Basic Engineering Circuit Analysis 11th Edition by David Irwin ,Robert Nelms
النسخة 11الرقم المعياري الدولي: 978-1118539293
Basic Engineering Circuit Analysis 11th Edition by David Irwin ,Robert Nelms
النسخة 11الرقم المعياري الدولي: 978-1118539293 تمرين 28
A balanced three-phase source supplies power to three loads:
Load 1: 30 kVA at 0.8 pf lagging
Load 2: 24 kW at 0.6 pf leading
Load 3: unknown
If the line voltage and total complex power at the load are 208 V rms and 60 0° kVA, respectively, find the unknown load.
Load 1: 30 kVA at 0.8 pf lagging
Load 2: 24 kW at 0.6 pf leading
Load 3: unknown
If the line voltage and total complex power at the load are 208 V rms and 60 0° kVA, respectively, find the unknown load.
التوضيح
Consider the expression for
.
Subst...