Deck 21: Motor Installation

ملء الشاشة (f)
exit full mode
سؤال
Figure 21-2 <strong>Figure 21-2   A 3-hp single-phase AC motor is connected to a 208-volt line. What will be the full-load running current of this motor? Use the accompanying figure.</strong> A) 4.1 A B) 16 A C) 18.7 A D) 30.8 A <div style=padding-top: 35px>
A 3-hp single-phase AC motor is connected to a 208-volt line. What will be the full-load running current of this motor? Use the accompanying figure.

A) 4.1 A
B) 16 A
C) 18.7 A
D) 30.8 A
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
Figure 21-10 <strong>Figure 21-10   A 15-hp, three-phase squirrel-cage motor with a code letter of K is connected to a 240-volt line. Determine the locked-rotor current using the accompanying figure.</strong> A) 245.1 B) 266.7 C) 287.4 D) 306.7 <div style=padding-top: 35px>
A 15-hp, three-phase squirrel-cage motor with a code letter of K is connected to a 240-volt line. Determine the locked-rotor current using the accompanying figure.

A) 245.1
B) 266.7
C) 287.4
D) 306.7
سؤال
Figure 21-4 <strong>Figure 21-4   A 150-hp, 460-volt synchronous motor is to be operated at 80% power factor. What will be the full-load current rating of the motor? Use the accompanying figure.</strong> A) 66 B) 81 C) 127 D) 189 <div style=padding-top: 35px>
A 150-hp, 460-volt synchronous motor is to be operated at 80% power factor. What will be the full-load current rating of the motor? Use the accompanying figure.

A) 66
B) 81
C) 127
D) 189
سؤال
Figure 21-14 <strong>Figure 21-14   A 40-hp three-phase squirrel cage motor is connected to a 208-volt line. What is the minimum size NEMA starter that should be used to connect this motor to the line? Use the accompanying figure.</strong> A) 00 B) 1 C) 2 D) 4 <div style=padding-top: 35px>
A 40-hp three-phase squirrel cage motor is connected to a 208-volt line. What is the minimum size NEMA starter that should be used to connect this motor to the line? Use the accompanying figure.

A) 00
B) 1
C) 2
D) 4
سؤال
Figure 21-10 <strong>Figure 21-10   Most motor circuits are protected by ____.</strong> A) instantaneous-trip circuit breakers or inverse-time circuit breakers B) instantaneous-trip circuit breakers C) dual-element time-delay fuses or inverse-time circuit breakers D) non-time delay fuses <div style=padding-top: 35px>
Most motor circuits are protected by ____.

A) instantaneous-trip circuit breakers or inverse-time circuit breakers
B) instantaneous-trip circuit breakers
C) dual-element time-delay fuses or inverse-time circuit breakers
D) non-time delay fuses
سؤال
Figure 21-4 <strong>Figure 21-4   A 200-hp, 2300-volt synchronous motor is to be operated at 90% power factor. What will be the full-load current rating of this motor? Use the accompanying figure.</strong> A) 44 B) 48 C) 52 D) 56 <div style=padding-top: 35px>
A 200-hp, 2300-volt synchronous motor is to be operated at 90% power factor. What will be the full-load current rating of this motor? Use the accompanying figure.

A) 44
B) 48
C) 52
D) 56
سؤال
Figure 21-14 <strong>Figure 21-14   If for some reason this fuse will not permit the motor to start without blowing, NEC Section 430.52(C)(1) Exception 2(b) states that the rating of a dual-element time delay fuse may be increased to a maximum of ____ of the full-load motor current.</strong> A) 75% B) 115% C) 175% D) 225% <div style=padding-top: 35px>
If for some reason this fuse will not permit the motor to start without blowing, NEC Section 430.52(C)(1) Exception 2(b) states that the rating of a dual-element time delay fuse may be increased to a maximum of ____ of the full-load motor current.

A) 75%
B) 115%
C) 175%
D) 225%
سؤال
The size of the short-circuit protective device is determined by Section 430.62(A).
سؤال
All heater sizes are chosen from a chart supplied by the starter manufacturer.
سؤال
Figures 21-4 and 21-12 <strong>Figures 21-4 and 21-12     A 100-hp three-phase squirrel-cage induction motor is connected to a 240-volt line. The motor does not contain a NEMA design code. A dual-element time delay fuse is to be used as the short-circuit protective device. Use the accompanying figure to determine the size needed.</strong> A) 350 A B) 400 A C) 450 A D) 500 A <div style=padding-top: 35px> <strong>Figures 21-4 and 21-12     A 100-hp three-phase squirrel-cage induction motor is connected to a 240-volt line. The motor does not contain a NEMA design code. A dual-element time delay fuse is to be used as the short-circuit protective device. Use the accompanying figure to determine the size needed.</strong> A) 350 A B) 400 A C) 450 A D) 500 A <div style=padding-top: 35px>
A 100-hp three-phase squirrel-cage induction motor is connected to a 240-volt line. The motor does not contain a NEMA design code. A dual-element time delay fuse is to be used as the short-circuit protective device. Use the accompanying figure to determine the size needed.

A) 350 A
B) 400 A
C) 450 A
D) 500 A
سؤال
As a general rule the temperature rating of most devices will not exceed ____ degrees C.

A) 45
B) 55
C) 65
D) 75
سؤال
Different tables from the ____ (NEC®) are used to determine the running current for the different types of motors.

A) National Engineering Council
B) National Electrical Code®
C) National Electrical Council
D) National Engineering Code
سؤال
Starter sizes are rated by motor type, horsepower, and connected voltage.
سؤال
When the termination temperature rating is not listed or known, for circuits rated at 100 amperes or less, or for #14 AWG through #1 AWG conductors, the ampacity of the wire, regardless of the temperature rating, must be selected from the 60°C column.
سؤال
There are two basic methods for determining the locked-rotor current (____ current) of a squirrel-cage induction motor depending on the information available.

A) starting
B) running
C) stopping
D) nameplate
سؤال
Figure 21-2 <strong>Figure 21-2   When using a two-phase, three-wire system, the size of the neutral conductor must be increased by the square root of ____.</strong> A) 1.5 B) 2 C) 3 D) 5 <div style=padding-top: 35px>
When using a two-phase, three-wire system, the size of the neutral conductor must be increased by the square root of ____.

A) 1.5
B) 2
C) 3
D) 5
سؤال
Two-phase motors use the nameplate rating instead of the values shown in the table for full-load currents.
سؤال
Figures 21-4 and 21-12 <strong>Figures 21-4 and 21-12     The two most common starter size ratings are NEMA and ____.</strong> A) NIST B) NFPA C) UL D) IEC <div style=padding-top: 35px> <strong>Figures 21-4 and 21-12     The two most common starter size ratings are NEMA and ____.</strong> A) NIST B) NFPA C) UL D) IEC <div style=padding-top: 35px>
The two most common starter size ratings are NEMA and ____.

A) NIST
B) NFPA
C) UL
D) IEC
سؤال
Motors especially designed for low speed and high torque, or multispeed motors, shall have their running current determined from the ____.

A) starting speed
B) attached overload protection device
C) nameplate rating
D) NEC tables
سؤال
Section 430.22(A) states that conductors supplying a single motor shall have an ampacity of not less than ____% of the motor full-load current.

A) 90
B) 125
C) 155
D) 200
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/20
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 21: Motor Installation
1
Figure 21-2 <strong>Figure 21-2   A 3-hp single-phase AC motor is connected to a 208-volt line. What will be the full-load running current of this motor? Use the accompanying figure.</strong> A) 4.1 A B) 16 A C) 18.7 A D) 30.8 A
A 3-hp single-phase AC motor is connected to a 208-volt line. What will be the full-load running current of this motor? Use the accompanying figure.

A) 4.1 A
B) 16 A
C) 18.7 A
D) 30.8 A
C
2
Figure 21-10 <strong>Figure 21-10   A 15-hp, three-phase squirrel-cage motor with a code letter of K is connected to a 240-volt line. Determine the locked-rotor current using the accompanying figure.</strong> A) 245.1 B) 266.7 C) 287.4 D) 306.7
A 15-hp, three-phase squirrel-cage motor with a code letter of K is connected to a 240-volt line. Determine the locked-rotor current using the accompanying figure.

A) 245.1
B) 266.7
C) 287.4
D) 306.7
D
3
Figure 21-4 <strong>Figure 21-4   A 150-hp, 460-volt synchronous motor is to be operated at 80% power factor. What will be the full-load current rating of the motor? Use the accompanying figure.</strong> A) 66 B) 81 C) 127 D) 189
A 150-hp, 460-volt synchronous motor is to be operated at 80% power factor. What will be the full-load current rating of the motor? Use the accompanying figure.

A) 66
B) 81
C) 127
D) 189
D
4
Figure 21-14 <strong>Figure 21-14   A 40-hp three-phase squirrel cage motor is connected to a 208-volt line. What is the minimum size NEMA starter that should be used to connect this motor to the line? Use the accompanying figure.</strong> A) 00 B) 1 C) 2 D) 4
A 40-hp three-phase squirrel cage motor is connected to a 208-volt line. What is the minimum size NEMA starter that should be used to connect this motor to the line? Use the accompanying figure.

A) 00
B) 1
C) 2
D) 4
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
5
Figure 21-10 <strong>Figure 21-10   Most motor circuits are protected by ____.</strong> A) instantaneous-trip circuit breakers or inverse-time circuit breakers B) instantaneous-trip circuit breakers C) dual-element time-delay fuses or inverse-time circuit breakers D) non-time delay fuses
Most motor circuits are protected by ____.

A) instantaneous-trip circuit breakers or inverse-time circuit breakers
B) instantaneous-trip circuit breakers
C) dual-element time-delay fuses or inverse-time circuit breakers
D) non-time delay fuses
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
6
Figure 21-4 <strong>Figure 21-4   A 200-hp, 2300-volt synchronous motor is to be operated at 90% power factor. What will be the full-load current rating of this motor? Use the accompanying figure.</strong> A) 44 B) 48 C) 52 D) 56
A 200-hp, 2300-volt synchronous motor is to be operated at 90% power factor. What will be the full-load current rating of this motor? Use the accompanying figure.

A) 44
B) 48
C) 52
D) 56
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
7
Figure 21-14 <strong>Figure 21-14   If for some reason this fuse will not permit the motor to start without blowing, NEC Section 430.52(C)(1) Exception 2(b) states that the rating of a dual-element time delay fuse may be increased to a maximum of ____ of the full-load motor current.</strong> A) 75% B) 115% C) 175% D) 225%
If for some reason this fuse will not permit the motor to start without blowing, NEC Section 430.52(C)(1) Exception 2(b) states that the rating of a dual-element time delay fuse may be increased to a maximum of ____ of the full-load motor current.

A) 75%
B) 115%
C) 175%
D) 225%
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
8
The size of the short-circuit protective device is determined by Section 430.62(A).
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
9
All heater sizes are chosen from a chart supplied by the starter manufacturer.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
10
Figures 21-4 and 21-12 <strong>Figures 21-4 and 21-12     A 100-hp three-phase squirrel-cage induction motor is connected to a 240-volt line. The motor does not contain a NEMA design code. A dual-element time delay fuse is to be used as the short-circuit protective device. Use the accompanying figure to determine the size needed.</strong> A) 350 A B) 400 A C) 450 A D) 500 A <strong>Figures 21-4 and 21-12     A 100-hp three-phase squirrel-cage induction motor is connected to a 240-volt line. The motor does not contain a NEMA design code. A dual-element time delay fuse is to be used as the short-circuit protective device. Use the accompanying figure to determine the size needed.</strong> A) 350 A B) 400 A C) 450 A D) 500 A
A 100-hp three-phase squirrel-cage induction motor is connected to a 240-volt line. The motor does not contain a NEMA design code. A dual-element time delay fuse is to be used as the short-circuit protective device. Use the accompanying figure to determine the size needed.

A) 350 A
B) 400 A
C) 450 A
D) 500 A
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
11
As a general rule the temperature rating of most devices will not exceed ____ degrees C.

A) 45
B) 55
C) 65
D) 75
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
12
Different tables from the ____ (NEC®) are used to determine the running current for the different types of motors.

A) National Engineering Council
B) National Electrical Code®
C) National Electrical Council
D) National Engineering Code
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
13
Starter sizes are rated by motor type, horsepower, and connected voltage.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
14
When the termination temperature rating is not listed or known, for circuits rated at 100 amperes or less, or for #14 AWG through #1 AWG conductors, the ampacity of the wire, regardless of the temperature rating, must be selected from the 60°C column.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
15
There are two basic methods for determining the locked-rotor current (____ current) of a squirrel-cage induction motor depending on the information available.

A) starting
B) running
C) stopping
D) nameplate
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
16
Figure 21-2 <strong>Figure 21-2   When using a two-phase, three-wire system, the size of the neutral conductor must be increased by the square root of ____.</strong> A) 1.5 B) 2 C) 3 D) 5
When using a two-phase, three-wire system, the size of the neutral conductor must be increased by the square root of ____.

A) 1.5
B) 2
C) 3
D) 5
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
17
Two-phase motors use the nameplate rating instead of the values shown in the table for full-load currents.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
18
Figures 21-4 and 21-12 <strong>Figures 21-4 and 21-12     The two most common starter size ratings are NEMA and ____.</strong> A) NIST B) NFPA C) UL D) IEC <strong>Figures 21-4 and 21-12     The two most common starter size ratings are NEMA and ____.</strong> A) NIST B) NFPA C) UL D) IEC
The two most common starter size ratings are NEMA and ____.

A) NIST
B) NFPA
C) UL
D) IEC
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
19
Motors especially designed for low speed and high torque, or multispeed motors, shall have their running current determined from the ____.

A) starting speed
B) attached overload protection device
C) nameplate rating
D) NEC tables
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
20
Section 430.22(A) states that conductors supplying a single motor shall have an ampacity of not less than ____% of the motor full-load current.

A) 90
B) 125
C) 155
D) 200