Deck 12: General Provisions

Full screen (f)
exit full mode
Question
Branch circuits recognized by Article 210 shall be rated in accordance with the maximum permitted ampere rating or setting of the ____.

A) overcurrent device
B) load
C) receptacle
D) conductor
Use Space or
up arrow
down arrow
to flip the card.
Question
____ receptacles are permitted on a 15-ampere overcurrent protective device.

A) Four
B) Five
C) Ten
D) Twelve
Question
The 6-ft rule applies to _____.

A) both commercial occupancies and dwelling units
B) neither commercial occupancies nor dwelling units
C) commercial occupancies only
D) dwelling units only
Question
Sign and outline lighting outlets must be calculated at a minimum of ____ per required branch circuit.

A) 1000 volt-amperes
B) 1100 volt-amperes
C) 1200 volt-amperes
D) 1500 volt-amperes
Question
For circuits supplying loads consisting of motor-operated utilization equipment (fastened in place with a motor larger than 1.8 hp) in combination with other loads, the total calculated load must be based on ____% of the largest motor load plus the sum of the other loads.

A) 50
B) 75
C) 125
D) 150
Question
A continuous load is defined as a load ____.

A) having the maximum level of current sustained for three hours or more
B) having the maximum level of current sustained for two hours or more
C) on any general purpose receptacle
D) on any dedicated receptacle
Question
Individual moveable showcases can be connected by ____.

A) flexible cord to permanently installed receptacles
B) permanent wiring (contained in a raceway) to a junction box
C) rigid wiring to permanently installed receptacles
D) flexible cord to a power strip
Question
One of two methods for calculating show-window branch-circuit loads is to multiply each receptacle by ____ volt-amperes.

A) 90
B) 120
C) 180
D) 200
Question
Receptacles, connectors, and attachment plugs for showcases must be of a listed grounding type, rated ____.

A) 10 or 15 amperes
B) 10 or 20 amperes
C) 15 or 20 amperes
D) 20 or 25 amperes
Question
Show-window branch-circuit loads must be calculated either by (a) the unit load per outlet as required by other provisions of 220.14 or (b) at ____ volt-amperes per linear foot.

A) 90
B) 120
C) 180
D) 200
Question
When considering receptacle volt-ampere rating, a single piece of equipment (consisting of four or more receptacles) must be calculated at not less than ____ volt-amperes per receptacle.

A) 40
B) 80
C) 90
D) 120
Question
The supply circuit's calculated load for lighting units that have ballasts or transformers is based on the ____, not on the lamps' total wattage.

A) calculated continuous load
B) total ampere ratings of such units
C) the ampere rating of the ballast
D) the ampere rating on the nameplate
Question
Wall switch-controlled lighting outlets are not required in commercial occupancies, except for ____ containing equipment that requires servicing.

A) attics and underfloor spaces
B) show-window areas
C) adjacent outdoor spaces
D) kitchen areas
Question
In hotel and motel guest rooms and suites, _____ do not require a receptacle.

A) bathrooms
B) hallways
C) kitchenettes
D) bedrooms
Question
In cord-connected showcases, the secondary circuit(s) of each electric-discharge lighting ballast is (are) ____.

A) connected to a wall receptacle
B) limited to the adjacent branch circuit
C) not limited to any number of showcases
D) limited to one showcase
Question
The minimum number of branch circuits is determined from ____ load and the size (or rating) of the circuits used.

A) the average daily
B) the maximum
C) 125% of the maximum
D) the total computed
Question
The disconnecting means for a sign in a commercial or industrial building must be ____ or outline lighting system that it controls.

A) within 10 ft of the sign
B) on the main feeder line to the sign
C) generally accessible to the sign
D) within sight of the sign
Question
Where appliances are unlikely to be used simultaneously, each ____ or fraction thereof (of separate and continuous length) shall be considered one outlet of not less than 180 volt-amperes.

A) 5 ft (1.5 m)
B) 6 ft (1.8 m)
C) 8 ft (2.4 m)
D) 12 ft (3.7 m)
Question
Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum branch-circuit conductor size shall have an allowable ampacity not less than the noncontinuous load plus ____ % of the continuous load.

A) 50
B) 75
C) 125
D) 150
Question
Receptacles on a branch circuit are calculated at ____ per strap.

A) 160 volt-amperes
B) 180 volt-amperes
C) 190 volt-amperes
D) 200 volt-amperes
Question
Heavy-duty lighting track is identified for use exceeding ____ amperes.

A) 10
B) 20
C) 30
D) 40
Question
The ____ for the controlled lighting circuit shall be provided at the location where switches control lighting loads that are supplied by a grounded general-purpose branch circuit serving bathrooms, hallways, stairways, and habitable rooms or occupiable spaces as defined in the applicable building code.

A) junction box
B) panel box
C) terminal lead
D) grounded circuit conductor
Question
A 3-phase, 4-wire, wye-connected power system supplying nonlinear loads may necessitate a design allowing for the possibility of ____ on the neutral conductor.

A) transient arching
B) low harmonic neutral currents
C) excessive heat
D) high harmonic neutral currents
Question
A ballast in a fluorescent exit luminaire shall ____.

A) have GFCI protection
B) have thermal protection
C) not have thermal protection
D) not have GFCI protection
Question
A recessed luminaire not identified for contact with insulation shall have all recessed parts spaced at least ____ from combustible materials.

A) 1/2 in.(13 mm)
B) 1¼ in.(32 mm)
C) 1½ in.(38 mm)
D) 1¾ in.(44 mm)
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/25
auto play flashcards
Play
simple tutorial
Full screen (f)
exit full mode
Deck 12: General Provisions
1
Branch circuits recognized by Article 210 shall be rated in accordance with the maximum permitted ampere rating or setting of the ____.

A) overcurrent device
B) load
C) receptacle
D) conductor
A
2
____ receptacles are permitted on a 15-ampere overcurrent protective device.

A) Four
B) Five
C) Ten
D) Twelve
C
3
The 6-ft rule applies to _____.

A) both commercial occupancies and dwelling units
B) neither commercial occupancies nor dwelling units
C) commercial occupancies only
D) dwelling units only
D
4
Sign and outline lighting outlets must be calculated at a minimum of ____ per required branch circuit.

A) 1000 volt-amperes
B) 1100 volt-amperes
C) 1200 volt-amperes
D) 1500 volt-amperes
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
5
For circuits supplying loads consisting of motor-operated utilization equipment (fastened in place with a motor larger than 1.8 hp) in combination with other loads, the total calculated load must be based on ____% of the largest motor load plus the sum of the other loads.

A) 50
B) 75
C) 125
D) 150
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
6
A continuous load is defined as a load ____.

A) having the maximum level of current sustained for three hours or more
B) having the maximum level of current sustained for two hours or more
C) on any general purpose receptacle
D) on any dedicated receptacle
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
7
Individual moveable showcases can be connected by ____.

A) flexible cord to permanently installed receptacles
B) permanent wiring (contained in a raceway) to a junction box
C) rigid wiring to permanently installed receptacles
D) flexible cord to a power strip
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
8
One of two methods for calculating show-window branch-circuit loads is to multiply each receptacle by ____ volt-amperes.

A) 90
B) 120
C) 180
D) 200
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
9
Receptacles, connectors, and attachment plugs for showcases must be of a listed grounding type, rated ____.

A) 10 or 15 amperes
B) 10 or 20 amperes
C) 15 or 20 amperes
D) 20 or 25 amperes
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
10
Show-window branch-circuit loads must be calculated either by (a) the unit load per outlet as required by other provisions of 220.14 or (b) at ____ volt-amperes per linear foot.

A) 90
B) 120
C) 180
D) 200
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
11
When considering receptacle volt-ampere rating, a single piece of equipment (consisting of four or more receptacles) must be calculated at not less than ____ volt-amperes per receptacle.

A) 40
B) 80
C) 90
D) 120
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
12
The supply circuit's calculated load for lighting units that have ballasts or transformers is based on the ____, not on the lamps' total wattage.

A) calculated continuous load
B) total ampere ratings of such units
C) the ampere rating of the ballast
D) the ampere rating on the nameplate
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
13
Wall switch-controlled lighting outlets are not required in commercial occupancies, except for ____ containing equipment that requires servicing.

A) attics and underfloor spaces
B) show-window areas
C) adjacent outdoor spaces
D) kitchen areas
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
14
In hotel and motel guest rooms and suites, _____ do not require a receptacle.

A) bathrooms
B) hallways
C) kitchenettes
D) bedrooms
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
15
In cord-connected showcases, the secondary circuit(s) of each electric-discharge lighting ballast is (are) ____.

A) connected to a wall receptacle
B) limited to the adjacent branch circuit
C) not limited to any number of showcases
D) limited to one showcase
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
16
The minimum number of branch circuits is determined from ____ load and the size (or rating) of the circuits used.

A) the average daily
B) the maximum
C) 125% of the maximum
D) the total computed
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
17
The disconnecting means for a sign in a commercial or industrial building must be ____ or outline lighting system that it controls.

A) within 10 ft of the sign
B) on the main feeder line to the sign
C) generally accessible to the sign
D) within sight of the sign
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
18
Where appliances are unlikely to be used simultaneously, each ____ or fraction thereof (of separate and continuous length) shall be considered one outlet of not less than 180 volt-amperes.

A) 5 ft (1.5 m)
B) 6 ft (1.8 m)
C) 8 ft (2.4 m)
D) 12 ft (3.7 m)
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
19
Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum branch-circuit conductor size shall have an allowable ampacity not less than the noncontinuous load plus ____ % of the continuous load.

A) 50
B) 75
C) 125
D) 150
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
20
Receptacles on a branch circuit are calculated at ____ per strap.

A) 160 volt-amperes
B) 180 volt-amperes
C) 190 volt-amperes
D) 200 volt-amperes
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
21
Heavy-duty lighting track is identified for use exceeding ____ amperes.

A) 10
B) 20
C) 30
D) 40
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
22
The ____ for the controlled lighting circuit shall be provided at the location where switches control lighting loads that are supplied by a grounded general-purpose branch circuit serving bathrooms, hallways, stairways, and habitable rooms or occupiable spaces as defined in the applicable building code.

A) junction box
B) panel box
C) terminal lead
D) grounded circuit conductor
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
23
A 3-phase, 4-wire, wye-connected power system supplying nonlinear loads may necessitate a design allowing for the possibility of ____ on the neutral conductor.

A) transient arching
B) low harmonic neutral currents
C) excessive heat
D) high harmonic neutral currents
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
24
A ballast in a fluorescent exit luminaire shall ____.

A) have GFCI protection
B) have thermal protection
C) not have thermal protection
D) not have GFCI protection
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
25
A recessed luminaire not identified for contact with insulation shall have all recessed parts spaced at least ____ from combustible materials.

A) 1/2 in.(13 mm)
B) 1¼ in.(32 mm)
C) 1½ in.(38 mm)
D) 1¾ in.(44 mm)
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
locked card icon
Unlock Deck
Unlock for access to all 25 flashcards in this deck.