Deck 6: Determining Branch Circuit, Feeder Circuit, and Service Entrance Requirements
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/40
Play
Full screen (f)
Deck 6: Determining Branch Circuit, Feeder Circuit, and Service Entrance Requirements
1
When doing branch circuit, feeder, and service entrance calculations, one volt-amp equals __________.
A) one joule
B) one watt
C) one ohm
D) one mil
A) one joule
B) one watt
C) one ohm
D) one mil
B
2
A supplemental grounding electrode is a grounding electrode used to 'back-up' a metal water pipe grounding electrode.
True
3
When doing a service entrance calculation, if a residence has four fixed appliances, a demand factor of __________% is applied to the total load of these appliances.
A) 50
B) 75
C) 80
D) 100
A) 50
B) 75
C) 80
D) 100
B
4
A(n) __________ is the circuit conductors between the final overcurrent device and the outlets.
A) open circuit
B) branch circuit
C) feeder circuit
D) service conductor
A) open circuit
B) branch circuit
C) feeder circuit
D) service conductor
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
5
Which of the following areas is included when computing the general lighting load of a house?
A) Open Porches
B) Garages
C) Crawl spaces
D) Finished basements
A) Open Porches
B) Garages
C) Crawl spaces
D) Finished basements
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
6
Which of the following is not permitted to be connected to a small appliance branch circuit?
A) Refrigerator
B) Electric clock
C) Gas stove
D) Kitchen lighting fixture
A) Refrigerator
B) Electric clock
C) Gas stove
D) Kitchen lighting fixture
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
7
Which of the following loads does not require a grounded conductor?
A) 2-wire, 120 volt
B) 3-wire, 120/240 volt
C) 2-wire, 240 volt
D) None of the above
A) 2-wire, 120 volt
B) 3-wire, 120/240 volt
C) 2-wire, 240 volt
D) None of the above
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
8
According to the NEC, the unit load used to calculate the minimum number of general lighting circuits in a dwelling is __________ volt-amperes per square foot.
A) 2
B) 3
C) 4
D) 5
A) 2
B) 3
C) 4
D) 5
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
9
An point on the wiring system at which current it taken to supply electrical equipment is called a receptacle.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
10
All of the following types of branch circuits are found in residential wiring except:
A) general lighting
B) laundry
C) large appliance
D) small appliance
A) general lighting
B) laundry
C) large appliance
D) small appliance
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
11
If cables are bundled together for more than 24" and the total number of current-carrying conductors exceeds __________, the ampacity of the conductors must be derated.
A) 2
B) 3
C) 4
D) 5
A) 2
B) 3
C) 4
D) 5
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
12
When cables or conductors are physically tied, wrapped, or taped together, they are considered to be ______________.
A) bundled
B) messy
C) supported
D) secured
A) bundled
B) messy
C) supported
D) secured
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
13
When doing a service entrance calculation and applying the demand factor to the total load of the general lighting load, the small appliance circuits, and the laundry circuit, the first ___________ volt-amps are computed at 100%
A) 2,000
B) 2,500
C) 3,000
D) 4,000
A) 2,000
B) 2,500
C) 3,000
D) 4,000
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
14
A house with 2,000 square feet of habitable living space will require at least _________ general lighting circuits if 15-ampere circuit breakers are used to provide circuit protection.
A) 3
B) 4
C) 5
D) 6
A) 3
B) 4
C) 5
D) 6
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
15
In a residential wiring, which of the following house areas does not have its power supplied by a small appliance circuit?
A) Bathroom
B) Dining room
C) Kitchen
D) Pantry
A) Bathroom
B) Dining room
C) Kitchen
D) Pantry
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
16
The rating of a panelboard is based on the ampacity of the __________.
A) main breaker
B) buss bar
C) service conductor
D) total amperage of each breaker in the panelboard
A) main breaker
B) buss bar
C) service conductor
D) total amperage of each breaker in the panelboard
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
17
A 200-ampere rated panel is designed and manufactured to accommodate __________ circuits.
A) 30
B) 40
C) 42
D) Could be any of the above
A) 30
B) 40
C) 42
D) Could be any of the above
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
18
The circuit conductors between the service equipment and the final branch circuit overcurrent protection device is a(n) __________.
A) open circuit
B) branch circuit
C) feeder circuit
D) service conductor
A) open circuit
B) branch circuit
C) feeder circuit
D) service conductor
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
19
Kitchen lighting outlets are permitted to be connected to any of the small appliance branch circuits that provide power for the kitchen receptacles.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
20
The minimum service entrance rating for a single-family home permitted by the NEC is __________ amperes.
A) 60
B) 75
C) 100
D) 200
A) 60
B) 75
C) 100
D) 200
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
21
According to NEC Table 310.15(B)(7) in the 2011 NEC, the minimum conductor size for a 200 ampere residential service entrance is _________ CU or _________ AL.
A) 4 AWG; 2 AWG
B) 3 AWG; 1 AWG
C) 2 AWG; 1/0 AWG
D) 2/0 AWG; 4/0 AWG
A) 4 AWG; 2 AWG
B) 3 AWG; 1 AWG
C) 2 AWG; 1/0 AWG
D) 2/0 AWG; 4/0 AWG
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
22
If an electric dryer has a nameplate rating of 4,500 watts, ____________________ watts will be used in the standard method service calculation.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
23
The NEC requires at least ____________________ small appliance circuits be installed in each dwelling unit.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
24
If the total computed load of a residence is 45,840 volt-amperes, the computed amperage of the residence is ____________________ amps.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
25
For the types of branch circuits found in residential wiring, the fuse or circuit breaker size can never be larger than ____________________ amps for a 12 AWG copper conductor.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
26
List at least 5 types of branch circuits found in residential wiring.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
27
Explain when sub-panels are used in residential wiring.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
28
According to Table 310.15(B)(16) in the 2011 NEC, the ampacity for a 3 AWG copper conductor using the 75 degree Celsius column is ____________.
A) 85 amps
B) 95 amps
C) 100 amps
D) 200 amps
A) 85 amps
B) 95 amps
C) 100 amps
D) 200 amps
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
29
The NEC states that the load for a household electric dryer must be computed at ____________________ watts or the nameplate rating, whichever is greater.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
30
A 1900 square foot residence has a general lighting load of ____________________ volt-amperes.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
31
Explain when bathroom lighting is permitted to be connected to the 20-amp rated bathroom branch circuit.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
32
____________________ is the current in amperes that a conductor can carry continuously under certain conditions of use without exceeding its temperature rating.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
33
A household electric range has a rating of 11 kW. When computing the service load, a minimum of ____________________ watts will be used.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
34
The NEC states that each two-wire small appliance circuit shall be computed at ____________________ volt-amperes.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
35
Dividing the total computed load in volt-amperes by the service voltage of ____________________ volts will give the minimum ampacity the service conductors must be rated for.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
36
Another way to calculate the minimum number of general lighting circuits required in a dwelling unit is to divide the total habitable square foot living area by ____________ square feet for 15 amp branch circuits and ______________ square feet for 20 amp branch circuits.
A) 200/300
B) 600/800
C) 750/1000
D) 1500/2000
A) 200/300
B) 600/800
C) 750/1000
D) 1500/2000
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
37
According to NEC Table 310.15(B)(7) in the 2011 NEC, the minimum conductor size for a 300 ampere residential service entrance is _________ CU or _________ AL.
A) 2 AWG; 1/0 AWG
B) 2/0 AWG; 4/0 AWG
C) 250 kcmil ; 350 kcmil
D) 400 kcmil ; 600 kcmil
A) 2 AWG; 1/0 AWG
B) 2/0 AWG; 4/0 AWG
C) 250 kcmil ; 350 kcmil
D) 400 kcmil ; 600 kcmil
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
38
Explain how the electric heating and the air conditioning loads are computed when calculating the total electrical load for a residential service.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
39
____________________ temperature is the temperature of the air that surrounds an object on all sides.
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck
40
According to Table 310.15(B)(16) in the 2011 NEC, the ampacity for a 12 AWG copper conductor using the 60 degree Celsius column is ____________.
A) 20 amps
B) 25 amps
C) 30 amps
D) 40 amps
A) 20 amps
B) 25 amps
C) 30 amps
D) 40 amps
Unlock Deck
Unlock for access to all 40 flashcards in this deck.
Unlock Deck
k this deck

