities
C) dual-family dwellings
D) one-family dwellings
سؤال
Conductors must have ____ and sufficient ampacity to carry the current for the load as calculated in accordance with Article 220.

A) sufficient length
B) adequate insulation
C) adequate mechanical strength
D) definitive markings
سؤال
Kitchen receptacles not serving countertops (such as receptacles behind refrigerators) ____ unless they are installed within 6 ft (1.8 m) of the outside edge of the sink.

A) must be on a separate branch circuit
B) require a dual phase leader
C) do not require GFCI protection
D) are not counted toward total load
سؤال
The higher the resistance through a conductor, the ____.

A) smaller the voltage drop
B) higher the voltage drop
C) the more stable the current
D) more neutral the offset
سؤال
The larger the circular mil area of a conductor, the ____.

A) greater the resistance
B) more insulation that is required
C) more flexible the conductor
D) lower the resistance
سؤال
A single-phase feeder (or branch circuit) conductor will have a total resistance ____ that of one conductor.

A) half
B) twice
C) three times
D) four times
سؤال
The conductor voltage that is dropped is a percentage of the source voltage and can be calculated by ____.

A) multiplying voltage drop by the source voltage
B) adding voltage drop to the source voltage
C) subtracting voltage drop from the source voltage
D) dividing voltage drop by the source voltage
سؤال
The recommended voltage drop for a branch circuit is ____ % or less.

A) 1
B) 5
C) 3
D) 7
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/25
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 10: Comprehensive Provisions
1
A drip loop's lowest point has a minimum vertical clearance of ____.

A) 4 ft (1.2 m)
B) 6 ft (1.8 m)
C) 8 ft (2.4 m)
D) 10 ft (3.0 m)
D
2
Service conductors supplying a building (or other structure) shall not ____.

A) terminate in a panel
B) be enclosed in a six-gang enclosure
C) pass through the interior of another building
D) have less than two disconnects
C
3
The vertical clearance above roof level must be maintained for a distance of at least ____ from all edges of the roof.

A) 3 ft (900 mm)
B) 4 ft (1.2 m)
C) 6 ft (1.8 m)
D) 8 ft (2.4 m)
A
4
If each feeder is 100 amperes, the minimum conductor size is ____.

A) 4 AWG copper (or 2 AWG aluminum)
B) 2 AWG copper (or 4 AWG aluminum)
C) 6 AWG copper (or 3 AWG aluminum)
D) 8 AWG copper (or4 AWG aluminum)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
5
All electric equipment must be ____ to allow ready and safe equipment operation and maintenance.

A) externally grounded
B) surrounded by sufficient unobstructed space
C) enclosed within a metal cabinet
D) surrounded by at least 2 ft of ventilation space
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
6
The maximum distance to any receptacle, measured horizontally along the wall line, is ____.

A) 6 in.(150 mm)
B) 12 in.(300 mm)
C) 18 in.(450 mm)
D) 24 in.(600 mm)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
7
Each occupant must have ready access to ____ protecting the conductors supplying that occupancy unless otherwise permitted in 240.24(B)(1) and (B)(2).

A) primary feeders
B) all overcurrent devices
C) panel boxes
D) service laterals
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
8
If the load requirements of a single-phase installation are greater than the serving agency normally supplies through one service, ____ are permitted.

A) additional agencies
B) multiple branches
C) service disconnects
D) multiple services
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
9
____ is defined as the underground conductors between the utility electric supply system and the service point.

A) Service lateral
B) Primary branch
C) Ancillary service
D) Connection branch
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
10
The conductors and equipment connecting the serving utility to the wiring system of the premises are called the ____.

A) main feeders
B) service
C) central lines
D) primary carriers
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
11
A minimum of ____ wall switch-controlled lighting outlet(s) is (are) required for dwelling hallways.

A) one
B) two
C) three
D) four
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
12
All 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground serving kitchen countertops must have ____.

A) separate circuit breakers
B) interior grounding
C) GFCI protection
D) exterior grounding
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
13
____ is the maximum number of disconnects per service.

A) Two
B) Three
C) Six
D) Nine
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
14
Skin effect and induction change the resistance in alternating-current (ac) circuits; therefore, resistance of a conductor is ____.

A) slightly lower in an ac circuit
B) reciprocally lower in a dc circuit
C) slightly higher in an ac circuit
D) reciprocally higher in a dc circuit
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
15
On long runs, it may be necessary to ____ to compensate for voltage drop.

A) decrease the branch circuit length
B) apply an approved voltage amplifier
C) boost supply influx
D) increase the branch-circuit conductor's size
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
16
Dwelling-unit branch circuits shall supply only loads within, or associated with, ____.

A) dwellings in that vertical line
B) a parallel unit
C) other branch circuits
D) that dwelling unit
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
17
A multifamily dwelling is a building containing ____ dwelling units.

A) one or more
B) two or more
C) three or more
D) four or more
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
18
General receptacle installation provisions for multifamily dwellings are almost identical to those for ____.

A) commercial properties
B) garage facilities
C) dual-family dwellings
D) one-family dwellings
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
19
Conductors must have ____ and sufficient ampacity to carry the current for the load as calculated in accordance with Article 220.

A) sufficient length
B) adequate insulation
C) adequate mechanical strength
D) definitive markings
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
20
Kitchen receptacles not serving countertops (such as receptacles behind refrigerators) ____ unless they are installed within 6 ft (1.8 m) of the outside edge of the sink.

A) must be on a separate branch circuit
B) require a dual phase leader
C) do not require GFCI protection
D) are not counted toward total load
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
21
The higher the resistance through a conductor, the ____.

A) smaller the voltage drop
B) higher the voltage drop
C) the more stable the current
D) more neutral the offset
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
22
The larger the circular mil area of a conductor, the ____.

A) greater the resistance
B) more insulation that is required
C) more flexible the conductor
D) lower the resistance
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
23
A single-phase feeder (or branch circuit) conductor will have a total resistance ____ that of one conductor.

A) half
B) twice
C) three times
D) four times
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
24
The conductor voltage that is dropped is a percentage of the source voltage and can be calculated by ____.

A) multiplying voltage drop by the source voltage
B) adding voltage drop to the source voltage
C) subtracting voltage drop from the source voltage
D) dividing voltage drop by the source voltage
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
25
The recommended voltage drop for a branch circuit is ____ % or less.

A) 1
B) 5
C) 3
D) 7