Deck 1: The Legal Requirements

ملء الشاشة (f)
exit full mode
سؤال
An Electrical installation certificate requires a tick against three types of work, they are

A) Minor works, Periodic inspection, Alterations
B) Periodic testing, additions, visual inspection
C) New installations, Alterations, Additions to existing installations
D) Cable colour change, New switches, low energy lamps
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
An Electrical installation certificate requires the due date of the first periodic inspection and test to be recorded by

A) The installer
B) The person carrying out the test
C) The designer
D) The customer
سؤال
Which of the following is a non statutory document

A) EWAR 1989
B) BS 7671
C) ESQCR 2002
D) HASAWA 1974
سؤال
Which sense human sense would be best suited to identifying an incomplete enclosure

A) Smell
B) Hearing
C) Touch
D) Sight
سؤال
High levels of safety must be present when using test leads and probes, which of the following would be suitable

A) Accurate test equipment
B) Finger guards
C) Probes exceeding 4mm
D) Very short leads
سؤال
Which instrument would be used to carry out a test for the continuity of protective bonding conductors

A) A low resistance ohmmeter
B) A continuity tester
C) A high ohmmeter
D) An insulation resistance tester
سؤال
When carrying out a test for protective bonding continuity the test instrument should have a range of

A) 0.2 to 2MΩ
B) 0.01 to 100Ω
C) 2.0 to 20Ω
D) 0.2 to 2.0Ω
سؤال
When carrying out a test on main protective bonding it is important that

A) One end is disconnected
B) The installation is not isolated
C) It is connected at both ends
D) The correct colour test leads are used
سؤال
When carrying out a ring circuit test the end to end resistance for each live conductor is 0.6O and the cpc end to end resistance is 1.0O. The expected value between L and E at each socket after cross connection would be

A) 1.6Ω
B) 0.3Ω
C) 0.4Ω
D) 1.2Ω
سؤال
The minimum permissible insulation resistance value between live conductors and earth on a low voltage lighting circuit is

A) 1.0Ω
B) 1.0mΩ
C) 1.0 MΩ
D) 0.5MΩ
سؤال
State the minimum acceptable insulation resistance test voltage for a circuit supplying equipment at 600v

A) 1000v d.c.
B) 500v d.c.
C) 600v d.c.
D) 250v d.c.
سؤال
Name three special locations identified in BS 7671

A) Caravan park, ice skating rink, room containing a bath or shower
B) Restrictive conductive location, Marina, Construction site
C) Sauna, areas with protective conductor currents, Swimming pool
D) Street lighting, mines and quarries, underground car parks
سؤال
The IP rating specific to finger protection is

A) IPXXB
B) IP2X
C) IPXXD
D) IPX2
سؤال
The minimum IP rating for the cover plate on the top of a motor is

A) IP56
B) IPX2
C) IPX4
D) IP4X
سؤال
The external loop impedance for an installation should be measured at

A) The end of a final circuit
B) The nearest socket outlet
C) The origin of the supply
D) At each socket outlet
سؤال
The maximum Ze expected for a TN-C-S system would be

A) 0.8Ω
B) 0.035Ω
C) 21Ω
D) 0.35Ω
سؤال
Ze should always be measured with the earthing conductor

A) Disconnected from the consumers unit
B) Coiled up
C) Bypassed
D) Connected to the consumers unit
سؤال
A metallic earth return path would be found in a

A) TT system
B) TN-S system
C) TN-C-S system
D) TN-C system
سؤال
The symbol I∆n is used to indicate the

A) Maximum RCD operating current
B) The tripping time of an RCD
C) The type of RCD
D) The current at which the RCD should trip
سؤال
The trip rating of an RCD used for additional protection should be

A) 0.03mA
B) 0.30mA
C) 100mA
D) 0.03A
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/20
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 1: The Legal Requirements
1
An Electrical installation certificate requires a tick against three types of work, they are

A) Minor works, Periodic inspection, Alterations
B) Periodic testing, additions, visual inspection
C) New installations, Alterations, Additions to existing installations
D) Cable colour change, New switches, low energy lamps
C
2
An Electrical installation certificate requires the due date of the first periodic inspection and test to be recorded by

A) The installer
B) The person carrying out the test
C) The designer
D) The customer
C
3
Which of the following is a non statutory document

A) EWAR 1989
B) BS 7671
C) ESQCR 2002
D) HASAWA 1974
B
4
Which sense human sense would be best suited to identifying an incomplete enclosure

A) Smell
B) Hearing
C) Touch
D) Sight
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
5
High levels of safety must be present when using test leads and probes, which of the following would be suitable

A) Accurate test equipment
B) Finger guards
C) Probes exceeding 4mm
D) Very short leads
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
6
Which instrument would be used to carry out a test for the continuity of protective bonding conductors

A) A low resistance ohmmeter
B) A continuity tester
C) A high ohmmeter
D) An insulation resistance tester
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
7
When carrying out a test for protective bonding continuity the test instrument should have a range of

A) 0.2 to 2MΩ
B) 0.01 to 100Ω
C) 2.0 to 20Ω
D) 0.2 to 2.0Ω
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
8
When carrying out a test on main protective bonding it is important that

A) One end is disconnected
B) The installation is not isolated
C) It is connected at both ends
D) The correct colour test leads are used
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
9
When carrying out a ring circuit test the end to end resistance for each live conductor is 0.6O and the cpc end to end resistance is 1.0O. The expected value between L and E at each socket after cross connection would be

A) 1.6Ω
B) 0.3Ω
C) 0.4Ω
D) 1.2Ω
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
10
The minimum permissible insulation resistance value between live conductors and earth on a low voltage lighting circuit is

A) 1.0Ω
B) 1.0mΩ
C) 1.0 MΩ
D) 0.5MΩ
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
11
State the minimum acceptable insulation resistance test voltage for a circuit supplying equipment at 600v

A) 1000v d.c.
B) 500v d.c.
C) 600v d.c.
D) 250v d.c.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
12
Name three special locations identified in BS 7671

A) Caravan park, ice skating rink, room containing a bath or shower
B) Restrictive conductive location, Marina, Construction site
C) Sauna, areas with protective conductor currents, Swimming pool
D) Street lighting, mines and quarries, underground car parks
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
13
The IP rating specific to finger protection is

A) IPXXB
B) IP2X
C) IPXXD
D) IPX2
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
14
The minimum IP rating for the cover plate on the top of a motor is

A) IP56
B) IPX2
C) IPX4
D) IP4X
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
15
The external loop impedance for an installation should be measured at

A) The end of a final circuit
B) The nearest socket outlet
C) The origin of the supply
D) At each socket outlet
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
16
The maximum Ze expected for a TN-C-S system would be

A) 0.8Ω
B) 0.035Ω
C) 21Ω
D) 0.35Ω
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
17
Ze should always be measured with the earthing conductor

A) Disconnected from the consumers unit
B) Coiled up
C) Bypassed
D) Connected to the consumers unit
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
18
A metallic earth return path would be found in a

A) TT system
B) TN-S system
C) TN-C-S system
D) TN-C system
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
19
The symbol I∆n is used to indicate the

A) Maximum RCD operating current
B) The tripping time of an RCD
C) The type of RCD
D) The current at which the RCD should trip
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
20
The trip rating of an RCD used for additional protection should be

A) 0.03mA
B) 0.30mA
C) 100mA
D) 0.03A