Deck 9: Services and Electrical Equipment

ملء الشاشة (f)
exit full mode
سؤال
The radius of the curve of the inner edge of any bend in service-entrance cable must be at least ____ times the diameter of the cable.

A) two
B) three
C) four
D) five
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
Overhead service conductors, accessible only to pedestrian traffic, must have a minimum ____-ft vertical clearance above finished grade.

A) 6
B) 8
C) 10
D) 12
سؤال
Entrance cables must be supported within ____ in. of every raceway or enclosure connection.

A) 6
B) 12
C) 18
D) 24
سؤال
All switchboards, switchgear, panelboards, distribution boards, and motor control centers must be located ____ and must be protected from damage.

A) in dedicated spaces
B) along bearing walls
C) within crawl spaces
D) inside duct work
سؤال
Underground service conductors are defined as the underground conductors between the service point and the ____ to the service-entrance conductors in a terminal box.

A) first interior branch
B) first point of connection
C) primary junction
D) secondary branch
سؤال
Panelboards include overcurrent devices as well as ____.

A) appliance branches
B) buses
C) main box nuts
D) line splitters
سؤال
The ampere rating of any circuit breaker rated at ____ amperes or less, and 1000 volts or less, must be molded, stamped, etched, or similarly marked into the handle or escutcheon area.

A) 75
B) 100
C) 125
D) 150
سؤال
Circuit breakers and fuses can be connected in parallel provided they are ____.

A) rated at 100 amperes or less
B) installed along the main feeder line
C) rated at 100 amperes or more
D) factory assembled and listed as a unit
سؤال
Although not stipulated in the NEC, some local jurisdictions have adopted ____ for service conductors.

A) specific distance requirements
B) load capacities
C) insulation materials
D) waterproofing standards
سؤال
Type ____ cable can be formed in a gooseneck and taped with a self-sealing weather-resistant thermoplastic.

A) SL
B) ME
C) SE
D) WE
سؤال
Service-entrance and overhead service conductors shall be arranged so that ____.

A) lightening rods will extend above them
B) water shall not enter the service raceway or equipment
C) sealed service head is not exposed
D) the main body is supported by rigid masting
سؤال
Type USE cable used for service laterals can ___.

A) be contained in a raceway
B) be locally grounded
C) emerge aboveground at outside terminations
D) be indirectly buried
سؤال
Conductors must have a vertical clearance of at least ____ ft above the roof surface.

A) 2
B) 4
C) 6
D) 8
سؤال
Working space illumination shall not be ____.

A) controlled by a switch plate
B) applied via a branch circuit
C) controlled by automatic means only
D) located along a bearing wall
سؤال
Voltage between overhead conductors does not exceed ____ volts.

A) 100
B) 200
C) 300
D) 400
سؤال
Wireways are ____ with hinged or removable covers used to house and protect electric wires and cables.

A) service boxes
B) raceways
C) non-metallic sheaths
D) troughs (sheet metal or nonmetallic)
سؤال
Circuit breakers must have a voltage rating (clearly marked) ____ voltage.

A) no more than the nominal system
B) within a predetermined range
C) no less than a predetermined range
D) no less than the nominal system
سؤال
Concrete, brick, or tile walls are recognized as ____.

A) insulated
B) grounded
C) waterproof
D) defacto raceways
سؤال
Panelboards shall be mounted in cabinets, cutout boxes, or identified enclosures and shall be ____.

A) removable
B) drop down
C) dead front
D) metallic
سؤال
Two to ____ circuit breakers or sets of fuses are acceptable as the overcurrent device to provide overload protection.

A) three
B) four
C) six
D) eight
سؤال
A one-family dwelling service disconnecting means must have a minimum rating of ____.

A) 120 amperes, 4-wire
B) 100 amperes, 2-wire
C) 100 amperes, 3-wire
D) 120 amperes, 3-wire
سؤال
Fuseholders for current-limiting fuses must not ____.

A) allow water seepage
B) allow cross-over sparking
C) permit insertion of non-current-limiting fuses
D) permit rewiring
سؤال
Main bonding jumpers and system bonding jumpers must be made of ____ or other corrosion-resistant material.

A) aluminum
B) stainless steel
C) sheathed aluminum
D) copper
سؤال
Cartridge fuses and fuseholders are classified according to ____.

A) voltage and amperage ranges
B) ampere ranges and melt-down
C) wattage or heat capacity
D) voltage ranges
سؤال
Splices in wire-type grounding electrode conductors are acceptable only if by means of irreversible compression-type connectors (listed as grounding and bonding equipment) or by the ____.

A) endothermic welding process
B) exothermic welding process
C) cold fusion
D) hot spark technique
سؤال
Fuses must be plainly marked (by printing on or a label attached to the fuse barrel), showing the following: (1) ampere rating, (2) voltage rating, (3) ____, (4) "current-limiting" where applicable, and (5) the name or trademark of the manufacturer.

A) material capacity
B) interrupting rating if other than 10,000 amperes
C) date of manufacture
D) interrupting rating if other than 1,000 amperes
سؤال
Conductor sizes are expressed in American Wire Gage (AWG) or in ____.

A) circular mils
B) copper gauge units
C) diameter in inches
D) millimeters squared
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/27
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 9: Services and Electrical Equipment
1
The radius of the curve of the inner edge of any bend in service-entrance cable must be at least ____ times the diameter of the cable.

A) two
B) three
C) four
D) five
D
2
Overhead service conductors, accessible only to pedestrian traffic, must have a minimum ____-ft vertical clearance above finished grade.

A) 6
B) 8
C) 10
D) 12
C
3
Entrance cables must be supported within ____ in. of every raceway or enclosure connection.

A) 6
B) 12
C) 18
D) 24
B
4
All switchboards, switchgear, panelboards, distribution boards, and motor control centers must be located ____ and must be protected from damage.

A) in dedicated spaces
B) along bearing walls
C) within crawl spaces
D) inside duct work
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
5
Underground service conductors are defined as the underground conductors between the service point and the ____ to the service-entrance conductors in a terminal box.

A) first interior branch
B) first point of connection
C) primary junction
D) secondary branch
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
6
Panelboards include overcurrent devices as well as ____.

A) appliance branches
B) buses
C) main box nuts
D) line splitters
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
7
The ampere rating of any circuit breaker rated at ____ amperes or less, and 1000 volts or less, must be molded, stamped, etched, or similarly marked into the handle or escutcheon area.

A) 75
B) 100
C) 125
D) 150
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
8
Circuit breakers and fuses can be connected in parallel provided they are ____.

A) rated at 100 amperes or less
B) installed along the main feeder line
C) rated at 100 amperes or more
D) factory assembled and listed as a unit
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
9
Although not stipulated in the NEC, some local jurisdictions have adopted ____ for service conductors.

A) specific distance requirements
B) load capacities
C) insulation materials
D) waterproofing standards
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
10
Type ____ cable can be formed in a gooseneck and taped with a self-sealing weather-resistant thermoplastic.

A) SL
B) ME
C) SE
D) WE
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
11
Service-entrance and overhead service conductors shall be arranged so that ____.

A) lightening rods will extend above them
B) water shall not enter the service raceway or equipment
C) sealed service head is not exposed
D) the main body is supported by rigid masting
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
12
Type USE cable used for service laterals can ___.

A) be contained in a raceway
B) be locally grounded
C) emerge aboveground at outside terminations
D) be indirectly buried
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
13
Conductors must have a vertical clearance of at least ____ ft above the roof surface.

A) 2
B) 4
C) 6
D) 8
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
14
Working space illumination shall not be ____.

A) controlled by a switch plate
B) applied via a branch circuit
C) controlled by automatic means only
D) located along a bearing wall
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
15
Voltage between overhead conductors does not exceed ____ volts.

A) 100
B) 200
C) 300
D) 400
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
16
Wireways are ____ with hinged or removable covers used to house and protect electric wires and cables.

A) service boxes
B) raceways
C) non-metallic sheaths
D) troughs (sheet metal or nonmetallic)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
17
Circuit breakers must have a voltage rating (clearly marked) ____ voltage.

A) no more than the nominal system
B) within a predetermined range
C) no less than a predetermined range
D) no less than the nominal system
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
18
Concrete, brick, or tile walls are recognized as ____.

A) insulated
B) grounded
C) waterproof
D) defacto raceways
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
19
Panelboards shall be mounted in cabinets, cutout boxes, or identified enclosures and shall be ____.

A) removable
B) drop down
C) dead front
D) metallic
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
20
Two to ____ circuit breakers or sets of fuses are acceptable as the overcurrent device to provide overload protection.

A) three
B) four
C) six
D) eight
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
21
A one-family dwelling service disconnecting means must have a minimum rating of ____.

A) 120 amperes, 4-wire
B) 100 amperes, 2-wire
C) 100 amperes, 3-wire
D) 120 amperes, 3-wire
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
22
Fuseholders for current-limiting fuses must not ____.

A) allow water seepage
B) allow cross-over sparking
C) permit insertion of non-current-limiting fuses
D) permit rewiring
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
23
Main bonding jumpers and system bonding jumpers must be made of ____ or other corrosion-resistant material.

A) aluminum
B) stainless steel
C) sheathed aluminum
D) copper
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
24
Cartridge fuses and fuseholders are classified according to ____.

A) voltage and amperage ranges
B) ampere ranges and melt-down
C) wattage or heat capacity
D) voltage ranges
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
25
Splices in wire-type grounding electrode conductors are acceptable only if by means of irreversible compression-type connectors (listed as grounding and bonding equipment) or by the ____.

A) endothermic welding process
B) exothermic welding process
C) cold fusion
D) hot spark technique
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
26
Fuses must be plainly marked (by printing on or a label attached to the fuse barrel), showing the following: (1) ampere rating, (2) voltage rating, (3) ____, (4) "current-limiting" where applicable, and (5) the name or trademark of the manufacturer.

A) material capacity
B) interrupting rating if other than 10,000 amperes
C) date of manufacture
D) interrupting rating if other than 1,000 amperes
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 27 في هذه المجموعة.
فتح الحزمة
k this deck
27
Conductor sizes are expressed in American Wire Gage (AWG) or in ____.