Deck 14: Branch Circuit Installation

Full screen (f)
exit full mode
Question
The receptacle installed for a clothes washing machine located in a laundry area of an unfinished basement or a bathroom must be GFCI protected.
Use Space or
up arrow
down arrow
to flip the card.
Question
A receptacle located under a kitchen sink for a cord-and-plug-connected garbage disposal must be GFCI protected.
Question
A(n) __________ circuit breaker has a trip time that gets faster as the fault current flowing through it gets larger.

A) dual-element
B) inverse time
C) plug fuse
D) type S
Question
The NEC permits low-voltage Class 2 doorbell cable to be run next to 120 or 240 volt branch circuits wired with nonmetallic sheathed cable.
Question
HACR is an acronym found on some circuit breakers and stands for 'heating, air conditioning, and ventilation'.
Question
The NEC requires most motor applications to be protected by overload devices sized not more than __________ of the motor's nameplate current rating.

A) 100%
B) 115%
C) 125%
D) 150%
Question
In the NEC, a bathroom is defined as an area that has a basin, a toilet and a __________.

A) urinal
B) tub
C) shower
D) Any of the above
Question
If a counter mounted cooktop unit has a nameplate rating of 7300 watts at 240 volts, the current draw will be __________ amperes.

A) 30.41
B) 41.65
C) 60.83
D) 72.6
Question
In a laundry room, receptacles must be placed so that no point along the wall is more than six feet from a receptacle.
Question
A receptacle for a gas-fired range is permitted to be connected to a small appliance circuit.
Question
Smoke detectors in homes must be hardwired to the electrical system but may have battery backup.
Question
The working space requirements of Section 110.26 in the NEC must be maintained when the disconnecting means for an air conditioning unit on the outside of the house is installed.
Question
A general lighting branch circuit installed in a house and protected by a 15-ampere circuit breaker may be wired with a __________ AWG copper conductor.

A) 14
B) 12
C) 10
D) Any of the above
Question
Electric water heaters must be wired with a three-wire cable because the white conductor in a two-wire cable is not permitted to be used as an ungrounded conductor in this type of installation.
Question
In an electric motor circuit the size of the circuit breaker and the circuit conductors is determined by the __________ of the motor.

A) horsepower rating
B) full load current
C) voltage rating
D) All of the above
Question
Electric ranges installed in houses are typically wired for __________ volt operation.

A) 120
B) 208
C) 240
D) 120/240
Question
There is no maximum number of receptacles allowed on 15, or 20 amp branch circuits in a house but it is suggested that the maximum number of receptacles permitted on a 15-amp rated circuit be no more than 10 and the maximum number of receptacles permitted on a 20-amp rated circuit be no more than __________.

A) 12
B) 13
C) 14
D) 15
Question
The minimum number of small appliance circuits required by the NEC in each house is __________.

A) 1
B) 2
C) 3
D) 4
Question
The NEC requires at least one 15 or 20 amp, 125 volt receptacle in a bathroom and it must be located no more than __________ inches from the edge of the basin.

A) 8"
B) 12"
C) 30"
D) 36"
Question
If a new electric clothes dryer is being installed in a home built before 1996 that has a three-wire cord-and-plug connection, the circuit must be replaced to accept a four-wire cord and plug.
Question
The NEC requires that small appliance branch circuits be protected with ____________________-ampere overcurrent protection devices.
Question
A ____________________-ampere overcurrent protection device is required for a residential general purpose branch circuit wired with a 12 AWG copper conductor.
Question
A(n) _________________________________ is a fuse type that has a time-delay feature built into it and is often used as an overcurrent protection device for electric motor circuits.
Question
When installing a receptacle for a cord and plug connected appliance, the receptacle must be located no more than __________ feet from the appliance.

A) 2
B) 5
C) 6
D) 8
Question
Which table in the NEC is used to determine the maximum rating of the motor short circuit and ground fault protection device (fuse or circuit breaker)?

A) Table 250.66
B) Table 310.104(A)
C) Table 430.52
D) Table 8, Chapter 9
Question
A hot water heating system is sometimes referred to as a(n) __________ heating system.

A) forced air
B) gas
C) electric
D) hydronic
Question
When determining the amount of electric heating to be installed in a house the rule of thumb is to use _______ watts per square foot for each heated area in a house.

A) 10
B) 100
C) 1
D) 50
Question
Who decides whether 15 or 20 amp rated general lighting circuits will be installed in a residential electrical system?

A) The homeowner
B) The architect
C) The electrical contractor
D) The plumber
Question
If an electric water heater is connected to water piping with connections that are designed so the water heater can be quickly and easily removed, a flexible cord and plug connection is allowed.
Question
Which NEC Table will tell you the full load current for a single-phase electric motor?

A) Table 310.15(B)(16)
B) Table 430.248
C) Table 8, Chapter 9
D) Table 430.250
Question
Most residential electric water heaters operate on 240 volts, are wired with 10 AWG conductors, and are protected with a __________-ampere overcurrent protection device.

A) 20
B) 30
C) 40
D) 50
Question
A(n) __________-colored switch cover is used to identify an oil burner safety switch.

A) orange
B) red
C) blue
D) yellow
Question
If an electric clothes dryer has a rating of 6 kW at 120/240 volts, it will draw ____________________ amperes.
Question
While there is no limit to the number of receptacles that can be connected to a general lighting branch circuit, a good rule of thumb is to assign each receptacle outlet a value of ____________________ amperes.
Question
Instead of installing the required bathroom receptacle on a wall or partition adjacent to the basin, it may be installed on the side or face of the basin cabinet, as long as it is located no more than __________ inches below the countertop.

A) 6
B) 12
C) 18
D) 24
Question
Where should carbon monoxide (CO) alarms be mounted?

A) near bedrooms and living areas
B) where occupants where hear the alarm while sleeping
C) on each level of a home and out of reach of children
D) all of the above
Question
On an individual branch circuit where no other items are served by the circuit, an air conditioner load cannot exceed __________ of the branch circuit ampacity.

A) 50%
B) 70%
C) 80%
D) 100%
Question
The NEC requires a laundry circuit to be rated at ____________________ amperes.
Question
A wall-mounted electric oven has a nameplate rating of 9 kW at 240 volts. The rated current is ____________________ amperes.
Question
The chime transformer is used to transform the 120 V residential circuit voltage down to the voltage that a chime system will operate on, usually ____________________ volts.
Question
Explain why some areas of the country have a high number of homes heated by electric heat, while in other parts of the country most homes are heated by oil or gas.
Question
When an installation technique is used that brings the circuit conductors directly to an electrical appliance and then terminates them at the appliance, the appliance is said to be ____________________.
Question
Explain what a carbon monoxide detector does.
Question
Discuss some of the drawbacks to wireless chimes.
Question
Explain how smoke detectors work.
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/45
auto play flashcards
Play
simple tutorial
Full screen (f)
exit full mode
Deck 14: Branch Circuit Installation
1
The receptacle installed for a clothes washing machine located in a laundry area of an unfinished basement or a bathroom must be GFCI protected.
True
2
A receptacle located under a kitchen sink for a cord-and-plug-connected garbage disposal must be GFCI protected.
False
3
A(n) __________ circuit breaker has a trip time that gets faster as the fault current flowing through it gets larger.

A) dual-element
B) inverse time
C) plug fuse
D) type S
B
4
The NEC permits low-voltage Class 2 doorbell cable to be run next to 120 or 240 volt branch circuits wired with nonmetallic sheathed cable.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
5
HACR is an acronym found on some circuit breakers and stands for 'heating, air conditioning, and ventilation'.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
6
The NEC requires most motor applications to be protected by overload devices sized not more than __________ of the motor's nameplate current rating.

A) 100%
B) 115%
C) 125%
D) 150%
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
7
In the NEC, a bathroom is defined as an area that has a basin, a toilet and a __________.

A) urinal
B) tub
C) shower
D) Any of the above
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
8
If a counter mounted cooktop unit has a nameplate rating of 7300 watts at 240 volts, the current draw will be __________ amperes.

A) 30.41
B) 41.65
C) 60.83
D) 72.6
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
9
In a laundry room, receptacles must be placed so that no point along the wall is more than six feet from a receptacle.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
10
A receptacle for a gas-fired range is permitted to be connected to a small appliance circuit.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
11
Smoke detectors in homes must be hardwired to the electrical system but may have battery backup.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
12
The working space requirements of Section 110.26 in the NEC must be maintained when the disconnecting means for an air conditioning unit on the outside of the house is installed.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
13
A general lighting branch circuit installed in a house and protected by a 15-ampere circuit breaker may be wired with a __________ AWG copper conductor.

A) 14
B) 12
C) 10
D) Any of the above
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
14
Electric water heaters must be wired with a three-wire cable because the white conductor in a two-wire cable is not permitted to be used as an ungrounded conductor in this type of installation.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
15
In an electric motor circuit the size of the circuit breaker and the circuit conductors is determined by the __________ of the motor.

A) horsepower rating
B) full load current
C) voltage rating
D) All of the above
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
16
Electric ranges installed in houses are typically wired for __________ volt operation.

A) 120
B) 208
C) 240
D) 120/240
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
17
There is no maximum number of receptacles allowed on 15, or 20 amp branch circuits in a house but it is suggested that the maximum number of receptacles permitted on a 15-amp rated circuit be no more than 10 and the maximum number of receptacles permitted on a 20-amp rated circuit be no more than __________.

A) 12
B) 13
C) 14
D) 15
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
18
The minimum number of small appliance circuits required by the NEC in each house is __________.

A) 1
B) 2
C) 3
D) 4
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
19
The NEC requires at least one 15 or 20 amp, 125 volt receptacle in a bathroom and it must be located no more than __________ inches from the edge of the basin.

A) 8"
B) 12"
C) 30"
D) 36"
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
20
If a new electric clothes dryer is being installed in a home built before 1996 that has a three-wire cord-and-plug connection, the circuit must be replaced to accept a four-wire cord and plug.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
21
The NEC requires that small appliance branch circuits be protected with ____________________-ampere overcurrent protection devices.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
22
A ____________________-ampere overcurrent protection device is required for a residential general purpose branch circuit wired with a 12 AWG copper conductor.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
23
A(n) _________________________________ is a fuse type that has a time-delay feature built into it and is often used as an overcurrent protection device for electric motor circuits.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
24
When installing a receptacle for a cord and plug connected appliance, the receptacle must be located no more than __________ feet from the appliance.

A) 2
B) 5
C) 6
D) 8
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
25
Which table in the NEC is used to determine the maximum rating of the motor short circuit and ground fault protection device (fuse or circuit breaker)?

A) Table 250.66
B) Table 310.104(A)
C) Table 430.52
D) Table 8, Chapter 9
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
26
A hot water heating system is sometimes referred to as a(n) __________ heating system.

A) forced air
B) gas
C) electric
D) hydronic
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
27
When determining the amount of electric heating to be installed in a house the rule of thumb is to use _______ watts per square foot for each heated area in a house.

A) 10
B) 100
C) 1
D) 50
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
28
Who decides whether 15 or 20 amp rated general lighting circuits will be installed in a residential electrical system?

A) The homeowner
B) The architect
C) The electrical contractor
D) The plumber
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
29
If an electric water heater is connected to water piping with connections that are designed so the water heater can be quickly and easily removed, a flexible cord and plug connection is allowed.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
30
Which NEC Table will tell you the full load current for a single-phase electric motor?

A) Table 310.15(B)(16)
B) Table 430.248
C) Table 8, Chapter 9
D) Table 430.250
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
31
Most residential electric water heaters operate on 240 volts, are wired with 10 AWG conductors, and are protected with a __________-ampere overcurrent protection device.

A) 20
B) 30
C) 40
D) 50
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
32
A(n) __________-colored switch cover is used to identify an oil burner safety switch.

A) orange
B) red
C) blue
D) yellow
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
33
If an electric clothes dryer has a rating of 6 kW at 120/240 volts, it will draw ____________________ amperes.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
34
While there is no limit to the number of receptacles that can be connected to a general lighting branch circuit, a good rule of thumb is to assign each receptacle outlet a value of ____________________ amperes.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
35
Instead of installing the required bathroom receptacle on a wall or partition adjacent to the basin, it may be installed on the side or face of the basin cabinet, as long as it is located no more than __________ inches below the countertop.

A) 6
B) 12
C) 18
D) 24
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
36
Where should carbon monoxide (CO) alarms be mounted?

A) near bedrooms and living areas
B) where occupants where hear the alarm while sleeping
C) on each level of a home and out of reach of children
D) all of the above
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
37
On an individual branch circuit where no other items are served by the circuit, an air conditioner load cannot exceed __________ of the branch circuit ampacity.

A) 50%
B) 70%
C) 80%
D) 100%
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
38
The NEC requires a laundry circuit to be rated at ____________________ amperes.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
39
A wall-mounted electric oven has a nameplate rating of 9 kW at 240 volts. The rated current is ____________________ amperes.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
40
The chime transformer is used to transform the 120 V residential circuit voltage down to the voltage that a chime system will operate on, usually ____________________ volts.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
41
Explain why some areas of the country have a high number of homes heated by electric heat, while in other parts of the country most homes are heated by oil or gas.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
42
When an installation technique is used that brings the circuit conductors directly to an electrical appliance and then terminates them at the appliance, the appliance is said to be ____________________.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
43
Explain what a carbon monoxide detector does.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
44
Discuss some of the drawbacks to wireless chimes.
Unlock Deck
Unlock for access to all 45 flashcards in this deck.
Unlock Deck
k this deck
45
Explain how smoke detectors work.