Deck 5: Electrical Protection and Safety: Part B

ملء الشاشة (f)
exit full mode
سؤال
For the protection of a large squirrel cage induction motor against single phase normally

A)An over-current relay is used
B)Differential relay is used
C)Directional relay is used
D)Negative sequence current sensitive relay is used
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
The most commonly used method for the protection of three phase feeder is

A)Time graded protection
B)Differential protection
C)Reverse power protection
D)None of the above
سؤال
Which is the pilotless protection method for feeder line ?

A)Differential protection
B)Carrier current protection
C)Time credit protection
D)None of the above
سؤال
Time graded protection of a radial feeder can be achieved by using

A)Definite time relay
B)Inverse time relay
C)Both definite and inverse time relays
D)None of the above
سؤال
Pilot-wire protection scheme is the most economical and provides high speed relaying for

A)Short length of lines upto 15 km
B)Medium length of lives up to 60 km
C)Long length of lines up to 200 km
D)All of the above
سؤال
Problems associated with differential protection is/are

A)Magnetising inrush current
B)Mismatching characteristics of CTs
C)Charge of ratio as a result of tapping
D)All of the above
سؤال
For the protection of transformers, harmonic restraint is used to guard against

A)Magnetising inrush current
B)Unbalanced operation
C)Lightning
D)Switching over-voltage
سؤال
The types of faults that occur in electric motors are

A)Stator
B)Rotor
C)Overload
D)All of the above
سؤال
The main function of under voltage protective device generally employed with a motor starter is to

A)Open the supply circuit on failure of power supply
B)Control the motor voltage
C)Prevent the opening of supply circuit
D)None of the above
سؤال
The bias factor S in unit protection synchronous generators

A)Lies between .05 and .1 pu
B)Is less than .05 pu
C)Lies between .1 to .25 pu
D)Is greater than .025 pu
سؤال
In a balanced voltage pilot wire protection scheme if the pilot circuit gets opened, the relay will

A)Fail to trip on internal faults
B)Trip on full load
C)Trip instantaneously on external faults
D)None of the above
سؤال
In a balanced voltage pilot-wire protection scheme, if the pilot circuit gets shortcircuited, the relay will

A)Fail to trip on internal faults
B)Fail to trip on external faults
C)Trip on full load
D)Trip instantaneously
سؤال
The frequency of carrier in the carrier current pilot scheme is in the range of

A)1 kHz to 10 kHz
B)10 kHz to 25 kHz
C)25 kHz to 50 kHz
D)50 kHz to 500 kHz
سؤال
The frequency of carrier transmitted by microwave pilot is in the range of

A)1000 kHz to 1500 kHz
B)2000 kHz to 5000 kHz
C)900 kHz to 6000 kHz
D)10000 kHz to 15000 kHz
سؤال
In carrier current protection the purpose of the wave trap is for

A)Trapping power frequency waves
B)Trapping high frequency waves entering into generators/ transformer unit
C)Both a and b
D)None of the above
سؤال
As soon as a fault develops in a generator stator, it is essential to suppress field excitation, otherwise

A)Terminal voltage will drop
B)It may lead to loss of synchronism
C)It will continue to supply power to the stator winding fault
D)All of the above
سؤال
Distance protection scheme is preferred over graded lime-lag over-current protection in HV and EHV lines because

A)It is faster in operation
B)It is simple
C)It is cheaper in cost
D)All of the above
سؤال
Requirements of protection power station buildings against direct strokes are

A)Interception
B)Conduction
C). Dissipation
D)All of the above
سؤال
The protection against direct lighting strokes and a high-voltage steep waves is provided by

A)Ground wires
B)Lightning arresters
C)Lightning arresters and ground wires
D)Earthing of neutral
سؤال
For protection of rotating machines against lightning surge .............is used

A)Lightning arrester
B)Capacitor
C)Combination of lightning arrester and a capacitor
D)Lightning conductor and arrester
سؤال
In between the generating station and consumers a number of transformation and switching stations exist, these are called the

A)Switchgears
B)Substations
C)Intermediate substations
D)Transformation stations
سؤال
With large reactance interconnector between two power stations

A)The power stations may fall out of step due to large angular displacement between the power stations
B)Power will be transferred with minimum power losses
C)Power will be transferred with voltage fluctuations and noise
D)None of the above
سؤال
In a isolated neutral system, when a single line to ground fault occurs

A)Persistent arcing grounds will be developed
B)Voltage in the healthy phases rise to full line value causing isolation breakdown
C)The capacitive current in the faulty phase rises to 3 times its normal value
D)All of the above
سؤال
Tap changing transformers are employed for

A)Stepping down the voltage
B)Stepping up the voltage
C)Supplying low-voltage current to instruments
D)Both stepping up and stepping down the voltage
سؤال
Field failure in an alternator occurs due to

A)Failure of exciter
B)Faulty field circuit breaker
C)In rush of large currents
D)Both A and B
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/25
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 5: Electrical Protection and Safety: Part B
1
For the protection of a large squirrel cage induction motor against single phase normally

A)An over-current relay is used
B)Differential relay is used
C)Directional relay is used
D)Negative sequence current sensitive relay is used
Negative sequence current sensitive relay is used
2
The most commonly used method for the protection of three phase feeder is

A)Time graded protection
B)Differential protection
C)Reverse power protection
D)None of the above
Differential protection
3
Which is the pilotless protection method for feeder line ?

A)Differential protection
B)Carrier current protection
C)Time credit protection
D)None of the above
Carrier current protection
4
Time graded protection of a radial feeder can be achieved by using

A)Definite time relay
B)Inverse time relay
C)Both definite and inverse time relays
D)None of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
5
Pilot-wire protection scheme is the most economical and provides high speed relaying for

A)Short length of lines upto 15 km
B)Medium length of lives up to 60 km
C)Long length of lines up to 200 km
D)All of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
6
Problems associated with differential protection is/are

A)Magnetising inrush current
B)Mismatching characteristics of CTs
C)Charge of ratio as a result of tapping
D)All of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
7
For the protection of transformers, harmonic restraint is used to guard against

A)Magnetising inrush current
B)Unbalanced operation
C)Lightning
D)Switching over-voltage
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
8
The types of faults that occur in electric motors are

A)Stator
B)Rotor
C)Overload
D)All of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
9
The main function of under voltage protective device generally employed with a motor starter is to

A)Open the supply circuit on failure of power supply
B)Control the motor voltage
C)Prevent the opening of supply circuit
D)None of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
10
The bias factor S in unit protection synchronous generators

A)Lies between .05 and .1 pu
B)Is less than .05 pu
C)Lies between .1 to .25 pu
D)Is greater than .025 pu
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
11
In a balanced voltage pilot wire protection scheme if the pilot circuit gets opened, the relay will

A)Fail to trip on internal faults
B)Trip on full load
C)Trip instantaneously on external faults
D)None of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
12
In a balanced voltage pilot-wire protection scheme, if the pilot circuit gets shortcircuited, the relay will

A)Fail to trip on internal faults
B)Fail to trip on external faults
C)Trip on full load
D)Trip instantaneously
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
13
The frequency of carrier in the carrier current pilot scheme is in the range of

A)1 kHz to 10 kHz
B)10 kHz to 25 kHz
C)25 kHz to 50 kHz
D)50 kHz to 500 kHz
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
14
The frequency of carrier transmitted by microwave pilot is in the range of

A)1000 kHz to 1500 kHz
B)2000 kHz to 5000 kHz
C)900 kHz to 6000 kHz
D)10000 kHz to 15000 kHz
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
15
In carrier current protection the purpose of the wave trap is for

A)Trapping power frequency waves
B)Trapping high frequency waves entering into generators/ transformer unit
C)Both a and b
D)None of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
16
As soon as a fault develops in a generator stator, it is essential to suppress field excitation, otherwise

A)Terminal voltage will drop
B)It may lead to loss of synchronism
C)It will continue to supply power to the stator winding fault
D)All of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
17
Distance protection scheme is preferred over graded lime-lag over-current protection in HV and EHV lines because

A)It is faster in operation
B)It is simple
C)It is cheaper in cost
D)All of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
18
Requirements of protection power station buildings against direct strokes are

A)Interception
B)Conduction
C). Dissipation
D)All of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
19
The protection against direct lighting strokes and a high-voltage steep waves is provided by

A)Ground wires
B)Lightning arresters
C)Lightning arresters and ground wires
D)Earthing of neutral
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
20
For protection of rotating machines against lightning surge .............is used

A)Lightning arrester
B)Capacitor
C)Combination of lightning arrester and a capacitor
D)Lightning conductor and arrester
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
21
In between the generating station and consumers a number of transformation and switching stations exist, these are called the

A)Switchgears
B)Substations
C)Intermediate substations
D)Transformation stations
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
22
With large reactance interconnector between two power stations

A)The power stations may fall out of step due to large angular displacement between the power stations
B)Power will be transferred with minimum power losses
C)Power will be transferred with voltage fluctuations and noise
D)None of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
23
In a isolated neutral system, when a single line to ground fault occurs

A)Persistent arcing grounds will be developed
B)Voltage in the healthy phases rise to full line value causing isolation breakdown
C)The capacitive current in the faulty phase rises to 3 times its normal value
D)All of the above
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
24
Tap changing transformers are employed for

A)Stepping down the voltage
B)Stepping up the voltage
C)Supplying low-voltage current to instruments
D)Both stepping up and stepping down the voltage
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
25
Field failure in an alternator occurs due to

A)Failure of exciter
B)Faulty field circuit breaker
C)In rush of large currents
D)Both A and B
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
locked card icon
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.