expand icon
book Basic Engineering Circuit Analysis 11th Edition by David Irwin ,Robert Nelms cover

Basic Engineering Circuit Analysis 11th Edition by David Irwin ,Robert Nelms

النسخة 11الرقم المعياري الدولي: 978-1118539293
book Basic Engineering Circuit Analysis 11th Edition by David Irwin ,Robert Nelms cover

Basic Engineering Circuit Analysis 11th Edition by David Irwin ,Robert Nelms

النسخة 11الرقم المعياري الدولي: 978-1118539293
تمرين 35
A balanced three-phase source supplies power to three loads:
Load 1: 24 kW at 0.8 pf lagging
Load 2: 10 kVA at 0.7 pf leading
Load 3: unknown
If the line voltage at the load is 208 V rms, the magnitude of the total complex power is 41.93 kVA, and the combined power factor at the load is 0.86 lagging, find the unknown load.
التوضيح
موثّق
like image
like image

Consider the expression for
blured image .
blured image Subst...

close menu
Basic Engineering Circuit Analysis 11th Edition by David Irwin ,Robert Nelms
cross icon