Question
Which of the following could be the reason that the subcooling would be low on an air conditioning system?

A) dirty or blocked condenser coil
B) system operating in low ambient conditions
C) liquid line restriction
D) noncondensable gas in the system
Use Space or
up arrow
down arrow
to flip the card.
Question
Which of the following would be considered noncondensable gas/es in a refrigeration system?

A) nitrogen
B) refrigerant
C) vaporized refrigerant oil
D) air
E) both a and d
Question
If, while troubleshooting an R-410A residential air conditioning system at near design conditions, the operating pressures are found to be 118 psig on the low side and 440 psig on the high side, it is most likely that the system is

A) operating with a dirty air filter
B) operating with a refrigerant overcharge
C) operating with an undercharge of refrigerant
D) operating properly
Question
Which of the following is NOT a condition of the belt being too tight on a blower?

A) bearing damage
B) belt slippage
C) excessive noise
D) excessive belt breakage
Question
Which is NOT a cause for low superheat in an air conditioning system?

A) refrigerant undercharge
B) overfeeding metering device
C) dirty air filters
D) restricted airflow through the evaporator coil
Question
Which type of bearings do most residential fan motors use?

A) ball
B) reed
C) sleeve
D) nylon
Question
Which of the following is a condition of an air conditioning system that is overcharged?

A) increased evaporator superheat
B) reduced evaporator efficiency
C) low operating pressures
D) evaporator coil frosting
Question
To use the electronic leak detector, the system must contain at least some refrigerant. If the system is operating with a small leak, plenty of pressurized refrigerant is left in the system. But if the system is void of refrigerant, it must first be pressurized with __________, to which a trace of refrigerant has been added.

A) halogen
B) hydrogen
C) nitrogen
D) oxygen
Question
If, while troubleshooting a residential central air conditioning system, the technician notices frost on the suction line, what is the most likely problem?

A) dirty air filter
B) defective condenser fan motor
C) dirty condenser
D) high superheat
E) normal operation
Question
Which type of leak detection uses a refrigerant additive charged into the refrigeration system?

A) halide
B) soap bubbles
C) electronic
D) UV leak detection
Question
Which type of leak detection involves burning refrigerant?

A) halide
B) electronic
C) soap bubbles
D) ultraviolet light
Question
If, while troubleshooting an R-22 residential air conditioning system at near design conditions, the operating pressures are found to be 40 psig on the low side and 116 psig on the high side, it is most likely that the system is

A) overcharged
B) operating with a dirty condenser
C) undercharged
D) operating properly
Question
Where is the high-side access port located on most residential central air conditioning systems?

A) discharge line
B) liquid line
C) suction line
D) directly on the compressor high side
Question
Which is NOT a cause of high superheat in an air conditioning system?

A) refrigerant undercharge
B) overfeeding metering device
C) underfeeding metering device
D) excessive airflow through the evaporator coil
Question
Which of the following could be the cause for excessive subcooling in an air conditioning system?

A) dirty or blocked condenser coil
B) defective condenser fan motor
C) system operating in low ambient conditions
D) service panels removed from condensing unit
Question
Most modern residential blower motors are of which type?

A) direct drive
B) belt drive
C) neither a nor b
D) both a and b
Question
Which of the following is NOT a condition of a belt on a blower motor being too loose?

A) reduced air flow
B) belt slippage
C) excessive noise
D) motor overheating
Question
Which of the following is a condition of an air conditioning system that is undercharged?

A) increased possibility of floodback to the compressor
B) higher operating pressures
C) low operating pressures
D) reduced evaporator superheat
Question
If, while troubleshooting an R-22 residential air conditioning system at near design conditions, the operating pressures are found to be 80 psig on the low side and 200 psig on the high side, it is most likely that the system is opperating

A) with a compressor that has leaking valves
B) with a rerigerant overcharge
C) with an overfeeding metering device
D) properly
Question
Residential air conditioning systems have a superheat range of __________ degrees under normal operating conditions.

A) 8 to 12
B) 6 to 10
C) 10 to 15
D) 1 to 5
Question
List three common ways by which air can find its way into an air conditioning system.
Question
List four possible fan motor mechanical problems.
Question
Newer, high efficiency air conditioning systems operate with __________ condenser saturation temperatures and pressures than older, standard efficiency systems.

A) higher
B) lower
Question
Arrange the following troubleshooting steps in the correct order.
_____ test the system operation
_____ gather information
_____ verify the complaint
_____ complete the service call
_____ perform a visual inspection
_____ isolate the problem
_____ correct the problem
Question
List three key indicators that pulleys are not aligned properly on blowers.
Question
Halide leak detectors will work only with __________ refrigerants.
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/26
auto play flashcards
Play
simple tutorial
Full screen (f)
exit full mode
Deck 21: Mechanical Troubleshooting
1
Which of the following could be the reason that the subcooling would be low on an air conditioning system?

A) dirty or blocked condenser coil
B) system operating in low ambient conditions
C) liquid line restriction
D) noncondensable gas in the system
A
2
Which of the following would be considered noncondensable gas/es in a refrigeration system?

A) nitrogen
B) refrigerant
C) vaporized refrigerant oil
D) air
E) both a and d
E
3
If, while troubleshooting an R-410A residential air conditioning system at near design conditions, the operating pressures are found to be 118 psig on the low side and 440 psig on the high side, it is most likely that the system is

A) operating with a dirty air filter
B) operating with a refrigerant overcharge
C) operating with an undercharge of refrigerant
D) operating properly
D
4
Which of the following is NOT a condition of the belt being too tight on a blower?

A) bearing damage
B) belt slippage
C) excessive noise
D) excessive belt breakage
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
5
Which is NOT a cause for low superheat in an air conditioning system?

A) refrigerant undercharge
B) overfeeding metering device
C) dirty air filters
D) restricted airflow through the evaporator coil
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
6
Which type of bearings do most residential fan motors use?

A) ball
B) reed
C) sleeve
D) nylon
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
7
Which of the following is a condition of an air conditioning system that is overcharged?

A) increased evaporator superheat
B) reduced evaporator efficiency
C) low operating pressures
D) evaporator coil frosting
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
8
To use the electronic leak detector, the system must contain at least some refrigerant. If the system is operating with a small leak, plenty of pressurized refrigerant is left in the system. But if the system is void of refrigerant, it must first be pressurized with __________, to which a trace of refrigerant has been added.

A) halogen
B) hydrogen
C) nitrogen
D) oxygen
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
9
If, while troubleshooting a residential central air conditioning system, the technician notices frost on the suction line, what is the most likely problem?

A) dirty air filter
B) defective condenser fan motor
C) dirty condenser
D) high superheat
E) normal operation
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
10
Which type of leak detection uses a refrigerant additive charged into the refrigeration system?

A) halide
B) soap bubbles
C) electronic
D) UV leak detection
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
11
Which type of leak detection involves burning refrigerant?

A) halide
B) electronic
C) soap bubbles
D) ultraviolet light
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
12
If, while troubleshooting an R-22 residential air conditioning system at near design conditions, the operating pressures are found to be 40 psig on the low side and 116 psig on the high side, it is most likely that the system is

A) overcharged
B) operating with a dirty condenser
C) undercharged
D) operating properly
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
13
Where is the high-side access port located on most residential central air conditioning systems?

A) discharge line
B) liquid line
C) suction line
D) directly on the compressor high side
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
14
Which is NOT a cause of high superheat in an air conditioning system?

A) refrigerant undercharge
B) overfeeding metering device
C) underfeeding metering device
D) excessive airflow through the evaporator coil
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
15
Which of the following could be the cause for excessive subcooling in an air conditioning system?

A) dirty or blocked condenser coil
B) defective condenser fan motor
C) system operating in low ambient conditions
D) service panels removed from condensing unit
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
16
Most modern residential blower motors are of which type?

A) direct drive
B) belt drive
C) neither a nor b
D) both a and b
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
17
Which of the following is NOT a condition of a belt on a blower motor being too loose?

A) reduced air flow
B) belt slippage
C) excessive noise
D) motor overheating
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
18
Which of the following is a condition of an air conditioning system that is undercharged?

A) increased possibility of floodback to the compressor
B) higher operating pressures
C) low operating pressures
D) reduced evaporator superheat
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
19
If, while troubleshooting an R-22 residential air conditioning system at near design conditions, the operating pressures are found to be 80 psig on the low side and 200 psig on the high side, it is most likely that the system is opperating

A) with a compressor that has leaking valves
B) with a rerigerant overcharge
C) with an overfeeding metering device
D) properly
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
20
Residential air conditioning systems have a superheat range of __________ degrees under normal operating conditions.

A) 8 to 12
B) 6 to 10
C) 10 to 15
D) 1 to 5
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
21
List three common ways by which air can find its way into an air conditioning system.
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
22
List four possible fan motor mechanical problems.
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
23
Newer, high efficiency air conditioning systems operate with __________ condenser saturation temperatures and pressures than older, standard efficiency systems.

A) higher
B) lower
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
24
Arrange the following troubleshooting steps in the correct order.
_____ test the system operation
_____ gather information
_____ verify the complaint
_____ complete the service call
_____ perform a visual inspection
_____ isolate the problem
_____ correct the problem
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
25
List three key indicators that pulleys are not aligned properly on blowers.
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
26
Halide leak detectors will work only with __________ refrigerants.
Unlock Deck
Unlock for access to all 26 flashcards in this deck.
Unlock Deck
k this deck
locked card icon
Unlock Deck
Unlock for access to all 26 flashcards in this deck.