Deck 10: Comprehensive Provisions
1
General receptacle installation provisions for multifamily dwellings are almost identical to those for ____.
A) commercial properties
B) garage facilities
C) dual family dwellings
D) one family dwellings
A) commercial properties
B) garage facilities
C) dual family dwellings
D) one family dwellings
D
2
The vertical clearance above roof level must be maintained for a distance of at least ____ ft from all edges of the roof.
A) 3
B) 4
C) 6
D) 8
A) 3
B) 4
C) 6
D) 8
A
3
All electric equipment must be ____ to allow ready and safe equipment operation and maintenance.
A) externally grounded
B) surrounded by sufficient unobstructed space
C) enclosed within a metal cabinet
D) surrounded by at least 2 ft of ventilation space
A) externally grounded
B) surrounded by sufficient unobstructed space
C) enclosed within a metal cabinet
D) surrounded by at least 2 ft of ventilation space
B
4
Service conductors supplying a building (or other structure) shall not ____.
A) terminate in a panel
B) be enclosed in a six-gang enclosure
C) pass through the interior of another building
D) have less than two disconnects
A) terminate in a panel
B) be enclosed in a six-gang enclosure
C) pass through the interior of another building
D) have less than two disconnects
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
5
A drip loop's lowest point has a minimum vertical clearance of ____ ft.
A) 4
B) 6
C) 8
D) 10
A) 4
B) 6
C) 8
D) 10
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
6
Dwelling-unit branch circuits shall supply only loads within, or associated only with, ____.
A) dwellings in that vertical line
B) a parallel unit
C) other branch circuits
D) that dwelling unit
A) dwellings in that vertical line
B) a parallel unit
C) other branch circuits
D) that dwelling unit
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
7
____ is the maximum number of disconnects per service grouped in any one location.
A) Two
B) Three
C) Six
D) Nine
A) Two
B) Three
C) Six
D) Nine
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
8
Each occupant must have ready access to ____ protecting the conductors supplying that occupancy.
A) primary feeders
B) all overcurrent devices
C) panel boxes
D) service laterals
A) primary feeders
B) all overcurrent devices
C) panel boxes
D) service laterals
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
9
The conductors and equipment that deliver energy from the electricity supply system to the wiring system of the premises are called the ____.
A) main feeders
B) service
C) central lines
D) primary carriers
A) main feeders
B) service
C) central lines
D) primary carriers
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
10
All 125-volt, single-phase, 15- and 20-ampere dwelling unit outdoor receptacles must have ____.
A) separate circuit breakers
B) interior grounding
C) GFCI protection
D) exterior grounding
A) separate circuit breakers
B) interior grounding
C) GFCI protection
D) exterior grounding
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
11
____ is defined as the underground conductors between the utility electric supply system and the service point.
A) Service lateral
B) Primary branch
C) Ancillary service
D) Connection branch
A) Service lateral
B) Primary branch
C) Ancillary service
D) Connection branch
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
12
If each feeder is 100 amperes, the minimum conductor size is ____.
A) 4 AWG copper (or 2 AWG aluminum)
B) 2 AWG copper (or 4 AWG aluminum)
C) 6 AWG copper (or 3 AWG aluminum)
D) 8 AWG copper (or4 AWG aluminum)
A) 4 AWG copper (or 2 AWG aluminum)
B) 2 AWG copper (or 4 AWG aluminum)
C) 6 AWG copper (or 3 AWG aluminum)
D) 8 AWG copper (or4 AWG aluminum)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
13
If the load requirements of a single-phase installation are greater than the serving agency normally supplies through one service, ____ are permitted.
A) additional agencies
B) multiple branches
C) service disconnects
D) multiple services
A) additional agencies
B) multiple branches
C) service disconnects
D) multiple services
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
14
A minimum of ____ wall switch-controlled lighting outlet(s) is (are) required for dwelling hallways.
A) one
B) two
C) three
D) four
A) one
B) two
C) three
D) four
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
15
Kitchen receptacles not serving countertops (such as receptacles behind refrigerators) ____ unless they are installed within 6 ft of the outside edge of the sink.
A) must be on a separate branch circuit
B) require a dual phase leader
C) do not require GFCI protection
D) are not counted towards total load
A) must be on a separate branch circuit
B) require a dual phase leader
C) do not require GFCI protection
D) are not counted towards total load
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
16
On long runs, it may be necessary to ____ to compensate for voltage drop.
A) decrease the branch circuit length
B) apply an approved voltage amplifier
C) boost supply influx
D) increase the branch-circuit conductor's size
A) decrease the branch circuit length
B) apply an approved voltage amplifier
C) boost supply influx
D) increase the branch-circuit conductor's size
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
17
A multifamily dwelling is a building containing ____ dwelling units.
A) one or more
B) two or more
C) three or more
D) four or more
A) one or more
B) two or more
C) three or more
D) four or more
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
18
Skin effect and induction change the resistance in alternating-current (ac) circuits, therefore resistance of a conductor is ____.
A) slightly lower in an ac circuit
B) reciprocally lower in a dc circuit
C) slightly higher in an ac circuit
D) reciprocally higher in a dc circuit
A) slightly lower in an ac circuit
B) reciprocally lower in a dc circuit
C) slightly higher in an ac circuit
D) reciprocally higher in a dc circuit
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
19
Conductors must have ____ and sufficient ampacity to carry the current for the load as calculated.
A) sufficient length
B) adequate insulation
C) adequate mechanical strength
D) definitive markings
A) sufficient length
B) adequate insulation
C) adequate mechanical strength
D) definitive markings
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
20
The maximum distance to any receptacle, measured horizontally along the wall line, is ____ in.
A) 6
B) 12
C) 18
D) 24
A) 6
B) 12
C) 18
D) 24
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
21
A single-phase feeder (or branch circuit) conductor will have a total resistance ____ that of one conductor.
A) half
B) twice
C) three times
D) four times
A) half
B) twice
C) three times
D) four times
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
22
The higher the resistance through a conductor, the ____.
A) smaller the voltage drop
B) higher the voltage drop
C) the more stable the current
D) more neutral the offset
A) smaller the voltage drop
B) higher the voltage drop
C) the more stable the current
D) more neutral the offset
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
23
The conductor voltage that is dropped is a percentage of the source voltage and can be calculated by ____.
A) multiplying voltage drop by the source voltage
B) adding voltage drop to the source voltage
C) subtracting voltage drop from the source voltage
D) dividing voltage drop by the source voltage
A) multiplying voltage drop by the source voltage
B) adding voltage drop to the source voltage
C) subtracting voltage drop from the source voltage
D) dividing voltage drop by the source voltage
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
24
The larger the circular mil area of a conductor, the ____.
A) greater the resistance
B) more insulation required
C) more flexible the conductor
D) smaller the resistance
A) greater the resistance
B) more insulation required
C) more flexible the conductor
D) smaller the resistance
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
25
Voltage drop in a single-phase circuit can also be found using the formula ____.
A) Voltage drop =R x L x I/2
B) Voltage drop = 2.46 x R x L x I
C) Voltage drop = 2 x R x L x I
D) Voltage drop = K x L/I
A) Voltage drop =R x L x I/2
B) Voltage drop = 2.46 x R x L x I
C) Voltage drop = 2 x R x L x I
D) Voltage drop = K x L/I
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck