Deck 15: Luminaires

ملء الشاشة (f)
exit full mode
سؤال
Describe the rules governing the disconnecting means for fluorescent luminaires.
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
Incandescent, open, or ____ lamps in lampholders; pendant luminaires; and pendant lampholders are not permitted in clothes closets.

A)recessed
B)surface-mounted
C)partially open
D)enclosed
سؤال
It is necessary that the illumination of a building comply with energy codes. These codes usually evaluate the illumination on the basis of the average ____ per square foot (meter)of illumination load.

A)watts
B)volt-amperes
C)lumens
D)candelas
سؤال
What are the requirements for multiwire branch circuits?
سؤال
What are the stipulations relevant to lamps in new energy conservation laws that have been enacted in some states?
سؤال
Type ____ luminaires are permitted to be installed in direct contact with thermal insulation.

A)IIC
B)IC
C)RC
D)XC
سؤال
Beginning with the 2008 edition of the National Electrical Code , the term luminaire is used exclusively. Previous editions of the NEC used the term luminaire followed by the term ____ in parentheses.

A)lamp
B)lighting source
C)fixture
D)lightbulb
سؤال
Most fluorescent lamps with energy savings ballasts, compact fluorescent lamps (CFLs), LEDs, and halogen lamps meet high-efficacy requirements. ____ do not.

A)Most fluorescent lamps with energy savings ballasts
B)Conventional incandescent lamps
C)Compact fluorescent lamps
D)Halogen lamps
سؤال
For surface-mounted and pendant-hung luminaires, support rods should be placed so that they extend about ____ in. below the finished ceiling.

A)one
B)two
C)three
D)four
سؤال
What are the guidelines for recessed incandescent luminaires not marked IC?
سؤال
A(n)____ branch circuit must supply only line-to-neutral loads if the luminaires are connected line-to-neutral.

A)multiwire
B)regular
C)irregular
D)dual-wire
سؤال
Recessed luminaires should be securely fastened to the ceiling framing members using bolts, screws, or ____.

A)tacks
B)rivets
C)grid elements
D)glue
سؤال
For fluorescent and HID luminaires, the volt-ampere allowance is based on the rating of the ____.

A)ballast
B)filament
C)tubing
D)phosphor
سؤال
Both incandescent and fluorescent recessed luminaires are marked with the temperature rating required for the ____ if more than 60 degrees C.

A)insulation
B)mounting box
C)supply conductors
D)ceiling
سؤال
Recessed incandescent luminaires not marked Type IC and those marked for installing directly in ____ must not have insulation over the top of the luminaire.

A)copper
B)aluminum
C)stainless steel
D)poured concrete
سؤال
The installation of luminaires, lighting outlets, and supports is covered in Article 410 of the NEC . Article 410 sets forth the basic requirements for the installation, commonly referred to as the "____."

A)light-up
B)grounding
C)pre-set
D)rough-in
سؤال
Why are there special requirements for clothes closets?
سؤال
Recessed luminaires are usually supported by ____ that are attached to the luminaires' rough-in box.

A)screws
B)nails
C)adjustable rails
D)outlet boxes
سؤال
Both Type THWN-2 and Type ____ conductors have an insulation temperature rating of 90 degrees Celsius and generally meet the temperature requirement for connecting luminaires.

A)THW
B)THHN
C)RHW
D)USE
سؤال
____ that have the light source completely enclosed are permitted in clothes closets.

A)Incandescent open lamps in lampholders
B)Pendant luminaires
C)Pendant lampholders
D)Surface-mounted or recessed fluorescent luminaires
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/20
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 15: Luminaires
1
Describe the rules governing the disconnecting means for fluorescent luminaires.
NEC 410.130(G)requires a means shall be provided for disconnecting fluorescent luminaires that have double-ended lamps and ballast(s). This requirement is for the safety of those having to work on the luminaire, such as changing out a ballast or socket. The disconnecting means is permitted to be inside or outside of the luminaire. If outside of the luminaire, it must be within sight of the luminaire.
Two-wire branch circuit: The disconnecting means is required to disconnect the ungrounded conductor supplying the ballast.
Multiwire branch circuit: The disconnecting means is required to simultaneously disconnect all conductors supplying the ballast, including the grounded conductor.
2
Incandescent, open, or ____ lamps in lampholders; pendant luminaires; and pendant lampholders are not permitted in clothes closets.

A)recessed
B)surface-mounted
C)partially open
D)enclosed
C
3
It is necessary that the illumination of a building comply with energy codes. These codes usually evaluate the illumination on the basis of the average ____ per square foot (meter)of illumination load.

A)watts
B)volt-amperes
C)lumens
D)candelas
A
4
What are the requirements for multiwire branch circuits?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
5
What are the stipulations relevant to lamps in new energy conservation laws that have been enacted in some states?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
6
Type ____ luminaires are permitted to be installed in direct contact with thermal insulation.

A)IIC
B)IC
C)RC
D)XC
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
7
Beginning with the 2008 edition of the National Electrical Code , the term luminaire is used exclusively. Previous editions of the NEC used the term luminaire followed by the term ____ in parentheses.

A)lamp
B)lighting source
C)fixture
D)lightbulb
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
8
Most fluorescent lamps with energy savings ballasts, compact fluorescent lamps (CFLs), LEDs, and halogen lamps meet high-efficacy requirements. ____ do not.

A)Most fluorescent lamps with energy savings ballasts
B)Conventional incandescent lamps
C)Compact fluorescent lamps
D)Halogen lamps
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
9
For surface-mounted and pendant-hung luminaires, support rods should be placed so that they extend about ____ in. below the finished ceiling.

A)one
B)two
C)three
D)four
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
10
What are the guidelines for recessed incandescent luminaires not marked IC?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
11
A(n)____ branch circuit must supply only line-to-neutral loads if the luminaires are connected line-to-neutral.

A)multiwire
B)regular
C)irregular
D)dual-wire
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
12
Recessed luminaires should be securely fastened to the ceiling framing members using bolts, screws, or ____.

A)tacks
B)rivets
C)grid elements
D)glue
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
13
For fluorescent and HID luminaires, the volt-ampere allowance is based on the rating of the ____.

A)ballast
B)filament
C)tubing
D)phosphor
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
14
Both incandescent and fluorescent recessed luminaires are marked with the temperature rating required for the ____ if more than 60 degrees C.

A)insulation
B)mounting box
C)supply conductors
D)ceiling
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
15
Recessed incandescent luminaires not marked Type IC and those marked for installing directly in ____ must not have insulation over the top of the luminaire.

A)copper
B)aluminum
C)stainless steel
D)poured concrete
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
16
The installation of luminaires, lighting outlets, and supports is covered in Article 410 of the NEC . Article 410 sets forth the basic requirements for the installation, commonly referred to as the "____."

A)light-up
B)grounding
C)pre-set
D)rough-in
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
17
Why are there special requirements for clothes closets?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
18
Recessed luminaires are usually supported by ____ that are attached to the luminaires' rough-in box.

A)screws
B)nails
C)adjustable rails
D)outlet boxes
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
19
Both Type THWN-2 and Type ____ conductors have an insulation temperature rating of 90 degrees Celsius and generally meet the temperature requirement for connecting luminaires.

A)THW
B)THHN
C)RHW
D)USE
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
20
____ that have the light source completely enclosed are permitted in clothes closets.

A)Incandescent open lamps in lampholders
B)Pendant luminaires
C)Pendant lampholders
D)Surface-mounted or recessed fluorescent luminaires
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
locked card icon
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.