Deck 17: Venting Plumbing Drainage Systems

Full screen (f)
exit full mode
Question
If aggressive chemicals are present in the drain line, vent piping material must be selected that is compatible with those chemicals.
Use Space or
up arrow
down arrow
to flip the card.
Question
A side vent is a vent connecting to a drain pipe through a fitting at an angle not greater than 45° to the vertical.
Question
Hangers should be selected based solely on cost and type of pipe.
Question
The principal function of the vent system is to

A) transport waste from fixtures to the building drain.
B) siphon water from traps.
C) allow sewer gases to enter the building.
D) provide air circulation.
Question
The ____ is the water in the trap that closes off the pathway for gases to pass from the drainage system into the room.

A) plumbing vent system
B) trap seal
C) main vent
D) trap arm
Question
Cast iron vent pipe run horizontally must be supported at every joint.
Question
Plastic vent pipe run vertically must be supported every 4 feet.
Question
Vent terminals above the roof may be used to support small antennas.
Question
The trap seal keeps sewer gases in the drainage system and prevents them from entering the building.
Question
In general, piping materials suitable for drainage may be used for vents.
Question
Yoke vents can be used on only buildings ten stories or less.
Question
Horizontal runs of copper tubing should be supported every 4 feet.
Question
All horizontal vent piping should be installed so it

A) slopes to drain.
B) is perfectly level.
C) inclines upward at" per foot rise.
D) none of the above.
Question
To prevent siphoning, trap arms should be installed level.
Question
A continuous vent is one that remains open even when fixtures are not being used.
Question
Benefits of a venting system include

A) encouraging aerobic bacteria to thrive and break down sewage.
B) permitting the transport of hazardous gases to the outside.
C) alleviating soap suds problems.
D) all of the above.
Question
Vents should be located under roof overhangs to prevent rain from entering them.
Question
Hangers for horizontal piping should allow for free movement of pipe.
Question
A ____ vent is both a drain line and a vent line.

A) loop
B) circuit
C) wet
D) back
Question
Fixtures that are not vented will not drain properly.
Question
Which of the following is NOT a factor in sizing a vent system?

A) the length of the piping to the open air
B) the sum of the length of all piping in the building
C) the size of the stack to be vented
D) the drainage fixture unit load to be served.
Question
____ are used to secure vertical pipes.

A) Suspension brackets
B) Split-ring hangers
C) Riser clamps
D) Clevis hangers
Question
Which of the following is a prohibited vent type?

A) crown vent
B) local vent
C) main vent
D) relief vent
Question
A ____ is a relief vent installed in high-rise systems to equalize pressures.

A) stack vent
B) side vent
C) yoke vent
D) main vent
Question
A ____ is a vertical vent that is a continuation of the drain which it serves.

A) back vent
B) common vent
C) continuous vent
D) dual vent
Question
The principal vent line in the system is called the ____.

A) side vent
B) relief vent
C) main vent
D) loop vent
Question
Fixtures that are not vented will drain

A) as well as vented fixtures.
B) some of the time.
C) most of the time.
D) erratically, with gurgling sounds and fluctuating water levels.
Question
Which of the following is NOT a factor when selecting chemical vent piping?

A) types of chemicals
B) chemical concentration
C) pressure
D) temperature
Question
The maximum pressure difference permitted at any trap outlet is plus or minus ____ of water column.

A) 1 inch
B) 1 foot
C) 2 inches
D) 2 feet
Question
The hydraulic gradient for a trap arm is ____ per foot.

A) "
B) "
C) "
D) "
Question
Hangers must be able to support piping that is ____ full of water.

A) 25%
B) 50%
C) 75%
D) 100%
Question
A ____ connects one or more individual vents with a vent stack or stack vent.

A) branch vent
B) circuit vent
C) dual vent
D) loop vent
Question
It is important that vent piping be supported adequately to prevent

A) sagging sections that can fill with water and block the vent.
B) pipe from coming apart at joints.
C) problems with leakage at roof flashings.
D) all of the above.
Question
What is the smallest size of vent piping generally permitted by code?

A) 1"
B) 1"
C) 1"
D) 2"
Question
At what intervals must horizontally-installed plastic piping be supported?

A) every 4 feet
B) at ends of branches
C) at changes in direction
D) all of the above
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/35
auto play flashcards
Play
simple tutorial
Full screen (f)
exit full mode
Deck 17: Venting Plumbing Drainage Systems
1
If aggressive chemicals are present in the drain line, vent piping material must be selected that is compatible with those chemicals.
True
2
A side vent is a vent connecting to a drain pipe through a fitting at an angle not greater than 45° to the vertical.
True
3
Hangers should be selected based solely on cost and type of pipe.
False
4
The principal function of the vent system is to

A) transport waste from fixtures to the building drain.
B) siphon water from traps.
C) allow sewer gases to enter the building.
D) provide air circulation.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
5
The ____ is the water in the trap that closes off the pathway for gases to pass from the drainage system into the room.

A) plumbing vent system
B) trap seal
C) main vent
D) trap arm
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
6
Cast iron vent pipe run horizontally must be supported at every joint.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
7
Plastic vent pipe run vertically must be supported every 4 feet.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
8
Vent terminals above the roof may be used to support small antennas.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
9
The trap seal keeps sewer gases in the drainage system and prevents them from entering the building.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
10
In general, piping materials suitable for drainage may be used for vents.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
11
Yoke vents can be used on only buildings ten stories or less.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
12
Horizontal runs of copper tubing should be supported every 4 feet.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
13
All horizontal vent piping should be installed so it

A) slopes to drain.
B) is perfectly level.
C) inclines upward at" per foot rise.
D) none of the above.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
14
To prevent siphoning, trap arms should be installed level.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
15
A continuous vent is one that remains open even when fixtures are not being used.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
16
Benefits of a venting system include

A) encouraging aerobic bacteria to thrive and break down sewage.
B) permitting the transport of hazardous gases to the outside.
C) alleviating soap suds problems.
D) all of the above.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
17
Vents should be located under roof overhangs to prevent rain from entering them.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
18
Hangers for horizontal piping should allow for free movement of pipe.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
19
A ____ vent is both a drain line and a vent line.

A) loop
B) circuit
C) wet
D) back
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
20
Fixtures that are not vented will not drain properly.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
21
Which of the following is NOT a factor in sizing a vent system?

A) the length of the piping to the open air
B) the sum of the length of all piping in the building
C) the size of the stack to be vented
D) the drainage fixture unit load to be served.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
22
____ are used to secure vertical pipes.

A) Suspension brackets
B) Split-ring hangers
C) Riser clamps
D) Clevis hangers
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
23
Which of the following is a prohibited vent type?

A) crown vent
B) local vent
C) main vent
D) relief vent
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
24
A ____ is a relief vent installed in high-rise systems to equalize pressures.

A) stack vent
B) side vent
C) yoke vent
D) main vent
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
25
A ____ is a vertical vent that is a continuation of the drain which it serves.

A) back vent
B) common vent
C) continuous vent
D) dual vent
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
26
The principal vent line in the system is called the ____.

A) side vent
B) relief vent
C) main vent
D) loop vent
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
27
Fixtures that are not vented will drain

A) as well as vented fixtures.
B) some of the time.
C) most of the time.
D) erratically, with gurgling sounds and fluctuating water levels.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
28
Which of the following is NOT a factor when selecting chemical vent piping?

A) types of chemicals
B) chemical concentration
C) pressure
D) temperature
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
29
The maximum pressure difference permitted at any trap outlet is plus or minus ____ of water column.

A) 1 inch
B) 1 foot
C) 2 inches
D) 2 feet
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
30
The hydraulic gradient for a trap arm is ____ per foot.

A) "
B) "
C) "
D) "
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
31
Hangers must be able to support piping that is ____ full of water.

A) 25%
B) 50%
C) 75%
D) 100%
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
32
A ____ connects one or more individual vents with a vent stack or stack vent.

A) branch vent
B) circuit vent
C) dual vent
D) loop vent
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
33
It is important that vent piping be supported adequately to prevent

A) sagging sections that can fill with water and block the vent.
B) pipe from coming apart at joints.
C) problems with leakage at roof flashings.
D) all of the above.
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
34
What is the smallest size of vent piping generally permitted by code?

A) 1"
B) 1"
C) 1"
D) 2"
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
35
At what intervals must horizontally-installed plastic piping be supported?

A) every 4 feet
B) at ends of branches
C) at changes in direction
D) all of the above
Unlock Deck
Unlock for access to all 35 flashcards in this deck.
Unlock Deck
k this deck
locked card icon
Unlock Deck