Deck 11: Cable Installation

ملء الشاشة (f)
exit full mode
سؤال
The inner edge of any bend in nonmetallic sheathed cable cannot be less than __________ times the cable diameter.

A) 6
B) 5
C) 4
D) 3
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
Romex is considered to be supported when it passes through bored or punched holes in framing members that are no more than 4 1/2 feet apart.
سؤال
Even though the NEC permits Type NM cable to be used in one- and two-family homes, it may not be approved for use in your area by the AHJ.
سؤال
Which of the following is not a type of nonmetallic sheathed cable?

A) Type NM
B) Type NM-B
C) Type NMC
D) Type NM-U
سؤال
The radius of the curve of the inner bend in Armored Cable must not be less than __________ times the diameter of the cable.

A) 3
B) 4
C) 5
D) 6
سؤال
A 'homerun' may enter a loadcenter through knockouts in the back, sides, top, or bottom of the loadcenter.
سؤال
Type MC cable with an interlocked armor or corrugated sheath cannot be bent to a radius of less than __________ times the external diameter of the metallic sheath.

A) 3
B) 5
C) 7
D) 9
سؤال
The electrician can incorporate waste from rough and finish wiring phases into the jobsite-recycling system.
سؤال
The NEC requires insulated staples to be used when securing and supporting Type NM cable.
سؤال
Romex must be secured at no more than __________ inches from all electrical boxes except a nonmetallic single-gang box.

A) 6"
B) 8"
C) 10"
D) 12"
سؤال
An insulated anti-short fitting required to be installed in the ends of Type AC cable to protect the wires from abrasion is typically called a(n) __________.

A) orange head
B) red head
C) blue devil
D) blue head
سؤال
Cables run along the sides of framing members must be installed at least __________ from the nearest edge of studs, joists, or rafters.

A) 3"
B) 6"
C) 1-1/4"
D) None of the above
سؤال
In attics not accessible by permanent stairs or ladders, Romex run across the top of floor joists within __________ of the scuttle hole must be protected by means such as guard strips.

A) 3'
B) 5'
C) 6'
D) 7'
سؤال
Suspended ceiling grids are permitted by the NEC to support nonmetallic sheathed cables.
سؤال
Romex installed in either a metal or plastic two-gang device box with interior cable clamps, must be secured no more than __________ from the device box.

A) 6"
B) 8"
C) 10"
D) 12"
سؤال
Type MC cable of sizes 14, 12, and 10 AWG must be secured within 12" from every box and then must be supported at intervals not exceeding __________.

A) 4.5'
B) 5'
C) 6'
D) 7'
سؤال
When service entrance cable is used for branch circuits, the only conductor permitted to be bare is the equipment grounding conductor.
سؤال
If a hole is bored into a stud and there is less than 1 1/4" between the edge of the hole and the edge of the stud, a steel plate at least 1/16" thick or a listed and marked steel plate that is less than 1/16" if it still provides equal or greater protection against nail or screw penetration, must be used.
سؤال
In new installations, service entrance cable with an uninsulated conductor (Type SEU) is permitted to be used in branch circuits for an electric range.
سؤال
During the rough-in wiring phase, an electrician always routes cable through floors or ceilings, which provides shorter routes than do perimeter walls.
سؤال
When installing Type MC cable in a house, an anti-short bushing (red head) is required at each end to provide protection for the conductors from the sharp edges of the cable armor.
سؤال
If Type AC is run through a hole in a framing member that has an edge closer than ____________________ inch(es) to the edge of the framing member, it must be protected by a metal plate at least 1/16" thick.
سؤال
The NEC requires at least __________ of free conductor in electrical device boxes for connection to switches and receptacles.

A) 6"
B) 8"
C) 10"
D) 12"
سؤال
Explain the use of running boards in unfinished basements.
سؤال
The maximum distance between supports for a Type NM cable is __________.

A) 3 feet
B) 4 1/2 feet
C) 6 feet
D) 10 feet
سؤال
When installing Romex into a single-gang nonmetallic device box, the cable must be secured no more than __________ from the box.

A) 8"
B) 10"
C) 12"
D) None of the above
سؤال
Which of the following cables are not permitted to be secured directly to the bottom edge of joists in an unfinished basement?

A) 6/2 NM cable
B) 6/3 NM cable
C) 8/2 NM cable
D) 8/3 NM cable
سؤال
Type AC cable must be supported at intervals not exceeding ____________________ feet along the run.
سؤال
Unrolling cable from a coil is very easily done with a device commonly called a __________.

A) spinner
B) roller
C) reel jack
D) fish tape
سؤال
The part of a branch circuit that originates in the loadcenter and provides electrical power to the first electrical box in a circuit is called a __________.

A) ground out
B) home run
C) fly ball
D) strike out
سؤال
Type NM cable is often purchased in __________ foot rolls that are packaged in plastic wrapping or in cardboard boxes.

A) 100
B) 150
C) 250
D) 1000
سؤال
When unrolling cable from a coil, the best way is to pull the cable out of the coil from the __________.

A) outside of the coil
B) inside of the coil
C) underside of the coil
D) None of the above
سؤال
If a cable is placed in a notch in wood studs or other wood framing members, a steel plate at least ____________________ inch thick must be used to protect the cable.
سؤال
Manufacturers of Type NM cable are now color coding their cables. The color typically used for 12 AWG Romex cable is __________.

A) red
B) blue
C) yellow
D) orange
سؤال
Explain why the sheathing of nonmetallic sheathed cable should extend into the device box or beyond the cable clamp approximately 1/4".
سؤال
In single-gang nonmetallic electrical device boxes, at least __________ of the cable sheathing must extend into the box.

A) 1/8"
B) 1/4"
C) 1/2"
D) 3/4"
سؤال
Explain what type of protection must be used when running Romex through bored or punched holes in metal studs.
سؤال
All of the following cable types are typically used in residential wiring except __________.

A) Type NM
B) Type AC
C) Type MI
D) Type MC
سؤال
Where passing through a floor and located on the outside of a wall, nonmetallic sheathed cable must be enclosed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, or Schedule 80 rigid PVC conduit extending at least ____________________ inches above the floor.
سؤال
Electricians commonly refer to Armored Clad Cable as ____________________ cable.
سؤال
Explain why two-wire Romex cable cannot be stapled on edge.
سؤال
Explain why you do not overtighten the clamp of a metal cable connector when securing a cable to an electrical enclosure.
سؤال
Explain what a 'jug handle' is.
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/43
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 11: Cable Installation
1
The inner edge of any bend in nonmetallic sheathed cable cannot be less than __________ times the cable diameter.

A) 6
B) 5
C) 4
D) 3
B
2
Romex is considered to be supported when it passes through bored or punched holes in framing members that are no more than 4 1/2 feet apart.
True
3
Even though the NEC permits Type NM cable to be used in one- and two-family homes, it may not be approved for use in your area by the AHJ.
True
4
Which of the following is not a type of nonmetallic sheathed cable?

A) Type NM
B) Type NM-B
C) Type NMC
D) Type NM-U
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
5
The radius of the curve of the inner bend in Armored Cable must not be less than __________ times the diameter of the cable.

A) 3
B) 4
C) 5
D) 6
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
6
A 'homerun' may enter a loadcenter through knockouts in the back, sides, top, or bottom of the loadcenter.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
7
Type MC cable with an interlocked armor or corrugated sheath cannot be bent to a radius of less than __________ times the external diameter of the metallic sheath.

A) 3
B) 5
C) 7
D) 9
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
8
The electrician can incorporate waste from rough and finish wiring phases into the jobsite-recycling system.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
9
The NEC requires insulated staples to be used when securing and supporting Type NM cable.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
10
Romex must be secured at no more than __________ inches from all electrical boxes except a nonmetallic single-gang box.

A) 6"
B) 8"
C) 10"
D) 12"
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
11
An insulated anti-short fitting required to be installed in the ends of Type AC cable to protect the wires from abrasion is typically called a(n) __________.

A) orange head
B) red head
C) blue devil
D) blue head
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
12
Cables run along the sides of framing members must be installed at least __________ from the nearest edge of studs, joists, or rafters.

A) 3"
B) 6"
C) 1-1/4"
D) None of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
13
In attics not accessible by permanent stairs or ladders, Romex run across the top of floor joists within __________ of the scuttle hole must be protected by means such as guard strips.

A) 3'
B) 5'
C) 6'
D) 7'
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
14
Suspended ceiling grids are permitted by the NEC to support nonmetallic sheathed cables.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
15
Romex installed in either a metal or plastic two-gang device box with interior cable clamps, must be secured no more than __________ from the device box.

A) 6"
B) 8"
C) 10"
D) 12"
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
16
Type MC cable of sizes 14, 12, and 10 AWG must be secured within 12" from every box and then must be supported at intervals not exceeding __________.

A) 4.5'
B) 5'
C) 6'
D) 7'
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
17
When service entrance cable is used for branch circuits, the only conductor permitted to be bare is the equipment grounding conductor.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
18
If a hole is bored into a stud and there is less than 1 1/4" between the edge of the hole and the edge of the stud, a steel plate at least 1/16" thick or a listed and marked steel plate that is less than 1/16" if it still provides equal or greater protection against nail or screw penetration, must be used.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
19
In new installations, service entrance cable with an uninsulated conductor (Type SEU) is permitted to be used in branch circuits for an electric range.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
20
During the rough-in wiring phase, an electrician always routes cable through floors or ceilings, which provides shorter routes than do perimeter walls.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
21
When installing Type MC cable in a house, an anti-short bushing (red head) is required at each end to provide protection for the conductors from the sharp edges of the cable armor.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
22
If Type AC is run through a hole in a framing member that has an edge closer than ____________________ inch(es) to the edge of the framing member, it must be protected by a metal plate at least 1/16" thick.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
23
The NEC requires at least __________ of free conductor in electrical device boxes for connection to switches and receptacles.

A) 6"
B) 8"
C) 10"
D) 12"
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
24
Explain the use of running boards in unfinished basements.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
25
The maximum distance between supports for a Type NM cable is __________.

A) 3 feet
B) 4 1/2 feet
C) 6 feet
D) 10 feet
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
26
When installing Romex into a single-gang nonmetallic device box, the cable must be secured no more than __________ from the box.

A) 8"
B) 10"
C) 12"
D) None of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
27
Which of the following cables are not permitted to be secured directly to the bottom edge of joists in an unfinished basement?

A) 6/2 NM cable
B) 6/3 NM cable
C) 8/2 NM cable
D) 8/3 NM cable
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
28
Type AC cable must be supported at intervals not exceeding ____________________ feet along the run.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
29
Unrolling cable from a coil is very easily done with a device commonly called a __________.

A) spinner
B) roller
C) reel jack
D) fish tape
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
30
The part of a branch circuit that originates in the loadcenter and provides electrical power to the first electrical box in a circuit is called a __________.

A) ground out
B) home run
C) fly ball
D) strike out
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
31
Type NM cable is often purchased in __________ foot rolls that are packaged in plastic wrapping or in cardboard boxes.

A) 100
B) 150
C) 250
D) 1000
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
32
When unrolling cable from a coil, the best way is to pull the cable out of the coil from the __________.

A) outside of the coil
B) inside of the coil
C) underside of the coil
D) None of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
33
If a cable is placed in a notch in wood studs or other wood framing members, a steel plate at least ____________________ inch thick must be used to protect the cable.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
34
Manufacturers of Type NM cable are now color coding their cables. The color typically used for 12 AWG Romex cable is __________.

A) red
B) blue
C) yellow
D) orange
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
35
Explain why the sheathing of nonmetallic sheathed cable should extend into the device box or beyond the cable clamp approximately 1/4".
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
36
In single-gang nonmetallic electrical device boxes, at least __________ of the cable sheathing must extend into the box.

A) 1/8"
B) 1/4"
C) 1/2"
D) 3/4"
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
37
Explain what type of protection must be used when running Romex through bored or punched holes in metal studs.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
38
All of the following cable types are typically used in residential wiring except __________.

A) Type NM
B) Type AC
C) Type MI
D) Type MC
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
39
Where passing through a floor and located on the outside of a wall, nonmetallic sheathed cable must be enclosed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, or Schedule 80 rigid PVC conduit extending at least ____________________ inches above the floor.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
40
Electricians commonly refer to Armored Clad Cable as ____________________ cable.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
41
Explain why two-wire Romex cable cannot be stapled on edge.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
42
Explain why you do not overtighten the clamp of a metal cable connector when securing a cable to an electrical enclosure.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 43 في هذه المجموعة.
فتح الحزمة
k this deck
43
Explain what a 'jug handle' is.