Deck 20: Special-Purpose Outlets for Ranges, Counter-Mounted Cooking Unit G, and Wall-Mounted Oven F
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/24
Play
Full screen (f)
Deck 20: Special-Purpose Outlets for Ranges, Counter-Mounted Cooking Unit G, and Wall-Mounted Oven F
1
Cord sets rated 30 amperes are usually called ____ cords, and cord sets rated 40, 45, or 50 amperes are called ____ cords.
A) SJT; SJ
B) dryer; range
C) heavy-duty; extra heavy-duty
D) washer; dryer
A) SJT; SJ
B) dryer; range
C) heavy-duty; extra heavy-duty
D) washer; dryer
B
2
Match the following NEMA designations with the range and dryer plug-and-receptacle types they represent.
a.30-ampere, four-wire
b.50-ampere, four-wire
c.30-ampere, three-wire
d.50-ampere, three-wire
NEMA 14-50
a.30-ampere, four-wire
b.50-ampere, four-wire
c.30-ampere, three-wire
d.50-ampere, three-wire
NEMA 14-50
b
3
A feeder or service neutral load can be figured at ____ of the load on the ungrounded conductors for ranges and ovens.
A) 70 percent
B) 80 percent
C) 125 percent
D) none of the above
A) 70 percent
B) 80 percent
C) 125 percent
D) none of the above
C
4
Match the following NEMA designations with the range and dryer plug-and-receptacle types they represent.
a.30-ampere, four-wire
b.50-ampere, four-wire
c.30-ampere, three-wire
d.50-ampere, three-wire
NEMA 14-30
a.30-ampere, four-wire
b.50-ampere, four-wire
c.30-ampere, three-wire
d.50-ampere, three-wire
NEMA 14-30
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
5
Calculate the overcurrent protection needed for a countertop cooking unit rated 7,450 watts, 120/240 volts.
Use nameplate rating per Table 220.55, Note 4.
I = W/E = 7,450/240 = 31.04 amperes
Use nameplate rating per Table 220.55, Note 4.
I = W/E = 7,450/240 = 31.04 amperes
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
6
A(n) ____ is NOT an acceptable disconnecting means for appliances.
A) circuit-breaker in sight of the appliance
B) circuit-breaker or switch capable of being locked in the off position
C) attachment cord and plug
D) horsepower-rated switch
A) circuit-breaker in sight of the appliance
B) circuit-breaker or switch capable of being locked in the off position
C) attachment cord and plug
D) horsepower-rated switch
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
7
When a separate branch-circuit is run to a wall-mounted oven or to a counter-mounted cooking unit, the branch circuit size is based on ____ of the nameplate rating of the appliance.
A) 80 percent
B) 100 percent
C) 125 percent
D) none of the above
A) 80 percent
B) 100 percent
C) 125 percent
D) none of the above
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
8
Unit switches that have a(n) ____________________ are acceptable as the disconnecting means for that appliance.
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
9
NEC ____________________ states that the branch circuit overcurrent protection shall not exceed the rating marked on the appliance.
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
10
For electric ranges that have a computer demand of 8.75 kW or more, the neutral conductor can be reduced to not less than ____________________ percent of the branch-circuit rating but never smaller than ____________________ AWG.
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
11
Match the following NEMA designations with the range and dryer plug-and-receptacle types they represent.
a.30-ampere, four-wire
b.50-ampere, four-wire
c.30-ampere, three-wire
d.50-ampere, three-wire
NEMA 10-30
a.30-ampere, four-wire
b.50-ampere, four-wire
c.30-ampere, three-wire
d.50-ampere, three-wire
NEMA 10-30
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
12
On all types and ratings of receptacles, the grounding blade is ____ than the others to ensure that it makes its connection before the grounded conductors do and breaks its connection after they do (first make-last break).
A) larger
B) more durable
C) longer
D) tarnish-resistant
A) larger
B) more durable
C) longer
D) tarnish-resistant
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
13
For free-standing electric ranges, Table 220.55 permits the ____________________ load to be considerably less than the connected load.
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
14
A "unit switch" used as a disconnecting means for an appliance shall ____.
A) be horsepower-rated
B) interrupt all ungrounded circuit conductors
C) have a NEMA 3R enclosure when installed outdoors
D) both a and b
A) be horsepower-rated
B) interrupt all ungrounded circuit conductors
C) have a NEMA 3R enclosure when installed outdoors
D) both a and b
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
15
Receptacles rated 30 amperes are referred to as ____ receptacles, and receptacles rated 50 amperes are called ____ receptacles.
A) NEMA 30; NEMA 50
B) twist-lock; locking
C) dryer; range
D) none of the above
A) NEMA 30; NEMA 50
B) twist-lock; locking
C) dryer; range
D) none of the above
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
16
For appliances that have no marked maximum overcurrent protection, the branch-circuit overcurrent protection is sized at ____.
A) the maximum amount possible
B) the ampacity of the branch-circuit conductors supplying the appliance
C) 30 amperes maximum
D) none of the above
A) the maximum amount possible
B) the ampacity of the branch-circuit conductors supplying the appliance
C) 30 amperes maximum
D) none of the above
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
17
NEC 422.60(A) requires that an appliance nameplate show ____.
A) the appliance rating in volts and amperes
B) the appliance connected load in volts and watts
C) the appliance branch circuit conductor size
D) either a or b
A) the appliance rating in volts and amperes
B) the appliance connected load in volts and watts
C) the appliance branch circuit conductor size
D) either a or b
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
18
In Table 220.55, what is the rationale for allowing demand factors for electric ranges but not for wall-mounted ovens or individual counter-mounted cooking units?
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
19
According to NEC, the total load of a cord-and-plug connected range or cooktop cannot exceed ____________________ percent of the rating of the branch circuit.
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
20
Name at least two different methods for connecting electric ranges, ovens, and cook tops.
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
21
Match the following NEMA designations with the range and dryer plug-and-receptacle types they represent.
a.30-ampere, four-wire
b.50-ampere, four-wire
c.30-ampere, three-wire
d.50-ampere, three-wire
NEMA 10-50
a.30-ampere, four-wire
b.50-ampere, four-wire
c.30-ampere, three-wire
d.50-ampere, three-wire
NEMA 10-50
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
22
Match the following types of range-dryer terminal and receptacle connectors with the types of conductor they are to be connected to.
a.Phase (hot) conductors
b.Grounded (neutral) conductor
c.Equipment grounding conductor
black/red
a.Phase (hot) conductors
b.Grounded (neutral) conductor
c.Equipment grounding conductor
black/red
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
23
Match the following types of range-dryer terminal and receptacle connectors with the types of conductor they are to be connected to.
a.Phase (hot) conductors
b.Grounded (neutral) conductor
c.Equipment grounding conductor
green
a.Phase (hot) conductors
b.Grounded (neutral) conductor
c.Equipment grounding conductor
green
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck
24
Match the following types of range-dryer terminal and receptacle connectors with the types of conductor they are to be connected to.
a.Phase (hot) conductors
b.Grounded (neutral) conductor
c.Equipment grounding conductor
white
a.Phase (hot) conductors
b.Grounded (neutral) conductor
c.Equipment grounding conductor
white
Unlock Deck
Unlock for access to all 24 flashcards in this deck.
Unlock Deck
k this deck

