Deck 10: Transformer Installation

ملء الشاشة (f)
exit full mode
سؤال
If the primary current is less than 2 amperes, the short circuit protective device can be set at not more than 250% of that value.
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
If the primary current is ____ amperes or more, it is permissible to increase the fuse size to the next highest standard rating.

A) 2
B) 4
C) 7
D) 9
سؤال
The actual impedance of a transformer is determined by its physical construction, such as the gage of the wire in the winding, the number of turns, the type of core material, and the magnetic efficiency of the core construction.
سؤال
According to the NEC, fuses must be plainly marked with the interrupting current or rating if it is other than 8,000 amperes.
سؤال
Assume that a single-phase transformer is a 2400/480 volt 15 kVA transformer. The full load current rating of the secondary winding is ____A.

A) 3
B) 5
C) 31.25
D) 160
سؤال
If the primary current is 9 amperes or more, the fuse or circuit breaker size is set at ____% of the primary current.

A) 110
B) 125
C) 153
D) 167
سؤال
There are several steps that should be followed when selecting a conductor. The first step is to determine the temperature rating of the devices and terminals.
سؤال
The temperature ratings of devices such as circuit breakers, fuses, and terminals are found in the ____ product directories.

A) Underwriters Laboratories'
B) National Electrical Code's
C) National Electrical Code Library's
D) Underwriters Library's
سؤال
____ impedance is an empirical value that can be used to predict transformer performance.

A) Decimal
B) Percent
C) Numeric
D) Summary
سؤال
The percent impedance is measured by connecting a(n) ____ across the low-voltage terminals and a variable voltage source across the high-voltage terminals.

A) ammeter
B) voltmeter
C) conductor
D) wattmeter
سؤال
The ability of a fuse or circuit breaker to open under the ____ fault current is expressed as the interrupting rating of the device.

A) maximum
B) minimum
C) average
D) required
سؤال
In general, fuses are rarely selected for protection of high voltage circuits because they are more expensive than other types of protection.
سؤال
____ can be used as the branch circuit protective devices in circuits supplying power to transformers.

A) Only fuses
B) Only circuit breakers
C) Fuses or circuit breakers
D) Neither fuses nor circuit breakers
سؤال
The minimum interrupting rating permitted for a fuse or circuit breaker in a specific installation is the ____ fault current available at the location of the protective device.

A) maximum linear
B) minimum symmetrical
C) maximum symmetrical
D) minimum surface
سؤال
When working with any transformer, the primary is the winding that is connected to a voltage source, and the secondary is the winding that is connected to an electrical load.
سؤال
NEC 215.2(A) states that the rating of a branch-circuit shall not be ____.

A) less than noncontinuous load plus 110% of the continuous load
B) more than continuous load plus 125% of the noncontinuous load
C) less than noncontinuous load plus 125% of the continuous load
D) more than continuous load plus 150% of the noncontinuous load
سؤال
The NEC states that an autotransformer rated at 1000 volts or less must be protected by an overcurrent device in each of the input ungrounded conductors.
سؤال
Occasionally, the temperature rating of devices such as circuit breakers, fuses, and terminals may be found on the piece of equipment, but this is the exception and not the rule.
سؤال
Percentages must be converted to a decimal form before they can be used in a mathematical formula. When this conversion has been made to represent the percent impedance in decimal form, this is called the decimal impedance.
سؤال
To determine the impedance of a transformer, first compute the full load current rating of the secondary winding using the formula I = E / VA.
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/20
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 10: Transformer Installation
1
If the primary current is less than 2 amperes, the short circuit protective device can be set at not more than 250% of that value.
False
2
If the primary current is ____ amperes or more, it is permissible to increase the fuse size to the next highest standard rating.

A) 2
B) 4
C) 7
D) 9
D
3
The actual impedance of a transformer is determined by its physical construction, such as the gage of the wire in the winding, the number of turns, the type of core material, and the magnetic efficiency of the core construction.
True
4
According to the NEC, fuses must be plainly marked with the interrupting current or rating if it is other than 8,000 amperes.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
5
Assume that a single-phase transformer is a 2400/480 volt 15 kVA transformer. The full load current rating of the secondary winding is ____A.

A) 3
B) 5
C) 31.25
D) 160
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
6
If the primary current is 9 amperes or more, the fuse or circuit breaker size is set at ____% of the primary current.

A) 110
B) 125
C) 153
D) 167
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
7
There are several steps that should be followed when selecting a conductor. The first step is to determine the temperature rating of the devices and terminals.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
8
The temperature ratings of devices such as circuit breakers, fuses, and terminals are found in the ____ product directories.

A) Underwriters Laboratories'
B) National Electrical Code's
C) National Electrical Code Library's
D) Underwriters Library's
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
9
____ impedance is an empirical value that can be used to predict transformer performance.

A) Decimal
B) Percent
C) Numeric
D) Summary
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
10
The percent impedance is measured by connecting a(n) ____ across the low-voltage terminals and a variable voltage source across the high-voltage terminals.

A) ammeter
B) voltmeter
C) conductor
D) wattmeter
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
11
The ability of a fuse or circuit breaker to open under the ____ fault current is expressed as the interrupting rating of the device.

A) maximum
B) minimum
C) average
D) required
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
12
In general, fuses are rarely selected for protection of high voltage circuits because they are more expensive than other types of protection.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
13
____ can be used as the branch circuit protective devices in circuits supplying power to transformers.

A) Only fuses
B) Only circuit breakers
C) Fuses or circuit breakers
D) Neither fuses nor circuit breakers
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
14
The minimum interrupting rating permitted for a fuse or circuit breaker in a specific installation is the ____ fault current available at the location of the protective device.

A) maximum linear
B) minimum symmetrical
C) maximum symmetrical
D) minimum surface
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
15
When working with any transformer, the primary is the winding that is connected to a voltage source, and the secondary is the winding that is connected to an electrical load.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
16
NEC 215.2(A) states that the rating of a branch-circuit shall not be ____.

A) less than noncontinuous load plus 110% of the continuous load
B) more than continuous load plus 125% of the noncontinuous load
C) less than noncontinuous load plus 125% of the continuous load
D) more than continuous load plus 150% of the noncontinuous load
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
17
The NEC states that an autotransformer rated at 1000 volts or less must be protected by an overcurrent device in each of the input ungrounded conductors.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
18
Occasionally, the temperature rating of devices such as circuit breakers, fuses, and terminals may be found on the piece of equipment, but this is the exception and not the rule.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
19
Percentages must be converted to a decimal form before they can be used in a mathematical formula. When this conversion has been made to represent the percent impedance in decimal form, this is called the decimal impedance.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
20
To determine the impedance of a transformer, first compute the full load current rating of the secondary winding using the formula I = E / VA.