Deck 7: Diagnosis of the Refrigeration System

ملء الشاشة (f)
exit full mode
سؤال
The outlet of the metering device is usually the coolest part of the system under normal operating conditions.
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
During a refrigerant system performance test it is noticed that both high-side and low-side pressure readings are about the same.Which of the following could be the possible cause?

A) A restricted susction line.
B) A faulty compressor.
C) A restricted expansion vave.
D) Moisture contamination.
سؤال
Which of the following could cause very low pressures on the low side of a system equipped with an expansion valve?

A) expansion valve stuck open
B) expansion valve stuck closed
C) compressor valves not sealing
D) compressor clutch inoperative
سؤال
R-134a has the exact same temperature and pressure relationship as R-12.
سؤال
An undercharged system will show which of the following gauge readings?

A) low side, low; high side, low
B) low side, low; high side, high
C) low side, high; high side, low
D) low side, high; high side, high
سؤال
Restricted airflow through the condenser core will result in higher than normal high-side pressures.
سؤال
Poor passenger compartment cooling may be the result of dirt or debris plugging the evaporator core cooling fins.
سؤال
Moisture in a refrigerant system may cause intermittent poor system performance.
سؤال
An R-134a expansion valve system that is properly charged has the following gauge readings,high-side 150 psig and low-side 42 psig and the ambient air temperature is 85°F.Which of the following is the most likely cause?

A) A restricted receiver drier
B) An out of adjustment temperature blend door
C) A restricted condenser
D) A stuck open expansion valve
سؤال
A pressure gauge reading of 26 psig (179 kPa)inside the evaporator of a system using R-134a means the evaporating temperature of the refrigerant is about

A) 25°F (-3.9°C).
B) 30°F (-1.1°C).
C) 35°F (1.7°C).
D) 40°F (4.4°C).
سؤال
On a cycling-clutch system,the desired average temperature of the evaporator should be about 35°F (1.7°C).
سؤال
Technician A says there is a direct relationship between the pressure and temperature of a refrigerant.Technician B says any apparent temperature-pressure relationships in a contaminated system are not valid.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
سؤال
A temperature change at the outlet of a system accumulator indicates the accumulator is restricted.
سؤال
High-side restrictions can cause extremely high temperatures.
سؤال
A manifold and gauge set is attached to an operating air conditioner.The low-side gauge reading is too high and the high-side reading is too low.What could be the problem?

A) refrigerant overcharge
B) insufficient refrigerant
C) defective compressor
D) expansion valve stuck open
سؤال
If the low-side gauge pressure is showing a vacuum,all of the following defects could be the cause,EXCEPT:

A) clogged inlet screen.
B) expansion valve stuck closed.
C) compressor valves worn.
D) moisture in the system.
سؤال
Ice on the evaporator coil is often a normal condition.
سؤال
A refrigerant system with air contamination will still operate properly.
سؤال
While a technician is performing an A/C system performance test,it is determined that the low pressure gauge is reading in the vacuum range.This reading could be caused by:

A) an overcharged refrigerant system.
B) a flooded evaporator
C) a restricted expansion valve
D) service hoses are connected to the incorrect system ports.
سؤال
What could happen if the evaporator pressure becomes too low?

A) Moisture in the system will cause the expansion valve to freeze.
B) Moisture will freeze on the evaporator surface restricting air flow.
C) Liquid refrigerant will damage the compressor.
D) Excessive temperature and pressure extremes will damage the evaporator.
سؤال
<strong>  Technician A says a restriction at point A would cause a high high-side pressure and a low low-side pressure.Technician B says a restriction at B would cause low high-side pressure and low low-side pressure.Who is correct?</strong> A) Technician A only B) Technician B only C) Both A and B D) Neither A nor B <div style=padding-top: 35px>
Technician A says a restriction at point "A" would cause a high high-side pressure and a low low-side pressure.Technician B says a restriction at "B" would cause low high-side pressure and low low-side pressure.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
سؤال
An R-134a expansion valve system that is properly charged has the following gauge readings,high-side 320 psig and low-side 50 psig and the ambient air temperature is 80°F.Which of the following is the most likely cause? Technician A says an air flow restriction through the condenser coud be the cause.Technician B says the refrigerant system coud be overcharged.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
سؤال
On a properly charged R-134a cycling clutch type A/C system theevaporator is icing.Which of the following could be the cause?

A) Restricted orifice tube
B) Restricted suction side line
C) A faulty pressure cycling switch
D) Moisture contamination.
سؤال
O-ring damage could be caused by

A) overtightening.
B) burrs on the fitting.
C) using the wrong type of O-ring.
D) all of the above.
سؤال
What can a defective compressor cause systems pressures to be?
سؤال
On a properly charged R-134a system an A/C performance test indicates both normal high- and low-side pressures,but poor cooling.Which of the following is the most likely cause?

A) Restricted air flow through the condenser.
B) Restricted air flow through the evaporator.
C) A faulty compressor.
D) Moisture contamination.
سؤال
On a vehicle equipped with front and rear A/C dual evaporator system,the front evaporator cools properly,but the rear evaporator is warm.Which of the following is the most likely cause?

A) An overcharged refrigerant system.
B) An undercharged refrigerant system.
C) A stuck open front expansion valve.
D) A stuck open rear expansion valve.
سؤال
What is the primary cause of corrosion in the air-conditioning system?
سؤال
A technician is checking refrigerant system pressures.Both high- and ow-side service ports are located on the A/C compressor.When the compressor is engaged,the high-side pressure instantly goes over 375 psig.What is the most ikely cause of this condition?

A) A resricted expansion valve.
B) A restricted receiver dryer.
C) A faulty cooling fan.
D) A restricted discharge hose.
سؤال
<strong>  Technician A says that at point A the refrigerant should be a low-pressure gas.Technician B says that at point B the refrigerant should be a low-pressure liquid.Who is correct?</strong> A) Technician A only B) Technician B only C) Both A and B D) Neither A nor B <div style=padding-top: 35px>
Technician A says that at point "A" the refrigerant should be a low-pressure gas.Technician B says that at point "B" the refrigerant should be a low-pressure liquid.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
سؤال
What is one method for determining if the internally regulated thermostatic expansion valve is functioning correctly?
سؤال
What are the possible causes of a low-side pressure that is high (45 psig),and a high-side pressure that is low (150 psig)?
سؤال
Which of the following is NOT a symptom of an overcharged air conditioning system?

A) Compressor cycles rapidly when equipped with a cycling-clutch pressure switch
B) Higher than normal high-side pressures
C) Reduced cooling capacity under any load condition
D) Early compressor failure
سؤال
At highway speed the A/C system cools normally,but poorly during around town stop and go driving.What is the most likely case of this condition?

A) A stuck closed engine thermostat.
B) A misadjusted air blend door.
C) An open electronic cooling fan relay.
D) An open high-speed blower relay.
سؤال
What is the real hazard of excessive concentrations of refrigerants in the service area,whether or not they have contacted an open flame?
سؤال
When can R-134a be used in a R-12 system?
سؤال
Technician A says the Delta T method of adjusting the charge levels of the refrigerant system relies on a comparison of the inlet and outlet temperatures of the evaporator.Technician B says systems should always be checked first for refrigerant contamination.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
سؤال
During a refrigerant system performance test the following results are recorded: outside ambient temperature of 90°F,high-side gauge reading of 145 psi and low pressure gauge reading of 14 psi.What is indicated by these results?

A) A restriction on the high side of the refrigerant system.
B) Low refrigerant levels.
C) Normal refrigerant system operation.
D) Faulty refrigerant compressor
سؤال
What may happen if the expansion valve remote bulb is not making contact with the evaporator outlet tube?
سؤال
On a refrigerant system there is heavy frost on the expansion vave inlet and low-side pressure is well below normal.Technician A says that the expansion valve is stuck in the open position could be the cause.Technician B says that a restricted expansion valve inet screan could be the cause.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
سؤال
What effect would an overcharge with refrigerant oil have on a system and how would it be detected?
سؤال
What is the symptom of a refrigerant system that is overcharges with refrigerant?
سؤال
What should you do first before condemning a refrigerant system component?
سؤال
If a refrigerant system is contaminated with moisture what would you expect to see on the low-side and high-side guages?
سؤال
If the refrigerant inside the evaporator is several degrees below 32°F (0°C),what keeps the evaporator from icing?
سؤال
List the probable causes of high pressure on both the low and high sides of an operating air conditioning system.
سؤال
How is a baseline used in a refrigerant system diagnosis test?
سؤال
How does the technician determine whether an excessively low gauge reading is caused by a clogged screen or by moisture in the system?
سؤال
Name some ways in which air could enter the air conditioning system.
سؤال
What effect would a high-side restriction have on a system and how would it be detected?
سؤال
What effect would a low-side restriction have on a system and how would it be detected?
سؤال
What are most restrictions in a refrigerant system are caused by?
سؤال
By comparison what are the different pressure characteristics of R-134a refrigerant compared to R-12 refrigerant?
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/53
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 7: Diagnosis of the Refrigeration System
1
The outlet of the metering device is usually the coolest part of the system under normal operating conditions.
True
2
During a refrigerant system performance test it is noticed that both high-side and low-side pressure readings are about the same.Which of the following could be the possible cause?

A) A restricted susction line.
B) A faulty compressor.
C) A restricted expansion vave.
D) Moisture contamination.
B
3
Which of the following could cause very low pressures on the low side of a system equipped with an expansion valve?

A) expansion valve stuck open
B) expansion valve stuck closed
C) compressor valves not sealing
D) compressor clutch inoperative
B
4
R-134a has the exact same temperature and pressure relationship as R-12.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
5
An undercharged system will show which of the following gauge readings?

A) low side, low; high side, low
B) low side, low; high side, high
C) low side, high; high side, low
D) low side, high; high side, high
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
6
Restricted airflow through the condenser core will result in higher than normal high-side pressures.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
7
Poor passenger compartment cooling may be the result of dirt or debris plugging the evaporator core cooling fins.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
8
Moisture in a refrigerant system may cause intermittent poor system performance.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
9
An R-134a expansion valve system that is properly charged has the following gauge readings,high-side 150 psig and low-side 42 psig and the ambient air temperature is 85°F.Which of the following is the most likely cause?

A) A restricted receiver drier
B) An out of adjustment temperature blend door
C) A restricted condenser
D) A stuck open expansion valve
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
10
A pressure gauge reading of 26 psig (179 kPa)inside the evaporator of a system using R-134a means the evaporating temperature of the refrigerant is about

A) 25°F (-3.9°C).
B) 30°F (-1.1°C).
C) 35°F (1.7°C).
D) 40°F (4.4°C).
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
11
On a cycling-clutch system,the desired average temperature of the evaporator should be about 35°F (1.7°C).
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
12
Technician A says there is a direct relationship between the pressure and temperature of a refrigerant.Technician B says any apparent temperature-pressure relationships in a contaminated system are not valid.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
13
A temperature change at the outlet of a system accumulator indicates the accumulator is restricted.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
14
High-side restrictions can cause extremely high temperatures.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
15
A manifold and gauge set is attached to an operating air conditioner.The low-side gauge reading is too high and the high-side reading is too low.What could be the problem?

A) refrigerant overcharge
B) insufficient refrigerant
C) defective compressor
D) expansion valve stuck open
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
16
If the low-side gauge pressure is showing a vacuum,all of the following defects could be the cause,EXCEPT:

A) clogged inlet screen.
B) expansion valve stuck closed.
C) compressor valves worn.
D) moisture in the system.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
17
Ice on the evaporator coil is often a normal condition.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
18
A refrigerant system with air contamination will still operate properly.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
19
While a technician is performing an A/C system performance test,it is determined that the low pressure gauge is reading in the vacuum range.This reading could be caused by:

A) an overcharged refrigerant system.
B) a flooded evaporator
C) a restricted expansion valve
D) service hoses are connected to the incorrect system ports.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
20
What could happen if the evaporator pressure becomes too low?

A) Moisture in the system will cause the expansion valve to freeze.
B) Moisture will freeze on the evaporator surface restricting air flow.
C) Liquid refrigerant will damage the compressor.
D) Excessive temperature and pressure extremes will damage the evaporator.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
21
<strong>  Technician A says a restriction at point A would cause a high high-side pressure and a low low-side pressure.Technician B says a restriction at B would cause low high-side pressure and low low-side pressure.Who is correct?</strong> A) Technician A only B) Technician B only C) Both A and B D) Neither A nor B
Technician A says a restriction at point "A" would cause a high high-side pressure and a low low-side pressure.Technician B says a restriction at "B" would cause low high-side pressure and low low-side pressure.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
22
An R-134a expansion valve system that is properly charged has the following gauge readings,high-side 320 psig and low-side 50 psig and the ambient air temperature is 80°F.Which of the following is the most likely cause? Technician A says an air flow restriction through the condenser coud be the cause.Technician B says the refrigerant system coud be overcharged.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
23
On a properly charged R-134a cycling clutch type A/C system theevaporator is icing.Which of the following could be the cause?

A) Restricted orifice tube
B) Restricted suction side line
C) A faulty pressure cycling switch
D) Moisture contamination.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
24
O-ring damage could be caused by

A) overtightening.
B) burrs on the fitting.
C) using the wrong type of O-ring.
D) all of the above.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
25
What can a defective compressor cause systems pressures to be?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
26
On a properly charged R-134a system an A/C performance test indicates both normal high- and low-side pressures,but poor cooling.Which of the following is the most likely cause?

A) Restricted air flow through the condenser.
B) Restricted air flow through the evaporator.
C) A faulty compressor.
D) Moisture contamination.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
27
On a vehicle equipped with front and rear A/C dual evaporator system,the front evaporator cools properly,but the rear evaporator is warm.Which of the following is the most likely cause?

A) An overcharged refrigerant system.
B) An undercharged refrigerant system.
C) A stuck open front expansion valve.
D) A stuck open rear expansion valve.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
28
What is the primary cause of corrosion in the air-conditioning system?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
29
A technician is checking refrigerant system pressures.Both high- and ow-side service ports are located on the A/C compressor.When the compressor is engaged,the high-side pressure instantly goes over 375 psig.What is the most ikely cause of this condition?

A) A resricted expansion valve.
B) A restricted receiver dryer.
C) A faulty cooling fan.
D) A restricted discharge hose.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
30
<strong>  Technician A says that at point A the refrigerant should be a low-pressure gas.Technician B says that at point B the refrigerant should be a low-pressure liquid.Who is correct?</strong> A) Technician A only B) Technician B only C) Both A and B D) Neither A nor B
Technician A says that at point "A" the refrigerant should be a low-pressure gas.Technician B says that at point "B" the refrigerant should be a low-pressure liquid.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
31
What is one method for determining if the internally regulated thermostatic expansion valve is functioning correctly?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
32
What are the possible causes of a low-side pressure that is high (45 psig),and a high-side pressure that is low (150 psig)?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
33
Which of the following is NOT a symptom of an overcharged air conditioning system?

A) Compressor cycles rapidly when equipped with a cycling-clutch pressure switch
B) Higher than normal high-side pressures
C) Reduced cooling capacity under any load condition
D) Early compressor failure
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
34
At highway speed the A/C system cools normally,but poorly during around town stop and go driving.What is the most likely case of this condition?

A) A stuck closed engine thermostat.
B) A misadjusted air blend door.
C) An open electronic cooling fan relay.
D) An open high-speed blower relay.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
35
What is the real hazard of excessive concentrations of refrigerants in the service area,whether or not they have contacted an open flame?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
36
When can R-134a be used in a R-12 system?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
37
Technician A says the Delta T method of adjusting the charge levels of the refrigerant system relies on a comparison of the inlet and outlet temperatures of the evaporator.Technician B says systems should always be checked first for refrigerant contamination.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
38
During a refrigerant system performance test the following results are recorded: outside ambient temperature of 90°F,high-side gauge reading of 145 psi and low pressure gauge reading of 14 psi.What is indicated by these results?

A) A restriction on the high side of the refrigerant system.
B) Low refrigerant levels.
C) Normal refrigerant system operation.
D) Faulty refrigerant compressor
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
39
What may happen if the expansion valve remote bulb is not making contact with the evaporator outlet tube?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
40
On a refrigerant system there is heavy frost on the expansion vave inlet and low-side pressure is well below normal.Technician A says that the expansion valve is stuck in the open position could be the cause.Technician B says that a restricted expansion valve inet screan could be the cause.Who is correct?

A) Technician A only
B) Technician B only
C) Both A and B
D) Neither A nor B
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
41
What effect would an overcharge with refrigerant oil have on a system and how would it be detected?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
42
What is the symptom of a refrigerant system that is overcharges with refrigerant?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
43
What should you do first before condemning a refrigerant system component?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
44
If a refrigerant system is contaminated with moisture what would you expect to see on the low-side and high-side guages?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
45
If the refrigerant inside the evaporator is several degrees below 32°F (0°C),what keeps the evaporator from icing?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
46
List the probable causes of high pressure on both the low and high sides of an operating air conditioning system.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
47
How is a baseline used in a refrigerant system diagnosis test?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
48
How does the technician determine whether an excessively low gauge reading is caused by a clogged screen or by moisture in the system?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
49
Name some ways in which air could enter the air conditioning system.
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
50
What effect would a high-side restriction have on a system and how would it be detected?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
51
What effect would a low-side restriction have on a system and how would it be detected?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
52
What are most restrictions in a refrigerant system are caused by?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
53
By comparison what are the different pressure characteristics of R-134a refrigerant compared to R-12 refrigerant?
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.
فتح الحزمة
k this deck
locked card icon
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 53 في هذه المجموعة.