Question 1
Multiple Choice
A(n) ____ minimum vertical clearance is required above finished grade for sidewalks, or from any platform or projection from which overhead conductors (of 150 volts, or less, to ground) might be reached.
Question 2
Multiple Choice
Ground-fault protection that functions to open the service disconnect will afford no protection from faults on the ____ of the protective element.
Question 3
Multiple Choice
Where the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the supply-side bonding jumper shall have an area not less than ____ of the area of the largest ungrounded supply conductor or equivalent area for parallel supply conductors.
Question 4
Multiple Choice
According to the NEC
, live parts of electric equipment operating at 50 to 1000 volts, nominal, shall be guarded against ____ by approved enclosures.
Question 5
Multiple Choice
The alternating current phase arrangement on 3-phase busses are ____ from front to back, top to bottom, or left to right, as viewed from the front of the switchboard, switchgear, or panelboard.
Question 6
Multiple Choice
Vertical wiring clearances apply to ____.
Question 7
Multiple Choice
No secondary overcurrent protection is required for certain transformers 1000 volts, nominal, or less with currents of at least 9 amperes and a maximum primary overcurrent protection of ____.
Question 8
Multiple Choice
The connection between the grounded circuit conductor (neutral) and the equipment grounding conductor at the service is the ____.
Question 9
Multiple Choice
Where rear access is required to work on nonelectrical parts at the back of enclosed equipment, a minimum working space of ____ horizontally is required.
Question 10
Multiple Choice
According to the NEC
, where a panelboard is supplied through a transformer, the overcurrent protection required by 408.36 shall be located on the ____ side of the transformer.
Question 11
Multiple Choice
Equipment rated ____ amperes (or more) and over 6 ft (1.8 m) wide requires an entrance to and egress from the required working space at least 24 in.(610 mm) wide and 6½ ft (2.0 m) high at each end of the working space.