Deck 15: Luminaires

ملء الشاشة (f)
exit full mode
سؤال
What are the requirements for multiwire branch circuits?
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
For surface-mounted and pendant-hung luminaires, support rods should be placed so that they extend about in.below the finished ceiling.

A)one
B)two
C)three
D)four
سؤال
What are the stipulations relevant to lamps in new energy conservation laws that have been enacted in some states?
سؤال
Describe the rules governing the disconnecting means for fluorescent luminaires.
سؤال
Multiwire branch circuits are defined in NEC Article 100 as a branch circuit that consists of two or more conductors that have a voltage between them, and a grounded conductor that has equal voltage between it and each ungrounded conductor of the circuit and that is connected to the neutral or grounded conductor of the system.

A)"hot"
B)grounded
C)ungrounded
D)semi-
سؤال
Type luminaires are permitted to be installed in direct contact with thermal insulation.

A)IIC
B)IC
C)RC
D)XC
سؤال
Most fluorescent lamps with energy savings ballasts, compact fluorescent lamps (CFLs), LEDs, and halogen lamps meet the high-efficacy requirement.do not.

A)Most fluorescent lamps with energy savings ballasts
B)Conventional incandescent lamps
C)Compact fluorescent lamps
D)Halogen Lamps
سؤال
Recessed luminaires are usually supported by that are attached to the luminaires' rough­in box.

A)screws
B)nails
C)adjustable rails
D)outlet boxes
سؤال
What are the guidelines for recessed incandescent luminaires not marked IC?
سؤال
All recessed incandescent luminaires must be equipped with factory-installed thermal protection, unless the luminaire is identified for use and installed in .

A)copper
B)aluminum
C)stainless steel
D)poured concrete
سؤال
Incandescent, open, or lamps in lampholders; pendant luminaires; and pendant lampholders are not permitted in clothes closets.

A)recessed
B)surface-mounted
C)partially open
D)enclosed
سؤال
A(n) branch circuit must supply only line-to-neutral loads if the luminaires are connected line-to-neutral.

A)multiwire
B)regular
C)irregular
D)dual-wire
سؤال
Beginning with the 2008 edition of the National Electrical Code, the term luminaire is used exclusively.Previous editions of the NEC used the term luminaire followed by the term ____ in parentheses.

A)lamp
B)lighting source
C)fixture
D)lightbulb
سؤال
Both Type THWN-2 and Type conductors have an insulation temperature rating of 90 degrees Celsius and generally meet the temperature requirement for connecting luminaires.

A)THW
B)THHN
C)RHW
D)USE
سؤال
Why are there special requirements for clothes closets?
سؤال
It is necessary that the illumination of a building comply with energy codes.These codes usually evaluate the illumination on the basis of the average per square foot (meter) of illumination load.

A)watts
B)volt-amperes
C)lumens
D)candelas
سؤال
For fluorescent and HID luminaires, the volt-ampere allowance is based on the rating of the .

A)ballast
B)filament
C)tubing
D)phosphor
سؤال
Recessed luminaires have to be securely fastened to the ceiling framing members using bolts, screws, or .

A)tacks
B)rivets
C)grid elements
D)flexible cables
سؤال
The installation of luminaires, lighting outlets, and supports is covered in Article 410 of the NEC.Article 410 sets forth the basic requirements for the installation, commonly referred to as the " ."

A)light-up
B)grounding
C)pre-set
D)rough-in
سؤال
that have the light source completely enclosed are permitted in clothes closets.

A)Incandescent open lamps in lampholders
B)Pendant luminaires
C)Pendant lampholders
D)Surface-mounted or recessed fluorescent luminaires
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/20
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 15: Luminaires
1
What are the requirements for multiwire branch circuits?
Per NEC 210.4, the requirements for multiwire branch circuits are:
1.All conductors of the multiwire branch circuit must originate in the same panelboard.
2.The disconnecting means must simultaneously disconnect all ungrounded conductors at the panelboard.In most cases, this is a circuit breaker(s).
3.The multiwire branch circuit must supply only line-to-neutral loads if the luminaires are connected line-to-neutral.
4.In the panelboard, the conductors that constitute a multiwire branch circuit is required to be grouped by tie wraps, tape, or similar means.This grouping of conductors does not have to be done when it is obvious where the conductors belong, such as a raceway that contains only one multiwire circuit with one grounded neutral conductor, or Type AC or Type MC cable.
2
For surface-mounted and pendant-hung luminaires, support rods should be placed so that they extend about in.below the finished ceiling.

A)one
B)two
C)three
D)four
A
3
What are the stipulations relevant to lamps in new energy conservation laws that have been enacted in some states?
The new laws in these states simply require that lamps in permanently installed luminaires:
∙ have high efficacy rating (high lumens per watt), or
∙ be controlled by occupancy sensors, or
∙ have a combination of lamp efficacy, occupancy sensor control, and/or dimmers.
Cord-connected floor or table lamps are not governed by current energy conservation laws.Most fluorescent lamps with energy savings ballasts, compact fluorescent lamps (CFLs), LEDs, and halogen lamps meet this high-efficacy requirement.Conventional incandescent lamps do not.
4
Describe the rules governing the disconnecting means for fluorescent luminaires.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
5
Multiwire branch circuits are defined in NEC Article 100 as a branch circuit that consists of two or more conductors that have a voltage between them, and a grounded conductor that has equal voltage between it and each ungrounded conductor of the circuit and that is connected to the neutral or grounded conductor of the system.

A)"hot"
B)grounded
C)ungrounded
D)semi-
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
6
Type luminaires are permitted to be installed in direct contact with thermal insulation.

A)IIC
B)IC
C)RC
D)XC
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
7
Most fluorescent lamps with energy savings ballasts, compact fluorescent lamps (CFLs), LEDs, and halogen lamps meet the high-efficacy requirement.do not.

A)Most fluorescent lamps with energy savings ballasts
B)Conventional incandescent lamps
C)Compact fluorescent lamps
D)Halogen Lamps
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
8
Recessed luminaires are usually supported by that are attached to the luminaires' rough­in box.

A)screws
B)nails
C)adjustable rails
D)outlet boxes
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
9
What are the guidelines for recessed incandescent luminaires not marked IC?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
10
All recessed incandescent luminaires must be equipped with factory-installed thermal protection, unless the luminaire is identified for use and installed in .

A)copper
B)aluminum
C)stainless steel
D)poured concrete
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
11
Incandescent, open, or lamps in lampholders; pendant luminaires; and pendant lampholders are not permitted in clothes closets.

A)recessed
B)surface-mounted
C)partially open
D)enclosed
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
12
A(n) branch circuit must supply only line-to-neutral loads if the luminaires are connected line-to-neutral.

A)multiwire
B)regular
C)irregular
D)dual-wire
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
13
Beginning with the 2008 edition of the National Electrical Code, the term luminaire is used exclusively.Previous editions of the NEC used the term luminaire followed by the term ____ in parentheses.

A)lamp
B)lighting source
C)fixture
D)lightbulb
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
14
Both Type THWN-2 and Type conductors have an insulation temperature rating of 90 degrees Celsius and generally meet the temperature requirement for connecting luminaires.

A)THW
B)THHN
C)RHW
D)USE
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
15
Why are there special requirements for clothes closets?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
16
It is necessary that the illumination of a building comply with energy codes.These codes usually evaluate the illumination on the basis of the average per square foot (meter) of illumination load.

A)watts
B)volt-amperes
C)lumens
D)candelas
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
17
For fluorescent and HID luminaires, the volt-ampere allowance is based on the rating of the .

A)ballast
B)filament
C)tubing
D)phosphor
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
18
Recessed luminaires have to be securely fastened to the ceiling framing members using bolts, screws, or .

A)tacks
B)rivets
C)grid elements
D)flexible cables
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
19
The installation of luminaires, lighting outlets, and supports is covered in Article 410 of the NEC.Article 410 sets forth the basic requirements for the installation, commonly referred to as the " ."

A)light-up
B)grounding
C)pre-set
D)rough-in
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
20
that have the light source completely enclosed are permitted in clothes closets.

A)Incandescent open lamps in lampholders
B)Pendant luminaires
C)Pendant lampholders
D)Surface-mounted or recessed fluorescent luminaires
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
locked card icon
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.