Deck 3: Determining the Required Number of Branch Circuits Lighting Outlets Receptacle Outlets

Full screen (f)
exit full mode
Question
A continuous load shall not exceed ____ percent of the rating of the branch circuit.

A) 50
B) 80
C) 100
D) 125
Use Space or
up arrow
down arrow
to flip the card.
Question
In construction of one- and two-family dwellings, the electrical circuits are usually designed by the ____.

A) electrician
B) architect
C) consulting engineer
D) project manager
Question
For continuous loads, the branch-circuit rating, the conductors, and the overcurrent device shall not be less than ____ percent of the rating of the equipment.

A) 75
B) 100
C) 125
D) 150
Question
Most public service commissions require that the voltage for residential services be held to ± ____ percent of the nominal voltage as measured at the service point.

A) three
B) five
C) eight
D) ten
Question
The National Electrical Code requires outdoor receptacles to be ____.

A) AFCI protected
B) GFCI protected
C) on a dedicated circuit
D) b and c
Question
What determines the rating of a branch circuit?

A) Branch-circuit wire size
B) Rating of the overcurrent device
C) Length of the circuit
D) Total number of receptacles
Question
With the exception of ____, the 20-ampere appliance circuits required by NEC are permitted to serve no other loads.

A) clock outlets
B) receptacles that are installed to plug in the cords of gas-fired ranges, ovens, or counter-mounted cooking units
C) receptacles in bathrooms
D) receptacles in a master bedroom
Question
How is track lighting load in residences calculated?

A) It is calculated at 150 volt-amperes per each two feet of track.
B) It is calculated at 60 watts per lighting head.
C) It is considered to be part of the general lighting load of 3 volt-amperes per square foot.
D) The method of calculation varies depending on the type of residence.
Question
Explain the difference between a receptacle and a receptacle outlet .
Question
Calculate the minimum number of 15-ampere lighting branch circuits required in a residence of 1,850 square feet.
Question
What are the outdoor receptacle requirements of a one-family dwelling as specified in NEC 210.52(E)(1) ?
Question
List the two cases where outdoor receptacles are exempt from GFCI protection.
Question
List two cases where receptacles may be installed below countertops.
Question
Which of the following is NOT included when calculating the usable area of a dwelling to compute the required lighting load?

A) living room
B) crawl space
C) unfinished basement
D) powder rooms
Question
The NEC defines a ____ as "the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)."

A) receptacle outlet
B) branch circuit
C) service-entrance conductor
D) feeder
Question
Wall receptacles in a habitable room must be placed so they are no further than ____ feet from any point along the wall.

A) 3
B) 5
C) 6
D) 12
Question
The general lighting load for a dwelling is based on the ____.

A) total number of rooms
B) city ordinance requirements
C) family lifestyle needs
D) square footage of the dwelling
Question
The minimum lighting load requirement for dwelling units is ____ volt-amperes per square ft (0.093 m3).

A) 2
B) 3
C) 5
D) 10
Question
Where there are _________________________ or more on an interior stairway, a wall-switch control of the stairway lighting must be provided on each floor level and any level that has an entryway.
Question
Explain what is meant by a nominal voltage rating.
Question
Match between columns
Premises:
Responses:
False
True
False
True
False
True
False
True
False
True
Question
Receptacles in unfinished basements must be ____________________ protected.
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/22
auto play flashcards
Play
simple tutorial
Full screen (f)
exit full mode
Deck 3: Determining the Required Number of Branch Circuits Lighting Outlets Receptacle Outlets
1
A continuous load shall not exceed ____ percent of the rating of the branch circuit.

A) 50
B) 80
C) 100
D) 125
B
2
In construction of one- and two-family dwellings, the electrical circuits are usually designed by the ____.

A) electrician
B) architect
C) consulting engineer
D) project manager
A
3
For continuous loads, the branch-circuit rating, the conductors, and the overcurrent device shall not be less than ____ percent of the rating of the equipment.

A) 75
B) 100
C) 125
D) 150
C
4
Most public service commissions require that the voltage for residential services be held to ± ____ percent of the nominal voltage as measured at the service point.

A) three
B) five
C) eight
D) ten
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
5
The National Electrical Code requires outdoor receptacles to be ____.

A) AFCI protected
B) GFCI protected
C) on a dedicated circuit
D) b and c
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
6
What determines the rating of a branch circuit?

A) Branch-circuit wire size
B) Rating of the overcurrent device
C) Length of the circuit
D) Total number of receptacles
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
7
With the exception of ____, the 20-ampere appliance circuits required by NEC are permitted to serve no other loads.

A) clock outlets
B) receptacles that are installed to plug in the cords of gas-fired ranges, ovens, or counter-mounted cooking units
C) receptacles in bathrooms
D) receptacles in a master bedroom
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
8
How is track lighting load in residences calculated?

A) It is calculated at 150 volt-amperes per each two feet of track.
B) It is calculated at 60 watts per lighting head.
C) It is considered to be part of the general lighting load of 3 volt-amperes per square foot.
D) The method of calculation varies depending on the type of residence.
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
9
Explain the difference between a receptacle and a receptacle outlet .
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
10
Calculate the minimum number of 15-ampere lighting branch circuits required in a residence of 1,850 square feet.
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
11
What are the outdoor receptacle requirements of a one-family dwelling as specified in NEC 210.52(E)(1) ?
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
12
List the two cases where outdoor receptacles are exempt from GFCI protection.
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
13
List two cases where receptacles may be installed below countertops.
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
14
Which of the following is NOT included when calculating the usable area of a dwelling to compute the required lighting load?

A) living room
B) crawl space
C) unfinished basement
D) powder rooms
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
15
The NEC defines a ____ as "the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)."

A) receptacle outlet
B) branch circuit
C) service-entrance conductor
D) feeder
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
16
Wall receptacles in a habitable room must be placed so they are no further than ____ feet from any point along the wall.

A) 3
B) 5
C) 6
D) 12
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
17
The general lighting load for a dwelling is based on the ____.

A) total number of rooms
B) city ordinance requirements
C) family lifestyle needs
D) square footage of the dwelling
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
18
The minimum lighting load requirement for dwelling units is ____ volt-amperes per square ft (0.093 m3).

A) 2
B) 3
C) 5
D) 10
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
19
Where there are _________________________ or more on an interior stairway, a wall-switch control of the stairway lighting must be provided on each floor level and any level that has an entryway.
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
20
Explain what is meant by a nominal voltage rating.
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
21
Match between columns
Premises:
Responses:
False
True
False
True
False
True
False
True
False
True
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
22
Receptacles in unfinished basements must be ____________________ protected.
Unlock Deck
Unlock for access to all 22 flashcards in this deck.
Unlock Deck
k this deck
locked card icon
Unlock Deck
Unlock for access to all 22 flashcards in this deck.