Deck 18: Device Installation

ملء الشاشة (f)
exit full mode
سؤال
Which of the following conductors are permitted to be used for the push-in method of attaching conductors to a device?

A) 14 AWG solid copper
B) 14 AWG stranded copper
C) 14 AWG aluminum
D) 14 AWG copper-clad aluminum
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
All metal device boxes need to have the circuit equipment-grounding conductor(s) connected to it with a 10-32 green grounding screw.
سؤال
A TVSS device works by __________ the high-surge voltage to a level that a piece of equipment like a computer can withstand.

A) smoothing
B) chopping
C) stopping
D) clamping
سؤال
An equipment-grounding conductor may not be __________.

A) bare
B) green
C) green with yellow stripes
D) green with white stripes
سؤال
The most common receptacle type used in residential wiring is the single receptacle.
سؤال
In all areas specified in Section 210.52, all nonlocking type 125- and 250-volt, 15- and 20-ampere receptacles must be tamper-resistant.(General Rule)
سؤال
If a white conductor in a Type NM cable is connected to a traveler terminal on a three-way switch, it does not have to be reidentified because it is not "hot" all the time.
سؤال
Section 210.12(A) in the NEC requires all of the 15- and 20-ampere, 120-volt branch circuits installed in dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sun rooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas to be AFCI protected.
سؤال
On a 20-ampere rated branch circuit, which of the following types of receptacles may not be used?

A) 20-ampere single receptacles
B) 15-ampere single receptacles
C) 15-ampere duplex receptacles
D) 20-ampere duplex receptacles
سؤال
When self-grounding receptacles are used with nonmetallic device boxes, there is no need to attach the circuit grounding conductor to the green screw on the receptacle.
سؤال
Section 404.10(B) specifies that screws used for attaching a switch to an electrical box must be sheet metal screws with a thread that matches the thread gage or size of the screw holes in the box.
سؤال
When a duplex receptacle is installed horizontally, it is recommended that the __________ slot be located on top.

A) grounded
B) grounding
C) ungrounded
D) Either A or B
سؤال
Which of the following determine the effect electrical shock has on the body?

A) The amount of current flowing through the body
B) The path the current takes through the body
C) The length of time the current flows through the body
D) All of the above
سؤال
A __________ device operates by monitoring the current flow on both the ungrounded "hot" conductor and the grounded conductor.

A) TVSS
B) circuit breaker
C) fuse
D) GFCI
سؤال
A Class A GFCI device is designed to trip when fault current levels are _____ milliamps or more and not to trip when the fault current is less than _____ milliamps.

A) 6, 4
B) 4, 6
C) 6, 5
D) 5, 2
سؤال
A __________ switch would be used to control two lights from one location.

A) double-pole
B) single-pole
C) three-way
D) four-way
سؤال
Many of the appliances used in today's homes contain sensitive electronic circuitry, circuit boards, or microprocessors and these components are susceptible to transient voltages, also known as __________ or voltage spikes.

A) voltage drops
B) voltage surges
C) voltage dips
D) voltage peaks
سؤال
A feed-through GFCI receptacle can provide GFCI protection for regular receptacles installed "downstream" on the same branch circuit.
سؤال
A multiple receptacle has more than __________ contact device(s) on the same yoke.

A) 1
B) 2
C) 3
D) 4
سؤال
A GFCI device provides protection against __________.

A) short circuits
B) ground faults
C) overcurrents
D) All of the above
سؤال
GFCI receptacles should be tested at least once per __________.

A) day
B) week
C) month
D) year
سؤال
A(n) ____________________ switch is used to control a 240-volt load from one location.
سؤال
A duplex receptacle that is wired so one half is hot all the time and the other half is switch-controlled is called a(n) ____________________ receptacle.
سؤال
If a device box has been installed too far back behind a wall, a __________ can be used to bring the edge of the box flush with the wall surface.

A) new box
B) wall shrinker
C) box extender
D) different kind of device
سؤال
Explain the purpose of the metal strap that runs through or behind a receptacle or switch.
سؤال
The metal frame that a receptacle or switch is built around is called a(n) ____________________.
سؤال
The preferred method for connecting a circuit conductor to a device is to form a __________ in the wire, put it under a terminal screw, and tighten the screw properly.

A) terminal loop
B) curve
C) circle
D) jug handle
سؤال
To GFCI-protect receptacles that are downstream from a GFCI receptacle, the wiring going to those receptacles is connected to the ____________________ terminals on a feed-through GFCI receptacle.
سؤال
A(n) _________ is a familiar type of transient voltage surge suppressor that is usually bought and installed by the homeowner rather than the electrician.
سؤال
The NEC defines a(n) ____________________ as a contact device installed at an outlet for the connection of an attachment plug.
سؤال
Electricians create a split-wired receptacle by removing the __________ between the brass terminal screws on the "hot" side of a duplex receptacle.

A) screw
B) connecting tab
C) strap
D) wire
سؤال
A device intended to provide protection from the effects of arc faults by recognizing characteristics unique to arcing and by functioning to de-energize the circuit when an arc is detected is called a(n) ________________________________________.
سؤال
The proper NEMA designation for a 30-ampere, 125/250-volt grounding-type receptacle installed for an electric clothes dryer is __________.

A) 5-15R
B) 6-30R
C) 14-30R
D) 10-30R
سؤال
The proper NEMA designation for a 15-ampere, 125-volt grounding-type receptacle is __________.

A) 5-15R
B) 5-15P
C) 5-20R
D) 6-15R
سؤال
On a receptacle, the ____________________ conductor is connected to the silver terminal screw.
سؤال
__________ connections on devices are a reliable way to terminate circuit conductors to a switch or receptacle device and can save time during installation because a terminal loop is not required to be made.

A) New
B) Push-in
C) Back-wired
D) Straight through
سؤال
If the two conductors to be connected to a single-pole switch are black and a reidentified white, the connection you are using is called a traditional _________________________.
سؤال
When more than one grounded conductor enters a device box, a wiring practice to use so that only one conductor gets connected to the silver terminal screw is to use a(n) ____________________.
سؤال
A __________ receptacle is one that has internal shutters that are closed behind the receptacle slots when there is no attachment plug inserted.The shutters open when a plug is inserted allowing the plug (and cord) to become energized.

A) duplex
B) single
C) tamper-resistant
D) GFCI
سؤال
Section 406.5 specifies that screws used for attaching a receptacle to an electrical box must be machine screws with 32 threads per inch or be the type supplied by a __________ receptacle.
سؤال
Describe different strategies that electricians use to properly position a duplex receptacle into a device box.
سؤال
Explain why it is recommended to install receptacles with the grounding slot up.
سؤال
Explain what can be done during the rough-in phase to make switch installation easier in the finish phase of the wiring process.
سؤال
Explain how metal faceplates are grounded if nonmetallic device boxes are used.
سؤال
Explain the drawbacks of the push-in method of securing conductors to devices.
سؤال
What do the letters "TVSS" stand for?
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/46
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 18: Device Installation
1
Which of the following conductors are permitted to be used for the push-in method of attaching conductors to a device?

A) 14 AWG solid copper
B) 14 AWG stranded copper
C) 14 AWG aluminum
D) 14 AWG copper-clad aluminum
A
2
All metal device boxes need to have the circuit equipment-grounding conductor(s) connected to it with a 10-32 green grounding screw.
True
3
A TVSS device works by __________ the high-surge voltage to a level that a piece of equipment like a computer can withstand.

A) smoothing
B) chopping
C) stopping
D) clamping
D
4
An equipment-grounding conductor may not be __________.

A) bare
B) green
C) green with yellow stripes
D) green with white stripes
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
5
The most common receptacle type used in residential wiring is the single receptacle.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
6
In all areas specified in Section 210.52, all nonlocking type 125- and 250-volt, 15- and 20-ampere receptacles must be tamper-resistant.(General Rule)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
7
If a white conductor in a Type NM cable is connected to a traveler terminal on a three-way switch, it does not have to be reidentified because it is not "hot" all the time.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
8
Section 210.12(A) in the NEC requires all of the 15- and 20-ampere, 120-volt branch circuits installed in dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sun rooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas to be AFCI protected.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
9
On a 20-ampere rated branch circuit, which of the following types of receptacles may not be used?

A) 20-ampere single receptacles
B) 15-ampere single receptacles
C) 15-ampere duplex receptacles
D) 20-ampere duplex receptacles
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
10
When self-grounding receptacles are used with nonmetallic device boxes, there is no need to attach the circuit grounding conductor to the green screw on the receptacle.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
11
Section 404.10(B) specifies that screws used for attaching a switch to an electrical box must be sheet metal screws with a thread that matches the thread gage or size of the screw holes in the box.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
12
When a duplex receptacle is installed horizontally, it is recommended that the __________ slot be located on top.

A) grounded
B) grounding
C) ungrounded
D) Either A or B
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
13
Which of the following determine the effect electrical shock has on the body?

A) The amount of current flowing through the body
B) The path the current takes through the body
C) The length of time the current flows through the body
D) All of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
14
A __________ device operates by monitoring the current flow on both the ungrounded "hot" conductor and the grounded conductor.

A) TVSS
B) circuit breaker
C) fuse
D) GFCI
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
15
A Class A GFCI device is designed to trip when fault current levels are _____ milliamps or more and not to trip when the fault current is less than _____ milliamps.

A) 6, 4
B) 4, 6
C) 6, 5
D) 5, 2
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
16
A __________ switch would be used to control two lights from one location.

A) double-pole
B) single-pole
C) three-way
D) four-way
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
17
Many of the appliances used in today's homes contain sensitive electronic circuitry, circuit boards, or microprocessors and these components are susceptible to transient voltages, also known as __________ or voltage spikes.

A) voltage drops
B) voltage surges
C) voltage dips
D) voltage peaks
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
18
A feed-through GFCI receptacle can provide GFCI protection for regular receptacles installed "downstream" on the same branch circuit.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
19
A multiple receptacle has more than __________ contact device(s) on the same yoke.

A) 1
B) 2
C) 3
D) 4
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
20
A GFCI device provides protection against __________.

A) short circuits
B) ground faults
C) overcurrents
D) All of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
21
GFCI receptacles should be tested at least once per __________.

A) day
B) week
C) month
D) year
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
22
A(n) ____________________ switch is used to control a 240-volt load from one location.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
23
A duplex receptacle that is wired so one half is hot all the time and the other half is switch-controlled is called a(n) ____________________ receptacle.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
24
If a device box has been installed too far back behind a wall, a __________ can be used to bring the edge of the box flush with the wall surface.

A) new box
B) wall shrinker
C) box extender
D) different kind of device
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
25
Explain the purpose of the metal strap that runs through or behind a receptacle or switch.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
26
The metal frame that a receptacle or switch is built around is called a(n) ____________________.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
27
The preferred method for connecting a circuit conductor to a device is to form a __________ in the wire, put it under a terminal screw, and tighten the screw properly.

A) terminal loop
B) curve
C) circle
D) jug handle
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
28
To GFCI-protect receptacles that are downstream from a GFCI receptacle, the wiring going to those receptacles is connected to the ____________________ terminals on a feed-through GFCI receptacle.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
29
A(n) _________ is a familiar type of transient voltage surge suppressor that is usually bought and installed by the homeowner rather than the electrician.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
30
The NEC defines a(n) ____________________ as a contact device installed at an outlet for the connection of an attachment plug.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
31
Electricians create a split-wired receptacle by removing the __________ between the brass terminal screws on the "hot" side of a duplex receptacle.

A) screw
B) connecting tab
C) strap
D) wire
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
32
A device intended to provide protection from the effects of arc faults by recognizing characteristics unique to arcing and by functioning to de-energize the circuit when an arc is detected is called a(n) ________________________________________.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
33
The proper NEMA designation for a 30-ampere, 125/250-volt grounding-type receptacle installed for an electric clothes dryer is __________.

A) 5-15R
B) 6-30R
C) 14-30R
D) 10-30R
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
34
The proper NEMA designation for a 15-ampere, 125-volt grounding-type receptacle is __________.

A) 5-15R
B) 5-15P
C) 5-20R
D) 6-15R
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
35
On a receptacle, the ____________________ conductor is connected to the silver terminal screw.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
36
__________ connections on devices are a reliable way to terminate circuit conductors to a switch or receptacle device and can save time during installation because a terminal loop is not required to be made.

A) New
B) Push-in
C) Back-wired
D) Straight through
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
37
If the two conductors to be connected to a single-pole switch are black and a reidentified white, the connection you are using is called a traditional _________________________.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
38
When more than one grounded conductor enters a device box, a wiring practice to use so that only one conductor gets connected to the silver terminal screw is to use a(n) ____________________.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
39
A __________ receptacle is one that has internal shutters that are closed behind the receptacle slots when there is no attachment plug inserted.The shutters open when a plug is inserted allowing the plug (and cord) to become energized.

A) duplex
B) single
C) tamper-resistant
D) GFCI
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
40
Section 406.5 specifies that screws used for attaching a receptacle to an electrical box must be machine screws with 32 threads per inch or be the type supplied by a __________ receptacle.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
41
Describe different strategies that electricians use to properly position a duplex receptacle into a device box.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
42
Explain why it is recommended to install receptacles with the grounding slot up.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
43
Explain what can be done during the rough-in phase to make switch installation easier in the finish phase of the wiring process.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
44
Explain how metal faceplates are grounded if nonmetallic device boxes are used.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
45
Explain the drawbacks of the push-in method of securing conductors to devices.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
46
What do the letters "TVSS" stand for?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.
فتح الحزمة
k this deck
locked card icon
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 46 في هذه المجموعة.