A(n) ____ minimum vertical clearance is required above finished grade for sidewalks, or from any platform or projection from which overhead conductors (of 150 volts, or less, to ground) might be reached.

A) 9-ft (2.7-m)
B) 10-ft (3.0-m)
C) 11-ft (3.3-m)
D) 12-ft (3.7-m)
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
Ground-fault protection that functions to open the service disconnect will afford no protection from faults on the ____ of the protective element.

A) circuit side
B) panel box side
C) underside
D) line side
سؤال
Where the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the supply-side bonding jumper shall have an area not less than ____ of the area of the largest ungrounded supply conductor or equivalent area for parallel supply conductors.

A) 10½%
B) 12½%
C) 15½%
D) 18½%
سؤال
According to the NEC , live parts of electric equipment operating at 50 to 1000 volts, nominal, shall be guarded against ____ by approved enclosures.

A) water damage
B) overvoltage
C) accidental contact
D) phase transformations
سؤال
The alternating current phase arrangement on 3-phase busses are ____ from front to back, top to bottom, or left to right, as viewed from the front of the switchboard, switchgear, or panelboard.

A) A, B, C
B) C, B, A
C) 1, 2, 3
D) 3, 2, 1
سؤال
Vertical wiring clearances apply to ____.

A) commercial services
B) residential services
C) all electrical feeder and service installations
D) dwellings over six stories
سؤال
No secondary overcurrent protection is required for certain transformers 1000 volts, nominal, or less with currents of at least 9 amperes and a maximum primary overcurrent protection of ____.

A) 75%
B) 100%
C) 125%
D) 150%
سؤال
The connection between the grounded circuit conductor (neutral) and the equipment grounding conductor at the service is the ____.

A) main switching lead
B) main bonding jumper
C) central lead
D) transverse bridge
سؤال
Where rear access is required to work on nonelectrical parts at the back of enclosed equipment, a minimum working space of ____ horizontally is required.

A) 20 in.(508 mm)
B) 30 in.(762 mm)
C) 36 in.(914 mm)
D) 40 in.(1 m)
سؤال
According to the NEC , where a panelboard is supplied through a transformer, the overcurrent protection required by 408.36 shall be located on the ____ side of the transformer.

A) top
B) bottom
C) primary
D) secondary
سؤال
Equipment rated ____ amperes (or more) and over 6 ft (1.8 m) wide requires an entrance to and egress from the required working space at least 24 in.(610 mm) wide and 6½ ft (2.0 m) high at each end of the working space.

A) 700
B) 1000
C) 1100
D) 1200
سؤال
Overcurrent protection for transformers over ____ volts, nominal, is required.

A) 300
B) 500
C) 600
D) 1000
سؤال
Service equipment in other than dwelling units shall be legibly marked in the field with the ____.

A) average impedance
B) minimum current
C) maximum available fault current
D) maximum average current
سؤال
A structural ceiling may not ____.

A) contain any wiring
B) contain any lighting
C) be a suspended or drop type
D) contain ductwork
سؤال
A drip loop's lowest point has a minimum vertical clearance of ____.

A) 9 ft (2.7 m)
B) 10 ft (3.0 m)
C) 11 ft (3.3 m)
D) 12 ft (3.7 m)
سؤال
The ____ phase must be that phase having the higher voltage to ground on 3-phase, 4-wire, delta-connected systems.

A) A
B) B
C) C
D) D
سؤال
All panelboards shall have a rating not less than the ____ required for the load calculated in accordance with Part III, IV, or V of Article 220.

A) minimum feeder capacity
B) maximum feeder capacity
C) 50% of maximum feeder capacity
D) 50% of minimum feeder capacity
سؤال
One access means to a working space is permitted where the location provides ____.

A) a continuous and unobstructed exit
B) adequate sprinkler coverage
C) balcony exits
D) adequate overhead clearance
سؤال
Where ungrounded conductors are increased in size for any reason other than as required in 310.15(B) or 310.15(C), wire-type equipment grounding conductors (where installed) shall be increased in size ____, according to the circular mil area of the ungrounded conductors.

A) proportionately
B) inversely
C) directly
D) indirectly
سؤال
A ____ is a large single panel, frame, or assembly of panels with front- or rear-mounted switches, protective devices (overcurrent, etc.), buses, and, usually, instruments.

A) panelboard
B) switchboard
C) circuit cabinet
D) panel cabinet
سؤال
Live generator parts operating at more than ____ volts ac to ground shall not be exposed to accidental contact by unqualified persons.

A) 25
B) 50
C) 75
D) 100
سؤال
The maximum rating for overcurrent protection on a primary unit is ____.

A) 125%
B) 250%
C) 300%
D) 350%
سؤال
All mechanical elements used to terminate a grounding electrode conductor or bonding jumper to a grounding electrode shall be ____.

A) painted
B) waterproof
C) accessible
D) lubricated
سؤال
A system that supplies a ____ and is derived from a transformer rated no more than 1000 volt-amperes does not require a grounding electrode conductor.

A) Class A, EE, AE circuit
B) main branch circuit
C) secondary circuit
D) Class 1, 2, or 3 circuit
سؤال
Premises wiring (system) is defined as ____, including power, lighting, control, and signal circuit wiring together with all their associated hardware, fittings, and wiring devices, both permanently and temporarily installed.

A) interior and exterior wiring
B) interior wiring
C) exterior wiring
D) main service wiring
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/25
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 14: Services Feeders and Equipment
1
A(n) ____ minimum vertical clearance is required above finished grade for sidewalks, or from any platform or projection from which overhead conductors (of 150 volts, or less, to ground) might be reached.

A) 9-ft (2.7-m)
B) 10-ft (3.0-m)
C) 11-ft (3.3-m)
D) 12-ft (3.7-m)
B
2
Ground-fault protection that functions to open the service disconnect will afford no protection from faults on the ____ of the protective element.

A) circuit side
B) panel box side
C) underside
D) line side
D
3
Where the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the supply-side bonding jumper shall have an area not less than ____ of the area of the largest ungrounded supply conductor or equivalent area for parallel supply conductors.

A) 10½%
B) 12½%
C) 15½%
D) 18½%
B
4
According to the NEC , live parts of electric equipment operating at 50 to 1000 volts, nominal, shall be guarded against ____ by approved enclosures.

A) water damage
B) overvoltage
C) accidental contact
D) phase transformations
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
5
The alternating current phase arrangement on 3-phase busses are ____ from front to back, top to bottom, or left to right, as viewed from the front of the switchboard, switchgear, or panelboard.

A) A, B, C
B) C, B, A
C) 1, 2, 3
D) 3, 2, 1
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
6
Vertical wiring clearances apply to ____.

A) commercial services
B) residential services
C) all electrical feeder and service installations
D) dwellings over six stories
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
7
No secondary overcurrent protection is required for certain transformers 1000 volts, nominal, or less with currents of at least 9 amperes and a maximum primary overcurrent protection of ____.

A) 75%
B) 100%
C) 125%
D) 150%
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
8
The connection between the grounded circuit conductor (neutral) and the equipment grounding conductor at the service is the ____.

A) main switching lead
B) main bonding jumper
C) central lead
D) transverse bridge
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
9
Where rear access is required to work on nonelectrical parts at the back of enclosed equipment, a minimum working space of ____ horizontally is required.

A) 20 in.(508 mm)
B) 30 in.(762 mm)
C) 36 in.(914 mm)
D) 40 in.(1 m)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
10
According to the NEC , where a panelboard is supplied through a transformer, the overcurrent protection required by 408.36 shall be located on the ____ side of the transformer.

A) top
B) bottom
C) primary
D) secondary
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
11
Equipment rated ____ amperes (or more) and over 6 ft (1.8 m) wide requires an entrance to and egress from the required working space at least 24 in.(610 mm) wide and 6½ ft (2.0 m) high at each end of the working space.

A) 700
B) 1000
C) 1100
D) 1200
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
12
Overcurrent protection for transformers over ____ volts, nominal, is required.

A) 300
B) 500
C) 600
D) 1000
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
13
Service equipment in other than dwelling units shall be legibly marked in the field with the ____.

A) average impedance
B) minimum current
C) maximum available fault current
D) maximum average current
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
14
A structural ceiling may not ____.

A) contain any wiring
B) contain any lighting
C) be a suspended or drop type
D) contain ductwork
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
15
A drip loop's lowest point has a minimum vertical clearance of ____.

A) 9 ft (2.7 m)
B) 10 ft (3.0 m)
C) 11 ft (3.3 m)
D) 12 ft (3.7 m)
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
16
The ____ phase must be that phase having the higher voltage to ground on 3-phase, 4-wire, delta-connected systems.

A) A
B) B
C) C
D) D
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
17
All panelboards shall have a rating not less than the ____ required for the load calculated in accordance with Part III, IV, or V of Article 220.

A) minimum feeder capacity
B) maximum feeder capacity
C) 50% of maximum feeder capacity
D) 50% of minimum feeder capacity
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
18
One access means to a working space is permitted where the location provides ____.

A) a continuous and unobstructed exit
B) adequate sprinkler coverage
C) balcony exits
D) adequate overhead clearance
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
19
Where ungrounded conductors are increased in size for any reason other than as required in 310.15(B) or 310.15(C), wire-type equipment grounding conductors (where installed) shall be increased in size ____, according to the circular mil area of the ungrounded conductors.

A) proportionately
B) inversely
C) directly
D) indirectly
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
20
A ____ is a large single panel, frame, or assembly of panels with front- or rear-mounted switches, protective devices (overcurrent, etc.), buses, and, usually, instruments.

A) panelboard
B) switchboard
C) circuit cabinet
D) panel cabinet
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
21
Live generator parts operating at more than ____ volts ac to ground shall not be exposed to accidental contact by unqualified persons.

A) 25
B) 50
C) 75
D) 100
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
22
The maximum rating for overcurrent protection on a primary unit is ____.

A) 125%
B) 250%
C) 300%
D) 350%
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
23
All mechanical elements used to terminate a grounding electrode conductor or bonding jumper to a grounding electrode shall be ____.

A) painted
B) waterproof
C) accessible
D) lubricated
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
24
A system that supplies a ____ and is derived from a transformer rated no more than 1000 volt-amperes does not require a grounding electrode conductor.

A) Class A, EE, AE circuit
B) main branch circuit
C) secondary circuit
D) Class 1, 2, or 3 circuit
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
25
Premises wiring (system) is defined as ____, including power, lighting, control, and signal circuit wiring together with all their associated hardware, fittings, and wiring devices, both permanently and temporarily installed.

A) interior and exterior wiring
B) interior wiring
C) exterior wiring
D) main service wiring
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.
فتح الحزمة
k this deck
locked card icon
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 25 في هذه المجموعة.