Deck 19: Special-Purpose Outletswater Pump, Water Heater
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/21
Play
Full screen (f)
Deck 19: Special-Purpose Outletswater Pump, Water Heater
1
According to NEC 230.7, conductors other than service-entrance conductors are not permitted in the same raceway as the service-entrance conductors. However, what does Exception No. 2 permit?
Exception No. 2 permits load management control conductors that have overcurrent protection to be installed in the service raceway.
2
A disconnect need not be in sight of motor and driven machinery if the disconnect can be ____________________ in the open "OFF" position.
individually locked
3
Water pumps that contain all required starting and protection components and connect directly to the pressure switch with no above-ground controller, are often called ____________________ pumps.
2-wire
2 wire
two-wire
2 wire
two-wire
4
Explain why heating elements in water heaters are frequently rated 250 volts for operation on 240-volt circuits.
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
5
Submersible pump cable supplied with well pump assemblies ____ also suitable for direct burial.
A) is
B) is not
A) is
B) is not
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
6
Motor disconnects are required to be ____.
A) universal (weatherproof) type
B) dual-voltage
C) horsepower-rated
D) listed as motor controllers
A) universal (weatherproof) type
B) dual-voltage
C) horsepower-rated
D) listed as motor controllers
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
7
If a 115/230-volt, dual-voltage motor has a full-load current of 8 amperes at 230 volts, the same motor connected for 115-volt operation will draw ____________________ amperes.
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
8
The Code requirements for standard resistance-type electric water heaters are found in Article 422. Because heat pump water heaters contain a hermetic refrigerant motor compressor, their Code requirements are found in Article ____________________.
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
9
When a non-motor-operated electrical appliance is not marked with its overcurrent protective device rating, NEC 422.11(E) states that the branch circuit overcurrent protection shall be ____.
A) 20 amperes where the appliance rating does not exceed 13.3 amperes
B) calculated using the appliance formula in Chapter 9
C) 150 percent of the appliance rating when over 13.3 amperes
D) both a and c
A) 20 amperes where the appliance rating does not exceed 13.3 amperes
B) calculated using the appliance formula in Chapter 9
C) 150 percent of the appliance rating when over 13.3 amperes
D) both a and c
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
10
Where the values of branch-circuit protection required for motors according to Table 430.52 do not correspond to standard ratings as listed in NEC 240.6, the next ____ rating is permitted to be used.
A) higher
B) lower
C) fuse
D) none of the above
A) higher
B) lower
C) fuse
D) none of the above
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
11
Because a water heater represents a continuous load, the branch circuit must be rated not less than ____ percent of the water heater nameplate rating.
A) 80
B) 100
C) 125
D) 225
A) 80
B) 100
C) 125
D) 225
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
12
An individual motor disconnect must be in sight of the motor controller and must disconnect the controller. The NEC definition of in sight means that the controller must be visible and not more than ____ from the disconnect.
A) 50 ft (15 m)
B) 75 ft (22.5 m)
C) 25 ft (7.5 m)
D) none of the above
A) 50 ft (15 m)
B) 75 ft (22.5 m)
C) 25 ft (7.5 m)
D) none of the above
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
13
Dual-voltage-rated pump motors are rated ____.
A) 115/230
B) 120/240
C) all of the above
D) none of the above
A) 115/230
B) 120/240
C) all of the above
D) none of the above
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
14
Most installations require motor overload protection not to exceed ____________________ of the motor's full-load current rating.
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
15
Should it be required to run a pump's circuit underground for any distance, it is necessary to install Type UF or Type USE cable or ____, and then make up the necessary splices in a listed weatherproof junction box
A) a raceway with suitable conductors
B) connect it to pole lighting standard grounding lugs
C) other cable a minimum of 12 inches deep
D) both a and c
A) a raceway with suitable conductors
B) connect it to pole lighting standard grounding lugs
C) other cable a minimum of 12 inches deep
D) both a and c
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
16
NEC 430.103 requires that a disconnecting means for a motor shall ____ ungrounded conductors.
A) open all
B) open no
A) open all
B) open no
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
17
The NEC permits overcurrent protective devices for individual branch circuits to appliances to be sized up to 150 percent of the appliance ampere rating. However, if the 150 percent sizing does not correspond to a standard size fuse or circuit-breaker, then what size is permitted?
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
18
Briefly explain what is meant by the electric utility program known by all of the following names: "time of day," "time of use," and "off-peak."
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
19
The overload protection for a motor might be thermal overloads (sometimes called ____________________) in the controller, electronic sensing overload devices, built-in thermal protection, or time-delay fuses.
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
20
Article 430 contains requirements for motor installations. The section that requires a motor disconnect to be within sight of the motor or capable of being locked is ____________________.
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck
k this deck
21
UL requires that the power (wattage) input must not exceed ____ percent of the water heater's nameplate rating.
A) 105
B) 110
C) 125
D) 150
A) 105
B) 110
C) 125
D) 150
Unlock Deck
Unlock for access to all 21 flashcards in this deck.
Unlock Deck